2007-04-05 19:04:49PLANNING AND ZONING:***** FAILED *****
  
 1.PROVIDE COMMENTS IN WRITING.
  
 2.THE PERMIT INDICATES, "NEW EXHAUST FANS ON ROOF,
 NEW ROOF-MOUNTED MAKE-UP FAN FOR 2ND FLOOR HOOD."THE
 PHOTOGRAPHS SHOWN IN MECHANICAL SHEET M-9, SHOW
 EXISTING HVAC AND EXHAUST FANS.ARE THEY PART OF THIS
 PERMIT? OR ARE THEY GOING TO BE REPLACED.PROVIDE A
 CROSS SECTION AND ELEVATION OF THE EQUIPMENT WITH
 RESPECT TO THE BUILDING, IN ORDER TO SHOW THAT THE
 MECHANICAL EQUIPMENT IS COVERED BY THE EXISTING
 PARAPET.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME AT THE
 NUMBER BELOW.
  