2007-04-19 07:32:50 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE ARCHITECTURAL FIRM WHOSE TITLE BLOCK APPEARS ON
 THE PLANS, MUST SIGN AND SEAL THE PLAN PER
 481.221(1)(B)FS. ONLY 1 SET SEALED.
  
 2} THE AREA OF THE KITCHEN THAT IS BEING EXTENDED MUST
 INCLUDE SMALL APPLIANCE CIRCUITS, PLEASE SEE
 210.52(B)(ALL) FOR REQUIREMENTS. PLACE SAME ON PLANS.
  
 3} THE NOTE ON SHEET E.1 DOES NOT ADDRESS CIRCUITING
 FOR THE NEW BATHROOM. SINCE NO PANEL SCHEDULE HAS BEEN
 PROVIDED, PLEASE INCLUDE VERBAGE FROM 210.11(C)(3) IN
 THE NOTE, ALSO 210.52(B), CLEAR ENOUGH TO CONVEY THOSE
 REQUIREMENTS TO THE CONTRACTOR.
  
 4} IF THERE IS WORK TO BE DONE IN THE PANTRY, IT MUST
 COMPLY WITH 210.52(B). INDICATE ADDED DEVICES.
  
 5} THE DISCONNECTING MEANS /RECEPTACLE FOR THE
 WASHER/DRYER IS NOT SHOWN.
  
 6} SHEET E.2 IS INCORRECTLY LABLED"1ST FLOOR
 LIGHTING".
  
 7} INDICATE IF THE PANEL SHOWN IN THE PANTRY IS BEING
 ADDED. IF SO PROVIDE A RISER DIAGRAM OF THE SERVICE.
  
 NOTE:PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL
 BE BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE
 CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE SEE
 ARTICLE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718