| 2007-04-07 10:41:01 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* CITY |
| | OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FROM PREVIOUS LIST, SAME PAPERWORK SUBMITTED. |
| | |
| | 1.)CONNECTION C4 REQUIRES 6" SPACING; YOUR |
| | INSTALLATION SCHEDULE SPECIFIES 10". |
| | |
| | NOTE THAT YOUR "GENERIC" INSTALLATION SCHEDULE DOES NOT |
| | REFER TO A CONNECTION TYPE.IF THE CONNECTION |
| | SPECIFIED IS NOT COMPLIANT FOR ALL CONNECTION TYPES, OR |
| | YOU ARE USING DIFFERENT CONNECTION TYPES FOR DIFFERENT |
| | OPENINGS, THIS SCHEDULE IS NOT USEFUL AS IT IS TO |
| | DETERMINE CODE COMPLIANCE AND TO ASSIST IN INSPECTIONS. |
| | PERMITS WILL BE ISSUED FROM THE "GENERIC" INSTALLATION |
| | SCHEDULE IF IT IS CLEARLY CODE COMPLIANT.IF IT |
| | REQUIRES THE INSPECTOR TO READ THROUGH THE PRODUCT |
| | APPROVAL AND CODE COMPLIANCE IS NOT EASILY DETERMINED, |
| | A SCHEDULE REFERRING TO EACH OPENING WILL BE REQUIRED |
| | AS STATED IN THE BUILDING OFFICIAL'S WRITTEN POLICY, |
| | SEE ATTACHED. |
| | |
| | ALSO NOTE THAT AS THIS IS A WRITTEN POLICY FROM THE |
| | BUILDING OFFICIAL, IF I ISSUE A PERMIT USING MY BEST |
| | JUDGEMENT THE I HAVE ENOUGH INFORMATION TO DETERMINE |
| | CODE COMPLIANCE BASED ON THE "GENERIC" INSTALLATION |
| | SCHEDULE, THIS WILL BE ON A CASE BY CASE BASIS AND |
| | OTHER PLANS EXAMINERS IN THIS DEPARTMENT MIGHT NOT |
| | ISSUE WITH THE SAME INFORMATION. |
| | |
| | NOTE THAT ALL OTHER CONTRACTORS ARE REQUIRED TO PROVIDE |
| | ALL REQUIRED INFORMATION. |
| | |