| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} THE ARCHITECTURAL FIRM WHOSE TITLE BLOCK APPEARS ON |
| | THE PLANS, MUST SIGN AND SEAL THE PLAN PER |
| | 481.221(1)(B)FS. ONLY 1 SET SEALED. |
| | |
| | 2} THE AREA OF THE KITCHEN THAT IS BEING EXTENDED MUST |
| | INCLUDE SMALL APPLIANCE CIRCUITS, PLEASE SEE |
| | 210.52(B)(ALL) FOR REQUIREMENTS. PLACE SAME ON PLANS. |
| | |
| | 3} THE NOTE ON SHEET E.1 DOES NOT ADDRESS CIRCUITING |
| | FOR THE NEW BATHROOM. SINCE NO PANEL SCHEDULE HAS BEEN |
| | PROVIDED, PLEASE INCLUDE VERBAGE FROM 210.11(C)(3) IN |
| | THE NOTE, ALSO 210.52(B), CLEAR ENOUGH TO CONVEY THOSE |
| | REQUIREMENTS TO THE CONTRACTOR. |
| | |
| | 4} IF THERE IS WORK TO BE DONE IN THE PANTRY, IT MUST |
| | COMPLY WITH 210.52(B). INDICATE ADDED DEVICES. |
| | |
| | 5} THE DISCONNECTING MEANS /RECEPTACLE FOR THE |
| | WASHER/DRYER IS NOT SHOWN. |
| | |
| | 6} SHEET E.2 IS INCORRECTLY LABLED"1ST FLOOR |
| | LIGHTING". |
| | |
| | 7} INDICATE IF THE PANEL SHOWN IN THE PANTRY IS BEING |
| | ADDED. IF SO PROVIDE A RISER DIAGRAM OF THE SERVICE. |
| | |
| | NOTE:PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL |
| | BE BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE |
| | CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE SEE |
| | ARTICLE. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |