| 2007-05-31 08:18:05 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| | FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | ***FROM PREVIOUS LISTS*** |
| | |
| | 5/31/7CALLED CONTRACTOR TO ATTEMPT TO RESOLVE THIS |
| | MATTER; VOICE MAILBOX IS FULL FOR 601-4763. |
| | |
| | _XX_4.IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R |
| | 301.2.1.2.PLANS STATE "EXISTING SHUTTERS".IMPACT |
| | PROTECTION IS REQUIRED TO BE IN COMPLIANCE WITH FBC |
| | R301.2.1.2.SHOW COMPLIANCE FOR "EXISTING SHUTTERS". |
| | |
| | 5/7/7PLEASE NOTE THAT EXISTING SHUTTERS, PERMIT |
| | #99041287 WAS ISSUED UNDER THE CODE IN EFFECT AT THAT |
| | TIME, MOST LIKELY THE 1997 STANDARD BUILDING CODE. |
| | MISSILE IMPACT PROTECTION REQUIREMENTS HAVE SINCE THEN |
| | BEEN MADE MORE RESTRICTIVE.TO USE THE EXISTING |
| | SHUTTERS, THE CONTRACTOR IS TO SHOW THAT THE SHUTTERS |
| | ARE COMPLIANT FOR THE CURRENT BUILDING CODE, FBC2004 |
| | RESIDENTIAL, SECTION 301.2.1.2. |
| | |
| | 5/31, SAME PLANS SUBMITTED WITH INFORMATION IN REGARDS |
| | TO SHUTTER PERMIT, AND THE ABOVE NOTE HIGHLIGHTED.IT |
| | IS NOT CLEAR HOW THE NOTE OF 5/7/7 WAS ADDRESSED. |
| | PLEASE CONTACT ME IF YOU NEED ASSISTANCE. |