| Plan Review Notes For Permit 07040078 |
| Permit Number |
07040078 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-04-07 15:36:18 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FACFLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | 1.)SEE HIGHLIGHTED PRODUCT APPROVAL.THE ANCHOR | | | SPACING ON THE INSTALLATION SCHEDULE IS NOT COMPLIANT | | | FOR EITHER CONCRETE OR HOLLOW BLOCK.YOU DO NOT | | | SPECIFY WHICH SUBSTRATE CONDITION EXISTS.SEE ATTACHED | | | SAMPLE INSTALLATION SCHEDULE. | | | | | | 2.)REMOVE THE PHOTOCOPIED ENGINEERING FROM THE MIDDLE | | | OF THE PRODUCT APPROVAL.THIS IS NOT A PART OF THE | | | PRODUCT APPROVAL, AND ENGINEERING IS REQUIRED TO BE | | | SIGNED, SEALED DATED ORIGINALS WHEN SUBMITTED FOR | | | PUBLIC RECORD FS471. | | | | | | 3.)IT IS NOT CLEAR IF THE BUILDING HEIGHT IS 60', THE | | | DESIGN PRESSURE IS 60', OR BOTH. |
|