| Plan Review Notes For Permit 07040043 |
| Permit Number |
07040043 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-05-30 16:51:18 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. | | | | | | 2} THE BATH CIRCUIT MAY NOT FEED OTHER RECEPTACLES . | | | 210.11.(C)(3). | | | | | | 3} THE REFERENCED CODES ARE INCORRECT. NFPA-72 IS 2002 | | | EDITION, 101 IS 2003 EDITION. SEE REFERENCED MATERIAL | | | IN THE 2004 FBC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|