| Date |
Text |
| 2007-08-31 07:36:31 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | CITY WPB MUNICIPAL CODE |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | ******FROM PREVIOUS REVIEWS: |
| | |
| | 1. OK |
| | 2. OK |
| | |
| | 3. 2 SETS OF PLANS, STAMPED BY THE DEPT OF BUSINESS |
| | REGULATION, HOTEL & RESTAURANT DIVISION SHALL BE |
| | SUBMITTED FOR REVIEW. ONLY ONE SET HAS THE DBPR STAMP. |
| | ALSO THE TWO PAGE "WORKSHEETS" SHALL BE ATTACHED TO |
| | EACH SET OF PLANS SUBMITTED FOR REVIEW BY THE CITY |
| | WPB. |
| | ****RESPONSE NOTED, BUT THE TWO PAGE "WORKSHEETS" HAVE |
| | NOT BEEN ATTACHED TO EACH SET OF PLAN. |
| | ******NO RESPONSE. STAMPED/REVIEWED SHEETS FROM DBPR |
| | HAVE BEEN DELETED FROM EACH SET. THESE ARE REQUIRED AS |
| | WELL AS THE TWO PAGE "SPECIFICATION WORKSHEETS". THE |
| | WORKSHEETS SHALL BE ATTACHED TO THE SHEETS STAMPED & |
| | REVIEWED BY DBPR AND ONE SHEET SHALL BE INSERTED INTO |
| | EACH SET OF PLANS AS REQUIRED BY SECTION 102.2.1. |
| | |
| | 4. THE GREASE INTERCEPTOR SHALL BE SIZED AND LOCATED BY |
| | THE ENVIRONMENTAL COMPLIANCE DEPT. PLEASE CONTACT |
| | RODNEY COMPO (561) 822-2272, [email protected], OR CALVIN |
| | WILLIAMS (561) 822-2284, [email protected]. THEIR FAX |
| | NUMBER IS (561) 822-2287. ARTICLE III SECTION 90-124. |
| | --PER ARTICLE III SECTION 90-124(7)(F) A CONCRETE, |
| | MINIMUM 750 GAL. INTERCEPTOR IS REQUIRED.(SEE |
| | ATTACHED UTILITY STANDARD FOR GREASE INTERCEPTORS).-- |
| | THE GREASE INTERCEPTORS ARE TO BE INSTALLED OUTSIDE THE |
| | FOOD PREPARATION AREA WITH THE DISHWASHER DISCHARGING |
| | VIA A SEPARATE LINE TO THE SANITARY. ARTICLE III |
| | SECTION 9--124(7)(B). |
| | ****RESPONSE NOTED, BUT NO INPUT FROM ENVIRONMENTAL |
| | COMPLIANCE HAS BEEN SUBMITTED. PLEASE SUBMIT WRITTEN |
| | APPROVAL OF THE SIZE GREASE INTERCEPTOR FROM MR. COMPO |
| | OR MR. WILLIAMS. |
| | ******NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | 5. OK |
| | |
| | 6. SHT A-2 MORE INFORMATION IS REQUIRED. IS THERE A |
| | FIXTURE DRAINING INTO THE GREASE TRAP SHOWN ON THE |
| | FLOOR PLAN AS PLUMBING PLAN KEY ITEM #6. PLEASE |
| | CLARIFY. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT THE GREASE FROM THE ROTISSERIE |
| | OVEN CAN NOT DRAIN INTO THE FLOOR SINK. THE GREASE |
| | SYSTEM IS DESIGNED TO INTERCEPT INCIDENTAL GREASE NOT |
| | GREASE DRIPPINGS FROM AN OVEN. THE GREASE WILL HAVE TO |
| | BE CONTAINED AND THEN DISPOSED OF PROPERLY AT A |
| | RENDERING PLANT, NOT DRAINED INTO THE FLOOR SINK. |
| | ******NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | 7. OK |
| | 8. OK |
| | 9. OK |
| | 10. OK |
| | 11. OK |
| | 12. OK |
| | 13. OK |
| | |
| | 14. SHT A-2 THE ACCESSIBLE TOILET ROOMS SHALL SHOW |
| | COMPLIANCE WITH THE FOLLOWING: |
| | ___FOR W/C |
| | A. 11-4.16.2 CLEAR FLOOR SPACE - ******NO RESPONSE, |
