Plan Review Notes
Plan Review Notes For Permit 07040087
Permit Number 07040087
Review Stop E
Sequence Number 1
Notes
Date Text
2007-04-15 19:31:48** UNSAT **
  
 ** PLEASE SEE ANY REFERENCES IN PLAN REVIEW NOTES TO
 CHAPTER 1 OF THE FBC ARE THAT WHICH IS ADOPTED BY THE
 CITY OF WEST PALM BEACH.
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLANS AT THIS TIME DO NOT INDICATE ANY CODES. PLEASE
 SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO THE 2004
 FBC FOR ALL TRADES AND THE 2005 NFPA-70. PLEASE KNOW
 THERE ARE CHANGES IN THE FBC WHICH MAY AFFECT DESIGNS
 FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE THE SEAL WHICH IS BEING USED BY THE
 ENGINEER IS NO LONGER VALID IN THE STATE OF FLORIDA.
 PLEASE SEE RULING FROM THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS IN FEB OF 04 WHICH REQUIRED ALL
 SEALS TO CONTAIN THE WORDING OF *LICENSE*. AN EXTENSION
 WAS GIVEN DECEMBER 31ST, 2005 HOWEVER ALL SEALS FOR
 ENGINEERS AFTER THAT DATE MUST USE NEW SEALS. PLEASE
 OBTAIN NEW SEAL.
 FAC 61G15-23.001
 ** THIS IS REQUIRED FOR ALL TRADES AND SHEETS WHETHER
 OR NOT COMMENT IS MADE BY OTHER TRADES.
  
 3) NOTE: PLEASE SEE FS 471.025, AND FAC 61G15-23.002
 WHICH REQUIRES PLANS TO BE SIGNED, DATED AND SEALED BY
 THE ENGINEER.
 PLEASE SEE PLANS APPEAR TO BE SIGNED, WITH *INITIALS*,
 IF THIS IS INDEED THE LEGAL SIGNATURE OF SAID ENGINEER,
 PLEASE SUBMIT, SIGNED, DATED AND SEALED LETTER FOR
 LEGAL SIGNATURE VERIFICATION. THIS WILL BE PLACED IN
 OUR SIGNATURE FILE FOR ANY FUTURE REFERENCE.
 ** PLEASE KNOW THAT THE LETTER WILL BE REQUIRED TO BE
 NOTARIZED WITH CORRECT INFORMATION FOR NOTARY AND
 ORIGINAL SIGNATURE PER FS 117.05
 *THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES.
  
 4) NOTE: PLEASE COMPLETE ELECTRICAL PLANS WITH
 ELECTRICAL AS SHOWN ON REFLECTED CEILING PLANS. PLEASE
 SEE MISSING INFORMATION FOR EXTERIOR LIGHTING, LOAD,
 SIZE AND TYPE OF FIXTURES.
 ONLY SOME SHOWN.
 PLEASE SEE FBC CHAPTER 13, 13-415.2 FOR MAXIMUM
 LIGHTING DENSITIES.
 FBC 106.1.2
  
 5) NOTE: PLEASE INDICATE IN BATHROOMS WITH MULTIPLE
 STALLS AN EMERGENCY BATTERY BACK UP TYPE FIXTURE W/
 BATTERY BACK UP WIRED PER 700.12E.
 LS 101 7.8, 7.9
  
 6) NOTE: PLEASE SEE VALUE FOR COMPLETE SCOPE OF WORK
 SEEMS LOW. PLEASE KNOW THE VALUE FOR WORK MUST INCLUDE
 ALL LABOR, MATERIALS AND EQUIPMENT EVEN IF OWNER
 SUPPLIED.
 FBC 108.3
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]