| 2007-04-21 12:53:27 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| | FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | |
| | 1.)OPENING REFERENCED IN PREVIOUS LIST WAS NOT |
| | REVISED. |
| | |
| | 2.)THIS IS EXPOSURE C.YOU HVE DESIGNED TO 47.2 |
| | EXPOSURE B WORST CASE.THIS IS NOT HIGH ENOUGH FOR |
| | SOME OPENINGS, SUCH AS SOME ON THE END ZONES SUCH AS |
| | OPENING 5.WORST CASE FOR EXPOSURE C, 15' MRH, IS |
| | -57.1.OPENING 5 WOULD REQUIRE 9" SPACING, NOT 12". |
| | |
| | 3.) OPENING 4 REQUIRES USE OF THE 15' CHART, HAS A |
| | MINIMUM REQUIRED DESIGN PRESSURE OF -48.19, SO YOU MUST |
| | USE THE -77PSF CHART.THIS REQUIERS 4" SPACING, NOT |
| | 12". |
| | |
| | 4.)SOME OF THE OPENING SIZES DO NOT ALL CORRELATE |
| | WITH THE FLOOR PLAN; FOR INSTANCE, SEE OPENING 18.ONE |
| | STATES 26X57, ONE IS 26X50. |
| | |
| | 5.)CHECK ALL OPENINGS.OTHER OPENINGS MAY HAVE |
| | INCORRECT ANCHOR SPACING. |
| | |
| | 6.)THERE ARE TWO DIFFERENT FLORIDA STATE PRODUCT |
| | APPROVALS INCLUDED IN THE PACKAGE, ONE EVALUATION |
| | REPORT.INCLUDE ONLY THE FL STATE PA THAT APPLIES TO |
| | THIS JOB. |
| | |