| 2007-10-23 08:59:42 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) MECHANICAL PLAN NEEDS TO BE SIGNED AND SEALED BY THE | | | ENGINEER ON RECORD (EVERETT C. FENNELL) SEE FAC | | | 61G15-23.002. | | | | | | 2) CONDENSER UNIT MODEL NUMBER SHOWING IN THE EQUIPMENT | | | NOTES IS FOR A 4 TON CONDENSER UNIT PLANS STATE ONLY A | | | 1.5 TON SYSTEM IS TO BE INSTALLED, PLEASE CORRECT, SEE | | | FBC 13-607.1.ABC.1.1. | | | | | | 3) AIR HANDLER UNIT MODEL NUMBER SHOWING IN THE | | | EQUIPMENT NOTES CAN NOT BE FOUND ON THE ARI DIRECTORY | | | WEB SITE, PLEASE CORRECT MODEL NUMBER AND SUBMIT THE | | | ARI REFERENCE NUMBER FOR THE A/C SYSTEM, SEE FBC | | | 13-607.1.ABC.3.1.1. | | | | | | 4) SANITARY RISER S/1 ON SHEET MP-1 HAD BEEN RED LINED | | | BY PLUMBING REVIEWER LAST TIME BUT REVISED PLANS MUST | | | SHOW THESE CORRECTIONS WHEN BEING REVISED, PLEASE | | | CORRECT, SEE FBC 106.1.1. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|