| | COMMENT NOT ADDRESSED. SHOW IN THE TOILET ROOM TO |
| | VERIFY COMPLIANCE. |
| | B. 11-4.16.5 FLUSH CONTROLS - ******NO RESPONSE, |
| | COMMENT NOT ADDRESSED. |
| | ___FOR LAV |
| | A. 11-4.19.3 CLEAR FLOOR SPACE - ******NO RESPONSE, |
| | COMMENT NOT ADDRESSED. SHOW IN THE TOILET ROOM TO |
| | VERIFY COMPLIANCE. |
| | B. 11-4.19.4 EXPOSED PIPES & SURFACES - ******NO |
| | RESPONSE, COMMENT NOT ADDRESSED. |
| | C. 11-4.19.5 FAUCETS - ******NO RESPONSE, COMMENT NOT |
| | ADDRESSED. |
| | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. |
| | |
| | 15. THE FOLLOWING ARE GAS PERMIT REQUIREMENTS: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. SOME SECTIONS DO NOT SHOW THE REQUIRED |
| | LENGTHS. ALSO SHOW ALL VALVES ON THE ISOMETRIC AS WELL |
| | AS THE SEDIMENT TRAPS REQUIRED IN SECTIONS 408.4 & |
| | 409.5. |
| | ****RESPONSE NOTED, BUT THE SEDIMENT TRAPS ARE NOT |
| | SHOWN. |
| | ******RESPONSE NOTED, BUT NOW "WHITE OUT" IS USED ON |
| | THE ISOMETRIC, (SEE BTU/HR NUMBERS), AND THIS IS NOT |
| | APPROVED ON SIGNED & SEALED PLANS PER SECTION 106.1.3. |
| | - SEPARATE SHUT OFF VALVES ARE REQUIRED FOR EACH GAS |
| | APPLIANCE. APPLIANCE MARKS 2 & 3 ONLY SHOW ONE SHUT OFF |
| | VALVE FOR TWO APPLIANCES. INDICATE VALVE SIZE FOR EACH |
| | APPLIANCE WHICH SHALL BE FULL SIZE PER TABLE 402.4(2). |
| | |
| | |
| | B. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | ****RESPONSE NOTED, BUT THE DISTANCE IS NOT SHOWN. |
| | ******RESPONSE NOTED, BUT THE TOTAL DISTANCE ADDS UP TO |
| | 111FT, NOT 105 AS SHOWN. |
| | |
| | C. OK |
| | D. OK |
| | |
| | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESS. |
| | ******RESPONSE NOTED, BUT THE WATER HEATER, OVEN AND |
| | COOK TOP STOVE MANUF. SHEETS HAVE NOT BEEN SUBMITTED. |
| | ALSO THE 36" RANGE INDICATES 203,000 BTU AND IT IS |
| | INDICATED AS 132,000 BTU. SEE MANUF. SHEET SUBMITTED |
| | WITH MODEL NUMBER INDICATED. |
| | |
| | F. N/A |
| | F. N/A |
| | G. OK |
| | |
| | ************NEW COMMENTS************ |
| | |
| | 1B. OK |
| | 2B. OK |
| | 3B. OK |
| | 4B. OK |
| | 5B. SHT M-1 PLUMBING FIXTURE SCHEDULE INDICATES THE |
| | GREASE INTERCEPTOR AND THE GAS WATER HEATER BY THE |
| | GENERAL CONTRACTOR.A SEPARATE GREASE INTERCEPTOR |
| | PERMIT IS REQUIRED BY THE PROVIDER OF THE GREASE |
| | INTERCEPTORAND SHALL BE HOOKED UP BY THE PLUMBING |
| | CONTRACTOR AS WELL AS THE GAS WATER HEATER. FS 489. |
| | ******NO RESPONSE. PLEASE INDICATE PLUMBING CONTRACTOR |
| | RESPONSIBILITY FOR THESE INSTALLATIONS. |
| | |
| | 6B. SEE ATTACHED SHEET CONCERNING THE DESIGN |
| | PROFESSIONALS AND FS 533.80(2)(B). THIS IS GIVEN AS A |
| | NOTICE AT THIS TIME. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. ******SUBMIT ONE SET |
| | OF VOID SHEETS FOR COMPARISON WHEN RESUBMITTING |
| | PLANS.****** |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |
| | |
| | |
| | |
| | |
| | . |