Plan Review Notes
Plan Review Notes For Permit 07040043
Permit Number 07040043
Review Stop M
Sequence Number 4
Notes
Date Text
2007-10-23 08:59:42PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) MECHANICAL PLAN NEEDS TO BE SIGNED AND SEALED BY THE
 ENGINEER ON RECORD (EVERETT C. FENNELL) SEE FAC
 61G15-23.002.
  
 2) CONDENSER UNIT MODEL NUMBER SHOWING IN THE EQUIPMENT
 NOTES IS FOR A 4 TON CONDENSER UNIT PLANS STATE ONLY A
 1.5 TON SYSTEM IS TO BE INSTALLED, PLEASE CORRECT, SEE
 FBC 13-607.1.ABC.1.1.
  
 3) AIR HANDLER UNIT MODEL NUMBER SHOWING IN THE
 EQUIPMENT NOTES CAN NOT BE FOUND ON THE ARI DIRECTORY
 WEB SITE, PLEASE CORRECT MODEL NUMBER AND SUBMIT THE
 ARI REFERENCE NUMBER FOR THE A/C SYSTEM, SEE FBC
 13-607.1.ABC.3.1.1.
  
 4) SANITARY RISER S/1 ON SHEET MP-1 HAD BEEN RED LINED
 BY PLUMBING REVIEWER LAST TIME BUT REVISED PLANS MUST
 SHOW THESE CORRECTIONS WHEN BEING REVISED, PLEASE
 CORRECT, SEE FBC 106.1.1.
  
 MECHANICAL PLAN REVIEW BY;