| 2007-04-28 10:46:18 | |
| | |
| | DENIED |
| | |
| | 1)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST |
| | EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC |
| | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES |
| | PER 108.3 FBC* VALUE HAS BEEN INCREASED AND FEES ARE |
| | DUE THESE MUST BE PAID PRIOR TO FURTHER REVIEW |
| | |
| | 2)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SETS OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561) 233-5025 FOR MOREINFORMATION. |
| | |
| | 3)A DESIGN PROFESSIONAL THAT IS REGISTERED TO |
| | PRACTICE UNDER CHAPTER 481 OR 471 OF |
| | THE FLORIDA STATUTES SHALL AFFIX THEIR OFFICIAL SEAL, |
| | SIGNATURE AND DATE TO SAID DRAWINGS AND SPECIFICATIONS |
| | PER 106.1 FBC 2004. THE EXEMPTION FROM LICENSURE UNDER |
| | 481.229 FS DOES NOT EXEMPT THE DESIGNER RESPONSIBLE FOR |
| | THE DRAWINGS FROM SIGNING AND DATING SAID DRAWINGS. |
| | |
| | 4)WORK ON EXISTING BUILDINGS IS COVERED UNDER THE FBC |
| | (EXISTING) AS SUCH A DESIGN PROFESSIONAL OR OWNERMUST |
| | ELECT ONE OR A COMBINATION OF LEVELS OF ALTERATION PER |
| | 301.5 FBC (EXISTING) |
| | |
| | 5)PROVIDE 2 COPIES OF SURVEY THAT SHOW THE PROPOSED |
| | ADDITION WITH SETBACK FROM PROPERTY LINES INDICATED |
| | |
| | 6)PROVIDE A SITE PLAN THAT SHOWS CORRECT MEASUREMENTS |
| | THAT MATCH SURVEY. |
| | |
| | 7)PROVIDE A SITE PLAN THAT SHOWS DRAINAGE IN |
| | COMPLIANCE WITH THE REQUIREMENTS OF R403.1 FBC RES. |
| | SHOWDRAINAGE FROM BUILDINGAND AWAY FROM ADJOINING |
| | PROPERTIES |
| | |
| | 8)IN AREAS OF QUESTIONABLE SOILS AS SHOWN IN THE |
| | OFFICIAL ZONING MAP OF THE CITY OF WEST PALM BEACH, 2 |
| | COPIES OF A SOIL TEST REPORT SHALL BE SUBMITTED PER |
| | R401.4 FBC RES. |
| | |
| | 9)PROVIDE BEAM/LINTEL DETAIL. TOB = 8'-0" DOOR IS |
| | 6'-8" IN ORDER TO FIT 8" BOND BEAM AND 8" LINTEL DOOR |
| | WILL NOT FIT. IF POURED DROP DOWN BEAM IS USED SHOW |
| | DETAIL. ALSO WILL BE REQUIRED FOR WINDOWS IF SAME |
| | ELEVATION IS USED. |
| | |
| | 10)DRAWING DOES NOT SHOWACCESSIBLE BATHROOM THAT |
| | COMPLIES WITH R322.1.1 FBC RES. W/C DOOR SIZE NOT |
| | PROVIDED. |
| | |
| | 11)IDENTIFY SAFETY GLAZING FOR SHOWER DOOR THAT MEETS |
| | PROVISIONS OF R308.4 FBC RES. |
| | |
| | 12)PROVIDE ATTIC ACCESS ON DRAWINGS TO ALL AREAS AS |
| | REQUIRED PER R807.1 FBC RES. |
| | |
| | 13)SUBMIT ENGINEERED TRUSS DRAWINGS THAT |
| | COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR |
| | BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND |
| | APPROVED BY THE DESIGNER OF RECORD |
| | |
| | 14)PROVIDE ENGINEERED SUBSTRATE ATTACHMENT FOR WOOD |
| | BUCKS PER 1714.5.4.1 FBC |
| | |
| | 15)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF |
| | EACH PRODUCT APPROVAL THAT |
| | IS RELEVANT PER 9B-72. THESE SHOULD INCLUDE THE FLORIDA |
| | STATE APPROVAL COVER PAGES, AND THE PRODUCT NOA THAT |
| | LISTS THE SYSTEM COMPONENTS/ FASTENER LIST PAGES, THE |
| | PAGES WITH THE CHOSEN ASSEMBLY/ SYSTEM TO BE USED AND |
| | THE GENERAL LIMITATIONS PAGE. ALL CAN BE FOUND ON |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 16)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA |
| | STATE PRODUCT APPROVAL COVER |
| | SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON |
| | WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT |
| | SUBMITTED APPLICATIONS WILL BE DENIED |
| | |
| | 17)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE |
| | 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL PER 106.3.3 FBC* |
| | |
| | |
| | 18)PLEASE PROVIDE (2) COPIES OF THE PRODUCT APPROVALS |
| | THAT PERTAIN TO BUILDING (NO FIXED WINDOWS ARE SHOWN ON |
| | THE DRAWINGS) |
| | |
| | 19)A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT IS REQUIRED PRIOR TO |
| | A PERMIT BEING ISSUED |
| | |
| | |
| | BLDG PLAN REVIEW |