2007-05-31 09:19:48*** DENIED ***
 1) PROVIDE RETURN AIR TO MASTER SUITE, SEE 2004 FBC/R
 M1602.4.
  
 2) THE 12X6" RETURN AIR GRILL APPEARS TO BE TOO SMALL
 FOR A 1.5 TON A/C SYSTEM PLEASE ENLARGE, OR YOU MAY
 SUBMIT MANUFACTURER'S SPECIFICATION'S SHOWING THE
 PRESSURE LOSS FOR THE RETURN AIR GRILL AND MANUAL D
 CALCULATIONS FOR RESIDENTIAL DUCT DESIGN, SEE 2004
 FBC/R M1601.1.
  
 *** 2004 FBC/R M1602.4 BALANCED RETURN AIR MAY BE
 ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS
 SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR
 HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO
 ACHIEVE PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF
 GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND USING AN
 UNRESTRICTED 1-INCH UNDERCUTTING OF DOORS TO ACHIEVE
 PROPER RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET
 THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR
 EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY
 ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.