| Date |
Text |
| 2007-07-10 11:47:21 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | CITY WPB MUNICIPAL CODE |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. PER ADDRESSING, THE WRONG PCN NUMBER WAS USED DURING |
| | APPLICATION FOR PERMIT. THE CORRECT ADDRESS IS 3008 S |
| | DIXIE HWY, NOT 3010 S DIXIE HWY AS INDICATED ON THE |
| | APPLICATION AND ON THE TITLE BLOCK OF SHEETS A-1 & A-2. |
| | PLEASE CHANGE THE APPLICATION AND THE TITLE BLOCKS TO |
| | REFLECT THE CORRECT ADDRESS. |
| | ****RESPONSE NOTED, BUT THE ADDRESS HAS NOT BEEN |
| | CHANGED ON THE ARCHITECTURAL SHEETS. |
| | |
| | 2. SHTS A-2 & A-2 THE BUSINESS NUMBER, (CERTIFICATE OF |
| | AUTHORIZATION), ADDRESS, AND PHONE NUMBER OF THE |
| | ARCHITECT'S BUSINESS SHALL BE INDICATED IN THE TITLE |
| | BLOCK AS WELL AS THE PRINTED NAME OF THE PERSON SEALING |
| | THE DOCUMENT. FAC 61G1-16.004(1)(2)(6) & FS 481.219, |
| | 481.2055. |
| | ****RESPONSE NOTED, COMMENT NOT ADDRESSED. |
| | |
| | 3. 2 SETS OF PLANS, STAMPED BY THE DEPT OF BUSINESS |
| | REGULATION, HOTEL & RESTAURANT DIVISION SHALL BE |
| | SUBMITTED FOR REVIEW. ONLY ONE SET HAS THE DBPR STAMP. |
| | ALSO THE TWO PAGE "WORKSHEETS" SHALL BE ATTACHED TO |
| | EACH SET OF PLANS SUBMITTED FOR REVIEW BY THE CITY |
| | WPB. |
| | ****RESPONSE NOTED, BUT THE TWO PAGE "WORKSHEETS" HAVE |
| | NOT BEEN ATTACHED TO EACH SET OF PLAN. |
| | |
| | 4. THE GREASE INTERCEPTOR SHALL BE SIZED AND LOCATED BY |
| | THE ENVIRONMENTAL COMPLIANCE DEPT. PLEASE CONTACT |
| | RODNEY COMPO (561) 822-2272, [email protected], OR CALVIN |
| | WILLIAMS (561) 822-2284, [email protected]. THEIR FAX |
| | NUMBER IS (561) 822-2287. ARTICLE III SECTION 90-124. |
| | --PER ARTICLE III SECTION 90-124(7)(F) A CONCRETE, |
| | MINIMUM 750 GAL. INTERCEPTOR IS REQUIRED.(SEE |
| | ATTACHED UTILITY STANDARD FOR GREASE INTERCEPTORS).-- |
| | THE GREASE INTERCEPTORS ARE TO BE INSTALLED OUTSIDE THE |
| | FOOD PREPARATION AREA WITH THE DISHWASHER DISCHARGING |
| | VIA A SEPARATE LINE TO THE SANITARY. ARTICLE III |
| | SECTION 9--124(7)(B). |
| | ****RESPONSE NOTED, BUT NO INPUT FROM ENVIRONMENTAL |
| | COMPLIANCE HAS BEEN SUBMITTED. PLEASE SUBMIT WRITTEN |
| | APPROVAL OF THE SIZE GREASE INTERCEPTOR FROM MR. COMPO |
| | OR MR. WILLIAMS. |
| | |
| | 5. OK |
| | |
| | 6. SHT A-2 MORE INFORMATION IS REQUIRED. IS THERE A |
| | FIXTURE DRAINING INTO THE GREASE TRAP SHOWN ON THE |
| | FLOOR PLAN AS PLUMBING PLAN KEY ITEM #6. PLEASE |
| | CLARIFY. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT THE GREASE FROM THE ROTISSERIE |
| | OVEN CAN NOT DRAIN INTO THE FLOOR SINK. THE GREASE |
| | SYSTEM IS DESIGNED TO INTERCEPT INCIDENTAL GREASE NOT |
| | GREASE DRIPPINGS FROM AN OVEN. THE GREASE WILL HAVE TO |
| | BE CONTAINED AND THEN DISPOSED OF PROPERLY AT A |
| | RENDERING PLANT, NOT DRAINED INTO THE FLOOR SINK. |
| | |
| | 7. OK |
| | 8. OK |
| | 9. OK |
| | 10. OK |
| | |
| | 11. SUBMIT A WATER ISOMETRIC RISER DIAGRAM SHOWING ALL |
| | PIPE SIZES, VALVES, REQUIRED WATER HAMMER ARRESTORS, |
| | (LOCATED NEAR THE FIXTURE IN AN "EFFECTIVE RANGE", NOT |
| | IN THE CEILING). INDICATE THE WATER SERVICE SIZE PER |
| | TABLE 603.1 AND INDICATE IF THERE IS AN EXISTING RPZV |
| | BACKFLOW PREVENTER ON THE WATER SERVICE. IF NO |
| | BACKFLOW, THEN ONE WILL BE REQUIRED PER SECTION |
