| Plan Review Notes For Permit 07030991 |
| Permit Number |
07030991 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-05-08 16:27:06 | *****DENIED***** | | | | | | | | | 1.THE NUMERICAL ADDRESS OF WHERE THE SCOPE OF WORK IS | | | TO BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH | | | SUBMITTED PLAN SHEET. | | | | | | 2.ON SHEET M-1, IN ADDITION TO GENERAL MECHANICAL | | | NOTE #8, INCLUDE THAT COMBUSTIBLE WASTE MATERIALS, | | | DUST, AND DEBRIS SHALL BE REMOVED FROM THE SITE DAILY | | | OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | | | 3.ALL EXIT COMPONENTS ARE TO BE MAINTAINED AT ALL | | | TIMES DURING THE SCOPE OF WORK. | | | | | | 4.IN ADDITION TO PLANS AND PERMIT NEEDED FOR THE | | | INSTALLATION OF THE HOOD SYSTEM, SEPARATE PLANS AND | | | PERMIT WILL BE REQUIRED FOR THE HOOD SUPPRESSION | | | SYSTEM. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|