| Date |
Text |
| 2007-04-11 10:39:33 | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE SUBMIT PLANS WHICH INDICATE THE LEGAL |
| | CONVERSION BACK TO A SINGLE FAMILY RESIDENCE. |
| | PLEASE SEE THAT THIS BUILDING SEEMS TO HAVE BEEN |
| | CONVERTED TO A DUPLEX WITH OUT ELECTRICAL CODE |
| | COMPLIANCE. |
| | PLEASE SEE ZONING COMMENTS, AS THIS BUILDING MAY NOT BE |
| | CONVERTED TO A DUPLEX, PLEASE INDICATE |
| | AS BEING CONVERTED BACK TO A SFR. |
| | |
| | 2) NOTE: PLEASE SUBMIT ELECTRICAL PLANS WHICH INDICATE |
| | EXISTING AND OR NEW ELECTRICAL WHICH MEETS CODE |
| | COMPLIANCE. AS WORK SEEMS TO HAVE BEEN DONE W/OUT THE |
| | CORRECT PERMITTING IT IS UNCLEAR WHAT IS CODE COMPLIANT |
| | THAT IS EXISTING. |
| | PLEASE SEE 210.8A FOR ALL LOCATIONS WHICH REQUIRE GFI |
| | PROTECTION. |
| | PLEASE SEE 210.52C FOR KITCHEN COUNTER RECEPTACLES |
| | WHICH IS ONLY TO BE FOR ONE KITCHEN. |
| | PLEASE SEE 210.52B1,210.11C, 220.53 FOR SMALL APPLIANCE |
| | CIRCUITS, BATH CIRCUITS, LAUNDRY ETC. |
| | PLEASE SEE ALL OF 220 FOR MINIMUM CIRCUITS REQUIRED |
| | ALONG WITH 210.52. |
| | PLEASE SHOW COMPLIANCE FOR ALL REQUIRED EGRESS LIGHTING |
| | INSIDE AND OUTSIDE THE DWELLING PER 210.70 AND LS 101 |
| | 7.8. |
| | PLEASE INDICATE NEW OR EXISTING SMOKE ALARMS PER |
| | NFPA-72 11.5.1.1, 11.8.3. (FBC R313) |
| | PLEASE SUBMIT A PANEL SCHEDULE SHOWING NEW OR EXISTING |
| | CIRCUITS MEETING CODE COMPLIANCE ALONG WITH CONDUCTOR |
| | SIZES. 408.4, 310.16, 240.4 |
| | PLEASE SHOW THE SERVICE/PANEL LOCATION. INDICATE MAIN |
| | DISCONNECT, NEW OR EXISTING. 230.70, 230.71 ETC. |
| | PLEASE SEE NEC 2005 FOR MANY OF THE SECTIONS NOTED |
| | ABOVE. |
| | PLEASE ALSO SEE THE 2004 FBC W/ 2006 REVISIONS. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |