| 2007-12-03 13:33:56 | |
| | ** DENIED 2NDD REVIEW ** |
| | |
| | ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEWS ARE |
| | STILL IN NEED OF ADDRESSING ALONG WITH SOME NEW |
| | COMMENTS BASED ON REVISED AND NEW PLANS SUBMITTED. |
| | |
| | 1) NOTE: PLEASE KNOW THE ADDRESS SITUATION HAS NOT YET |
| | BEEN DETERMINED FOR PROJECT. THE PERMIT APPLICATION AND |
| | RE-SUBMITTAL SHEET STILL INDICATES 6901-6905 YET PLANS |
| | CALLS FOR 6903. THE APPLIED LOCATION IN OUR SYSTEM AS |
| | OF THIS REVIEW IS 6901. |
| | THE ADDRESSING AND BUILDING REVIEW WILL BE ADDRESSING |
| | THESE COMMENTS HOWEVER THIS WILL AFFECT ALL SHEETS |
| | INCLUDING ELECTRICAL. |
| | PLEASE UPDATE ONCE ALL HAS BEEN DETERMINED. FBC |
| | 106.1.2, 106.3.5, FAC61G1-16.004 |
| | |
| | 2) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE |
| | CALCULATIONS PER 13-415.2. |
| | THIS IS TO INCLUDE OUTSIDE LIGHTING ALSO PER |
| | 13-415.2.ABC.1.3 |
| | THIS IS A NEW NOTE AS SCOPE ON ORIGINAL PLANS WAS NOT |
| | CLEAR. |
| | |
| | 3) NOTE: PLEASE SEE THAT THE NEW ELECTRICAL SERVICE AS |
| | SHOWN IS NOT PERMITTED. PLEASE KNOW AS THIS IS ONE |
| | BUILDING BY DEFINITION ONLY ONE ELECTRICAL SERVICE IS |
| | PERMITTED PER 230.2. |
| | PLEASE SUBMIT THE EXISTING RISER FOR NEW TENANT SPACE |
| | TO BE FED FROM THE EXISTING SERVICE OR THE EXISTING |
| | SERVICE WILL NEED TO BE UPGRADED FOR THE WHOLE |
| | BUILDING. |
| | |
| | 4) NOTE: PLEASE SEE THE LOAD CALCULATIONS INDICATE THE |
| | SIGN CIRCUIT AT 2500VA WHICH EXCEEDS THAT OF A 20AMP |
| | CIRCUIT. THE PANEL SCHEDULE INDICATES 15AMPS HOWEVER |
| | THIS DOES NOT CORRELATE WITH THE VA ON LOAD |
| | CALCULATIONS. |
| | PLEASE KNOW THE MINIMUM THAT IS REQUIRED BY THE NEC IS |
| | 1200 VA AT 125% FOR CONTINUOUS LOADS ON FEEDERS ETC. |
| | 600.5, 215.3, 230.42 |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |