| 2007-06-01 10:09:03 | *****DENIED***** |
| | |
| | |
| | 1.THE ACTUAL ADDRESS SHALL BE IN THE TITLE BLOCK OF |
| | EACH SUBMITTED PLAN SHEET.PLEASE BE ADVISED THAT THE |
| | PLAN SHEET INDICATES 6903 AS THE NUMERICAL ADDRESS |
| | WHEREAS THE ADDRESS NOTED IN THE CITY'S PERMIT SYSTEM |
| | INDICATES 6901. |
| | |
| | 2.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE |
| | REFERENCED. |
| | |
| | 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 4.THE REMOVAL AND (OR) REPLACEMENT OF BUILDING |
| | MATERIALS & SUPPLIES SHALL NOT HINDER OR INTERFERE WITH |
| | EMERGENCY RESPONSE ACCESS TO THE PROPERTY OR VICINITY |
| | THEREOF (INCLUDING STREETS, ROADS, FIRE LANES). |
| | |
| | 5.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL |
| | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR |
| | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| | |
| | 6.DISPLAY EXIT LIGHTS, EMERGENCY LIGHTS, AND THE |
| | LOCATION OF THE 2A:10BC FIRE RATED FIRE EXTINGUISHER(S) |
| | IN THIS OFFICE SPACE. |
| | |
| | 7.DOES THE PROPOSED STRUCTURE HAVE A FIRE ALARM |
| | AND/OR FIRE SPRINKLER SYSTEM IN ITS MAKEUP? |
| | |
| | 8.SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE EXTERIOR |
| | ELEVATION SO THAT IT IS DISTINGUISHABLE FROM THE OTHER |
| | SUITES.AS PER WEST PALM BEACH CODE,THOSE NUMBERS |
| | SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" |
| | IN WIDTH. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |