| 2007-04-15 19:53:29 | ** UNSAT ** |
| | |
| | ** PLEASE SEE ANY REFERENCES IN PLAN REVIEW NOTES TO |
| | CHAPTER 1 OF THE FBC ARE THAT WHICH IS ADOPTED BY THE |
| | CITY OF WEST PALM BEACH. |
| | |
| | 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| | ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| | UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLANS AT THIS TIME DO NOT INDICATE ANY CODES. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | |
| | 2) NOTE: PLEASE SEE FS 481.229 AS PLANS MUST BE DONE BY |
| | AND ARCHITECT AT A MINIMUM. PLANS FOR COMMERCIAL |
| | OCCUPANCY MAY NOT BE DONE BY A *RESIDENTIAL DESIGNER*. |
| | IF THERE ARE ANY QUESTIONS, PLEASE CONTACT THIS OFFICE |
| | OR STATE PROSECUTING ATTORNEY MR. DAVID MINACCI LEGAL |
| | COUNSEL TO THE BOARD OF ARCHITECTS. |
| | |
| | 3) NOTE: PLEASE COORDINATE THE ADDRESS FOR WORK BEING |
| | DONE. THE PALM BEACH COUNTY PROPERTY APPRAISER?S OFFICE |
| | INDICATES 6903, YET PERMIT APPLICATION INDICATE |
| | 6901-6905. |
| | IF THE PRIMARY ADDRESS IS 6903, SUITE OR UNIT NUMBERS |
| | MAY BE ASSIGNED AND SHALL ALSO BE INDICATED ON |
| | PLANS/TITLE BLOCKS. |
| | DOCUMENTS HAVE BEEN FORWARDED TO THE ADDRESSING |
| | REVIEWER. |
| | |
| | 4) NOTE: PLEASE CLARIFY IF WORK IS IN ONCE TENANT SPACE |
| | OR MORE THAN ONE? |
| | PLANS ARE NOT CLEAR AT THIS TIME FOR COMPLETE SCOPE OF |
| | WORK. |
| | PLEASE SUBMIT COMPLETE ELECTRICAL FOR NEW OR EXISTING |
| | FOR THIS SPACE. |
| | PLEASE INCLUDE NEW CIRCUITING ON PLANS AND CORRELATE |
| | WITH A PANEL SCHEDULE WHICH IS TO BE SUBMITTED. |
| | PLEASE INDICATE THE SIZE OF THE PANEL, SERVICE ETC. |
| | PLEASE SUBMIT LOADS, LOAD CALCULATIONS FOR SERVICE |
| | ETC. |
| | PLEASE SEE MISSING SIGN CIRCUITS. |
| | PLEASE SEE MISSING SHOW WINDOW RECEPTACLES. |
| | PLEASE SEE MISSING MINIMUM LIGHTING ON PLANS |
| | PLEASE SEE IF THESE ARE MULTIPLE TENANTS, NEED TO SHOW |
| | THE PANELS, OR HOUSE PANEL WHICH IS FEEDING NEW OUTSIDE |
| | LIGHTS. |
| | ETC ETC, |
| | 215.5, 408.4, 220.43, 600.5, 210.62, 240.4, 310.16 ETC |
| | PLEASE SEE THE 2005 NEC AS PLANS ARE NOT COMPLETE FOR |
| | SUFFICIENT ELECTRICAL REVIEW AT THIS TIME. |
| | AS THERE ARE MANY ITEMS MISSING, THERE MAY BE NEW |
| | COMMENTS WHEN PLANS ARE COMPLETED. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |