| Date |
Text |
| 2007-06-21 14:28:29 | BUILDING PLAN REVIEW |
| | PERMIT: 07031011 |
| | ADD: 3010 S. DIXIE HWY |
| | CONT: MIKE MOORE CONSTRUCTION |
| | TEL: (561)748-7000 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW 2ND |
| | ACTION: DENIED |
| | |
| | **************NO RESPONSE WERE GIVEN*************** |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2)61G1-16.004 TITLE BLOCK. |
| | A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR |
| | INTERIOR DESIGN DRAWINGS AND SPECIFICATION |
| | IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A |
| | MINIMUM, CONTAIN THE FOLLOWING INFORMATION: |
| | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. |
| | (2) FIRM LICENSE NUMBER. |
| | (3) NAME OR IDENTIFICATION OF PROJECT. |
| | (4) DATE PREPARED. |
| | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. |
| | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING |
| | THE DOCUMENT. |
| | |
| | 3)108.3* THE CLAIMED VALUATION ON THE PERMIT |
| | APPLICATION IS LOW.IF, IN THE OPINION OF THE BUILDING |
| | OFFICIAL, THE CLAIMED VALUATION OF BUILDING, |
| | ALTERATION, STRUCTURE, ELECTRUCAL, GAS, MECHANICAL OR |
| | PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE |
| | APPLICATION, THE PERMIT SHALL BE DENIED. FOR PERMITTING |
| | PURPOSES, VALUATION SHALL BE THE TOTAL REPLACEMENT |
| | VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, |
| | MECHANICAL, INTERIOR FINISH ARCHITECTURAL AND DESIGN |
| | FEES, MARKETING COST, AND OVERHEAD AND PROFIT EXCLUDING |
| | LAND VALUE. |
| | |
| | 4)110.2* W. P. B. ADMINISTRATIVE |
| | CODE, INFORMATION THAT IS REQUIRED FOR |
| | RECORD KEEPING. |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PROJECT WAS DESIGNED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE DESIGN OCCUPANT LOAD, SEE 1004. |
| | D) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| | IS REQUIRED. |
| | E) SQ. FT. FOOTPRINT |
| | F) SQ. FT. UNDER ROOF (TOTAL) |
| | G) OCCUPANT LOAD |
| | |
| | 5)11-4.32.2 SEATING. |
| | IF SEATING SPACES FOR PEOPLE IN WHEELCHAIRS ARE |
| | PROVIDED AT FIXED TABLES OR COUNTERS, CLEAR FLOOR SPACE |
| | COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED. SUCH |
| | CLEAR FLOOR SPACE SHALL NOT OVERLAP KNEE SPACE BY MORE |
| | THAN 19 INCHES (485 MM) (SEE FIGURE 45 ). 11-4.32.3 |
| | KNEE CLEARANCES.IF SEATING FOR PEOPLE IN WHEELCHAIRS IS |
| | PROVIDED AT TABLES OR COUNTERS, KNEE SPACES AT LEAST 27 |
| | INCHES (685 MM) HIGH, 30 INCHES (760 MM) WIDE, AND 19 |
| | INCHES (485 MM) DEEP SHALL BE PROVIDED (SEE FIGURE 45 |
| | ). SHOW HOW THE TABLES ON SHEET A-1 WILL MEET THE |
| | REQUIREMENTS OF FIG 45 BY INDICATING THE DIMENTIONS OF |
| | THE TABLEAND SHOWING THE CLEAR FLOOR SPACE ON THE |
| | PLANS. |
| | |
| | 6)INDICATE THE TYPE OF ALTERATION OF THE PROJECT IN |
| | ACCORDANCE WITH CH 3 OF THE 2004 FLORIDA EXISTING |
| | BUILDING CODE. |
| | |
| | 7)FBC.1210.1 FLOORS. IN OTHER THAN DWELLING UNITS, |
| | TOILET AND BATHING ROOM FLOORS SHALL HAVE A SMOOTH, |
| | HARD, NONABSORBENT SURFACE THAT EXTENDS UPWARD ONTO THE |
| | WALLS AT LEAST 6 INCHES (152 MM). |
| | |
| | 8)FBC.1210.2WALLS WITHIN 2 FEET (610 MM) OF URINALS |
| | AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD, |
| | NONABSORBENT SURFACE, TO A HEIGHT OF 4 FEET (1219 MM) |
| | ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS, |
| | THE MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE |
| | THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | 805-6726 |
| | |