| Plan Review Notes For Permit 07031031 |
| Permit Number |
07031031 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-04-10 10:18:36 | | | | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} INDICATE COMPLIANCE WITH 250.112 NEC. THERE ARE NO | | | EQUIPMENT GROUNDS RAN WITH ANY OF THE FEEDERS ON THE | | | PLAN. | | | | | | 2} THE SINGLE PHASE LOAD CALCULATION INCORRECTLY | | | APPLIES 220.14(F) FOTR THE GENERAL LIGHTING LOAD. THAT | | | LOAD SHOULD BE TAKEN FROM 220.12. ALSO@ 125 % PER | | | 215.2(A)(1). | | | | | | 3} PROVIDE A SITE PLAN INDICATING THE LOCATION OF ALL | | | SERVICE EQUIPMENT SO THAT THE INSPECTOR CAN LOCATE | | | SAME. | | | | | | 4} THE TITLE BLOCK FOR THE DESIGNER OF RECORD MUST | | | CONTAIN A CERTIFICATE OF AUTHORIZATION PER F.A.C. | | | | | | WILLIAM R. TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|