| Date |
Text |
| 2007-12-13 11:26:22 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****FROM PREVIOUS REVIEW: (FIRST REVIEW FOR THE DESIGN |
| | PROFESSIONL) |
| | |
| | 1. OK |
| | |
| | 2. ADDRESS ON THE APPLICATION DOES NOT REFLECT THE |
| | ADDRESS SHOWN ON THE PLANS, SEE THE PALM BEACH COUNTY |
| | PROPERTY APPRAISER'S WEB-SITE. PLEASE CORRELATE THE |
| | INFORMATION AND INDICATE UNIT NUMBER AFFECTED BY THE |
| | APPLICATION. SECTION 106.1.1. |
| | ****NO RESPONSE, NOT ADDRESSED. THE ADDRESS ON OUR |
| | SYSTEM IS 6901 S DIXIE HWY. THE APPLICATION & PLANS |
| | SHALL SHOW THE CORRECT ADDRESS ON THE TITLE BLOCK ONCE |
| | THE CORRECT ADDRESS, INCLUDING SPACE, SUITE OR UNIT |
| | DESIGNATION, HAS BEEN DETERMINED BY THE ADDRESSING |
| | REVIEWER. |
| | |
| | 3. SHT A1 SHOW COMPLIANCE WITH THE FOLLOWING: ___FOR |
| | W/C: |
| | A. 11-4.16.5 FLUSH CONTROLS |
| | ****NO RESPONSE, NOT ADDRESSED |
| | ___FOR LAV: |
| | A. 11-4.19.2 HEIGHT - SHOWS 2'10" FROM THE BOTTOM OF |
| | THE SLAB ON ONE SIDE OF THE DETAIL AND 2'11-1/2" FROM |
| | FINISHED FLOOR ON THE OTHER SIDE OF THE DETAIL. PLEASE |
| | COMPLY WITH SECTION 11-4.19.2. |
| | ****RESPONSE NOTED, BUT THE CLEARANCE IS NOT INDICATED. |
| | (29" REQUIRED). |
| | B. 11-4.19.5 FAUCETS |
| | ****NO RESPONSE, NOT ADDRESSED |
| | C. 11-4.29.6 MIRRORS |
| | ****NO RESPONSE, NOT ADDRESSED |
| | ___TOILET ROOM |
| | A. OK |
| | |
| | 4. NOT APPLICABLE |
| | |
| | 5. PER TABLE 403.1 A DRINKING FOUNTAIN IS REQUIRED. |
| | PLEASE INDICATE THE LOCATION OF THE DRINKING FOUNTAIN. |
| | ****NO RESPONSE, NOT ADDRESSED |
| | |
| | 6. SUBMIT A SANITARY ISOMETRIC RISER DIAGRAM SHOWING |
| | ALL PIPE SIZES, VENTS, TRAPS ETC. SECTION |
| | 106.3.5.1.3(4)(13). --THE SINK IS NOT SHOWN ON THE |
| | RISER DIAGRAM SUBMITTED, AND THE DRINKING FOUNTAIN |
| | SHALL BE SHOWN ALSO. IF THE RISER DIAGRAM IS NOT |
| | DESIGNED BY A DESIGN PROFESSIONAL, THE DESIGNER SHALL |
| | SIGN HIS OR HER NAME TO THE RISER DIAGRAM AND SHALL |
| | HAVE HIS OR HER NAME PRINTED ON THE RISER DIAGRAM. |
| | ****RESPONSE NOTED, BUT THE DRINKING FOUNTAIN SHALL BE |
| | INCLUDED. |
| | |
| | 7. SUBMIT A WATER ISOMETRIC RISER DIAGRAM SHOWING ALL |
| | PIPE SIZES, VALVES, WATER HAMMER ARRESTORS REQUIRED BY |
| | SECTION 604.9 & LOCATED NEAR THE FIXTURES, (NOT IN THE |
| | CEILING), ETC. SECTION 106.3.5.1.3(3)(10)(13). |
| | ****RESPONSE NOTED, BUT THE DRINKING FOUNTAIN SHALL BE |
| | INCLUDED. |
| | |
| | 8. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE TO |
| | THE SPACE. PLEASE INDICATE IF THE BACKFLOW IS EXISTING, |
| | OR IF NOT INDICATE ON THE WATER SUPPLY RISER DIAGRAM. |
| | SECTIONS 106.3.5.1.3(8) & 607.3.2. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | **********NEW COMMENTS********** |
| | |
| | 1B. THE APPLICATION REQUIRES THAT THE PROJECT IS |
| | DESCRIBED IN DETAIL. NO MENTION OF THE NEW ACCESSIBLE |
| | TOILET ROOM IS IN THE DESCRIPTION OF WORK. PLEASE |
| | DESCRIBE THE PROJECT IN DETAIL AS REQUIRED. |
| | |
| | 2B. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING |
| | COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS |
| | WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE |
| | WHO HAVE DIFFICULTY BENDING OR STOOPING. |
| | |
| | 3B. SHT A-3 DETAIL D SHOWS THE W/C 1'9" OFF THE WALL TO |
| | THE CENTER OF THE FIXTURE. 1'8" REQUIRED PER FIG. 28. |
| | (SEE DETAIL D-1). PLEASE CORRELATE. |
| | |
| | 4B. SHT A-3 DETAIL D NOTE FOR LAV PIPING INSULATION IS |
| | NOT COMPLETE AND LEGIBLE. PLEASE CLARIFY. SECTIONS |
| | 106.1.1 & 11-4.19.4. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE ONE |
| | SET OF THEM LOOSELY ON TOP OF THE COLLATED |
| | PLANS TO BE REVIEWED. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |