| 2007-12-07 11:16:39 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | ***REVISION DENIED *** |
| | 1) CHANGES MAY NOT BE DONE BY HAND TO ENGINEER SEALED |
| | PLANS. |
| | |
| | 2) THE CHANGES TO THE PLANS BY HAND DO NOT ADDRESS THE |
| | COMMENTS FROM THE LAST REVIEW 12-3-07 AND MAKE NO |
| | SENSE. PLEASE SEE NOTES FROM LAST REVIEW AND MAKE |
| | CORRECTIONS. |
| | |
| | ** NOTES FROM LAST REVIEW 12-3-07 ** |
| | 1) EXHAUST HOOD #1 HAS TWO 9"X16" EXHAUST DUCTS THE |
| | EXHAUST FAN IS 2,500 CFM'S , THAT WOULD PUT THE EXHAUST |
| | DUCT VELOCITY AT 1,250 CFM'S. SEE NOTE #4 ON PAGE 2 OF |
| | THE PLANS AND SEE 2004 FBC/M 506.3.4 STATES DUCT |
| | VELOCITY NOT LESS THAN 1,500 CFM'S. PLEASE CORRECT. |
| | |
| | 2) PAGE 1 OF PLANS FRONT ELEVATION OF HOOD #1 SHOWS THE |
| | EXHAUST FAN AND CURB NOT TO BE SECURED TO THE ROOF, |
| | PLEASE COMPLY WITH 2004 FBC 1609. |
| | |
| | 3) NEED TO ADD A FRONT VIEW FOR HOOD #2 TO THE PLANS. |
| | |
| | 4) PAGE 1 SECTION VIEW FOR HOOD #1 IS LISTING THE |
| | SUPPLY AND EXHAUST FANS AS #1, PLEASE CORRECT. |
| | |
| | 5) PLEASE LABEL HOODS AS #1 AND #2 ON PLAN. |
| | |
| | 6) PAGE TWO HOOD SCHEDULE SHOWS HOOD 1 EXHAUST SIZE AS |
| | 20X12, PLEASE CORRECT TO (2) 9X16. |
| | |
| | MECHANICAL PLAN REVIEW BY; |