Plan Review Notes
Plan Review Notes For Permit 07040043
Permit Number 07040043
Review Stop E
Sequence Number 1
Notes
Date Text
2007-04-12 14:06:07 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK
 MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002
 FAC.
  
 2} 240.24(D) OVERCURRENT DEVICES SHALL NOT BE LOCATED
 IN THE VICINITY OF EASILY IGNITIBLE MATERIAL, SUCH AS
 IN CLOTHES CLOSETS.PANEL "A" CANNOT BE LOCATED IN THE
 CLOSET. ALSO SEE 408.17 LOCATION RELATIVE TO EASILY
 IGNITIBLE MATERIAL.
  
 3} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), SEE CIRCUIT #2 AT 15 AMPS.
  
 4} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.1
 RESIDENTIAL FLORIDA BUILDING CODE. ALL 120-VOLT, SINGLE
 PHASE, 15- AND 20-AMPERE BRANCH CIRCUITS SUPPLYING
 OUTLETS INSTALLED IN DWELLING UNIT BEDROOMS SHALL BE
 PROTECTED BY A LISTED ARC-FAULT CIRCUIT INTERRUPTER,
 COMBINATION TYPE INSTALLED TO PROVIDE PROTECTION OF THE
 BRANCH CIRCUIT.
  
 5} ALL 120-VOLT, SINGLE PHASE, 15- AND 20-AMPERE BRANCH
 CIRCUITS SUPPLYING OUTLETS INSTALLED IN DWELLING UNIT
 BEDROOMS SHALL BE PROTECTED BY A LISTED ARC-FAULT
 CIRCUIT INTERRUPTER, COMBINATION TYPE INSTALLED TO
 PROVIDE PROTECTION OF THE BRANCH CIRCUIT. INDICATE SAME
 IN PANEL SCHEDULE.
 BRANCH/FEEDER AFCIS SHALL BE PERMITTED TO BE USED TO
 MEET THE REQUIREMENTS OF 210.12(B) UNTIL JANUARY 1,
 2008.
  
 6} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS
 DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES
 FOR CLARITY IN THE FIELD.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  
  