| 2007-04-12 14:06:07 | |
| | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK |
| | MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002 |
| | FAC. |
| | |
| | 2} 240.24(D) OVERCURRENT DEVICES SHALL NOT BE LOCATED |
| | IN THE VICINITY OF EASILY IGNITIBLE MATERIAL, SUCH AS |
| | IN CLOTHES CLOSETS.PANEL "A" CANNOT BE LOCATED IN THE |
| | CLOSET. ALSO SEE 408.17 LOCATION RELATIVE TO EASILY |
| | IGNITIBLE MATERIAL. |
| | |
| | 3} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE |
| | PER 210.11(C) (3), SEE CIRCUIT #2 AT 15 AMPS. |
| | |
| | 4} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.1 |
| | RESIDENTIAL FLORIDA BUILDING CODE. ALL 120-VOLT, SINGLE |
| | PHASE, 15- AND 20-AMPERE BRANCH CIRCUITS SUPPLYING |
| | OUTLETS INSTALLED IN DWELLING UNIT BEDROOMS SHALL BE |
| | PROTECTED BY A LISTED ARC-FAULT CIRCUIT INTERRUPTER, |
| | COMBINATION TYPE INSTALLED TO PROVIDE PROTECTION OF THE |
| | BRANCH CIRCUIT. |
| | |
| | 5} ALL 120-VOLT, SINGLE PHASE, 15- AND 20-AMPERE BRANCH |
| | CIRCUITS SUPPLYING OUTLETS INSTALLED IN DWELLING UNIT |
| | BEDROOMS SHALL BE PROTECTED BY A LISTED ARC-FAULT |
| | CIRCUIT INTERRUPTER, COMBINATION TYPE INSTALLED TO |
| | PROVIDE PROTECTION OF THE BRANCH CIRCUIT. INDICATE SAME |
| | IN PANEL SCHEDULE. |
| | BRANCH/FEEDER AFCIS SHALL BE PERMITTED TO BE USED TO |
| | MEET THE REQUIREMENTS OF 210.12(B) UNTIL JANUARY 1, |
| | 2008. |
| | |
| | 6} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS |
| | DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES |
| | FOR CLARITY IN THE FIELD. |
| | |