Plan Review Notes
Plan Review Notes For Permit 07031078
Permit Number 07031078
Review Stop E
Sequence Number 1
Notes
Date Text
2007-04-09 07:33:09 
  
 DENIED/INCOMPLETE INFORMATION
  
 1} INDICATE THE PHYSICALLOCATION OF THE SERVICE SHOWN
 ON SHEET 8. ALSO INDICATE IF IT IS TO BE SEPARATELY
 METERED.
  
 2} PROVIDE LOAD CALCULATION FOR THE SERVICE, INDICATE
 THE VOLTAGE AND AMPERAGE, AND IF IT IS SINGLE OR 3
 PHASE.
  
 THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY. THE CONTRACTOR OF RECORD MAY BE THE
 DESIGN PROFESSIONAL IF EXEMPTIONS UNDER THOSE STATUTES
 ARE APPLICABLE.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718
  