| 2007-04-16 11:39:33 | DENIED PLAN REVIEW ONLY, NOT FOR PERMIT: REFERENCE: |
| | ** FBC-2004 PLUMBING. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. THE DESIGN PROFESSIONAL IS REQUIRED BY CHAPTER 481, |
| | FLORIDA STATUTES PART 1, TO AFFIX HIS OR HER OFFICIAL |
| | SEAL, SIGNATURE AND DATE TO SAID DRAWINGS. |
| | |
| | 2. THE ARCHITECTS FLORIDA REGESTERED LICENSE NUMBER |
| | MUST BE ON THE TITLE BLOCK OF THE DRAWING. FLORIDA |
| | STATUTES 63G-16.004. |
| | |
| | 3. PLEASE PROVIDE THE FOLLOWING INFORMATION ON THE |
| | RESUBMITTED DRAWINGS. |
| | A} AUTOMATIC IRRIGATION CONTROLLER: THE CONTROLLER |
| | SHALL BE CAPABLE OF INCORPORATING A RAIN SHUT OFF |
| | DEVICE TO OVERRIDE THE IRRIGATION CYCLE WHEN ADEQUATE |
| | RAINFALL HAS OCCURED, AS REQUIRED BY FLORIDA STATUTES, |
| | SECTION 373.62. |
| | B} THE RAIN SWITCH SHALL BE PLACED ON A STATIONARY |
| | STRUCTURE MINIMUM OF 5-FOOT (1524MM) CLEARANCE FROM |
| | OTHER OUTDOOR EQUIPMENT, FREE AND CLEAR OF ANY TREE |
| | CANOPY OR OTHER OVERHEAD OBSTRUCTIONS, AND ABOVE THE |
| | HEIGHT OF THE SPRINKLER COVERAGE. |
| | |
| | 4. SHEET IRR 10 WET/WELL INTAKE FLUME DETAIL: PLEASE |
| | INDICATE THE WATER SOURCE (LAKE OR CANNEL) FOR THE WET |
| | WELL THROUGH THE 24" X 100' SDR 35 PVC INTAKE FLUME ON |
| | THE RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |