2007-05-07 09:50:23****************PROVISO****************
 PER FBC-2004 PLUMBING, SECTION 910.3 THE SIZE OF THE
 STACK VENT SHALL BE EQUAL TO THE SIZE OF THE WASTE
 STACK. OFFSETS SHALL BE PERMITTED IN THE STACK VENT AND
 SHALL BE LOCATED AT LEAST 6 INCHES ABOVE THE FLOOD
 LEVEL OF THE HIGHEST FIXTURE, AND SHALL BE IN
 ACCORDANCE WITH SECTION 905.2