| 2007-08-31 07:38:53 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | ******FROM PREVIOUS REVIEWS: |
| | |
| | 1. THE FOLLOWING ARE GAS PERMIT REQUIREMENTS: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. SOME SECTIONS DO NOT SHOW THE REQUIRED |
| | LENGTHS. ALSO SHOW ALL VALVES ON THE ISOMETRIC AS WELL |
| | AS THE SEDIMENT TRAPS REQUIRED IN SECTIONS 408.4 & |
| | 409.5. |
| | ****RESPONSE NOTED, BUT THE SEDIMENT TRAPS ARE NOT |
| | SHOWN. |
| | ******RESPONSE NOTED, BUT NOW "WHITE OUT" IS USED ON |
| | THE ISOMETRIC, (SEE BTU/HR NUMBERS), AND THIS IS NOT |
| | APPROVED ON SIGNED & SEALED PLANS PER SECTION 106.1.3. |
| | - SEPARATE SHUT OFF VALVES ARE REQUIRED FOR EACH GAS |
| | APPLIANCE. APPLIANCE MARKS 2 & 3 ONLY SHOW ONE SHUT OFF |
| | VALVE FOR TWO APPLIANCES. INDICATE VALVE SIZE FOR EACH |
| | APPLIANCE WHICH SHALL BE FULL SIZE PER TABLE 402.4(2). |
| | |
| | |
| | B. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | ****RESPONSE NOTED, BUT THE DISTANCE IS NOT SHOWN. |
| | ******RESPONSE NOTED, BUT THE TOTAL DISTANCE ADDS UP TO |
| | 111FT, NOT 105FT AS SHOWN. |
| | |
| | C. OK |
| | D. OK |
| | |
| | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESS. |
| | ******RESPONSE NOTED, BUT THE WATER HEATER, OVEN AND |
| | COOK TOP STOVE MANUF. SHEETS HAVE NOT BEEN SUBMITTED. |
| | ALSO THE 36" RANGE INDICATES 203,000 BTU AND IT IS |
| | INDICATED AS 132,000 BTU. SEE MANUF. SHEET SUBMITTED |
| | WITH MODEL NUMBER INDICATED. PLEASE CLARIFY. |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |
| | |
| | |
| | |
| | |
| | . |