2007-04-11 14:58:47*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON FORM 600A-04R, PER
 2004 FBC 13-600.3.A, (12-8-06 REVISION).
  
 2) REVISED ENERGY CALCULATIONS WILL NEED TO BE SIGNED
 BY OWNER/AGENT ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 3) THE MINIMUM SEER FOR A/C UNITS IS NOW 13 SEER, SEE
 2004 FBC 13-607.1.ABC.3.2.1, PLEASE CORRECT.
  
 4) SEE ENERGY CAL'S LINE 6 IS SHOWING 890 CONDITIONED
 FLOOR AREA, PLANS SHOW ONLY 631 SQUARE FEET, PLEASE
 CORRECT.
  
 5) SEE MECHANICAL PLANS PAGE MP-1, PLEASE PROVIDE FOR
 RETURN AIR BACK TO THE AIR HANDLER UNIT, PLEASE BE
 ADVISED RETURN AIR MAY NOT COME FROM THE BATHROOM, SEE
 2004 FBC/R M1602.2 (4).
  
 6) PLEASE SHOW THE SIZE OF ALL SUPPLY AIR GRILL ON
 MECHANICAL PLANS.
  
 7) MECHANICAL PLANS SHOW A 10 SEER A/C SYSTEM, SEE NOTE
 #3 AND PLEASE CORRECT.
  
 8) PLEASE SEE MECHANICAL PLANS YELLOW HIGH LIGHTED
 SUPPLY AIR DUCTS (FLEX ?) NEED TO SHOW THE SIZE OF THE
 DUCTS.
  
 9) THE PLANS NEED TO BE SIGNED AND SEALED BY THE
 ENGINEER EVERETT C. FENNELL AS HIS INFORMATION IS IN
 THE TITLE BLOCK.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.