| | 608.13.2.SECTIONS 106.3.5.1.3(3)(8)(10)(13) & 604.9. |
| | ****RESPONSE NOTED, BUT A FULL OPEN VALVE IS REQUIRED |
| | ON THE WATER DISTRIBUTION SUPPLY PIPE AT THE ENTRANCE |
| | INTO THE STRUCTURE. SECTION 606.1(2). |
| | |
| | 12. SHT A-2 THERMAL EXPANSION CONTROL IS REQUIRED PER |
| | SECTION 607.3.2. PLEASE INDICATE METHOD. ****RESPONSE |
| | NOTED, BUT A CHECK VALVE DOES NOT CONTROL THERMAL |
| | EXPANSION.PLEASE INDICATE PROPER APPROVED METHOD OF |
| | CONTROLING THERMAL EXPANSION. |
| | |
| | 13. OK |
| | |
| | 14. SHT A-2 THE ACCESSIBLE TOILET ROOMS SHALL SHOW |
| | COMPLIANCE WITH THE FOLLOWING: |
| | ___FOR W/C |
| | A. 11-4.16.2 CLEAR FLOOR SPACE |
| | B. 11-4.16.5 FLUSH CONTROLS |
| | ___FOR LAV |
| | A. 11-4.19.3 CLEAR FLOOR SPACE |
| | B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | C. 11-4.19.5 FAUCETS |
| | ALSO SHOW THE W/C TO BE 18" OFF THE WALL TO THE |
| | CENTERLINE OF THE FIXTURE PER FIG. 29. SHOW THE LAV TO |
| | BE A MINIMUM OF 15" OFF THE WALL TO THE CENTERLINE OF |
| | THE FIXTURE. (CENTER ON THE 30" OF THE 30"X48" CLEAR |
| | FLOOR SPACE REQUIRED FOR THE LAV). |
| | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. |
| | |
| | 15. THE FOLLOWING ARE GAS PERMIT REQUIREMENTS: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. SOME SECTIONS DO NOT SHOW THE REQUIRED |
| | LENGTHS. ALSO SHOW ALL VALVES ON THE ISOMETRIC AS WELL |
| | AS THE SEDIMENT TRAPS REQUIRED IN SECTIONS 408.4 & |
| | 409.5. |
| | ******RESPONSE NOTED, BUT THE SEDIMENT TRAPS ARE NOT |
| | SHOWN. |
| | |
| | B. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | ******RESPONSE NOTED, BUT THE DISTANCE IS NOT SHOWN. |
| | |
| | C. OK |
| | D. OK |
| | |
| | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ******RESPONSE NOTED, BUT COMMENT NOT ADDRESS. |
| | |
| | F. N/A |
| | F. N/A |
| | |
| | G. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | ******RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. SHOW |
| | VALVES & UNION ON RISER DIAGRAM. (SEE COMMENT #1). |
| | |
| | ************NEW COMMENTS************ |
| | |
| | 1B. (NEW) SHT P-1 INDICATES A WATER FILTER. THE WATER |
| | FILTER SHALL MEET THE REQUIREMENTS OF NSF 42. SUBMIT |
| | MANUF. SPECIFICATIONS SHOWING COMPLIANCE. SECTION |
| | 611.1. |
| | |
| | 2B. SHT P-1 A VENT IS REQUIRED ON THE GREASE SYSTEM. |
| | SECTION 901.2. |
| | |
| | 3B. SHT P-1 A SERVICE SINK IS REQUIRED PER TABLE 403.1. |
| | SINK SHALL BE CONNECTED TO THE GREASE SYSTEM. INDICATE |
| | THE LOCATION ON THE FLOOR PLAN, GREASE RISER DIAGRAM |
| | AND THE WATER RISER DIAGRAM. |
| | |
| | 4B. SHT M-1 GAS WATER HEATER DETAIL. A FLOOR DRAIN IS |
| | NOT AN APPROVED INDIRECT WASTE RECEPTOR. A FLOOR SINK |
| | OR HUB DRAIN SHALL BE USED. SECTIONS 802.3 & 802.3.2. |
| | |
| | 5B. SHT M-1 PLUMBING FIXTURE SCHEDULE INDICATES THE |
| | GREASE INTERCEPTOR AND THE GAS WATER HEATER BY THE |
| | GENERAL CONTRACTOR.A SEPARATE GREASE INTERCEPTOR |
| | PERMIT IS REQUIRED BY THE PROVIDER OF THE GREASE |
| | INTERCEPTORAND SHALL BE HOOKED UP BY THE PLUMBING |
| | CONTRACTOR AS WELL AS THE GAS WATER HEATER. FS 489. |
| | |
| | 6B. SEE ATTACHED SHEET CONCERNING THE DESIGN |
| | PROFESSIONALS AND FS 533.80(2)(B). THIS IS GIVEN AS A |
| | NOTICE AT THIS TIME. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |
| | |
| | |
| | |
| | |
| | . |