| 2007-04-19 11:40:07 | | | | INCOMPLETE INFORMATION | | | | | | PROVIDE INFORMATION REGARDING SERVICE RATING, 1 OR 3 | | | PHASE, VOLTAGE AND AMPERAGE. PROVIDE A RISER PER 215.5, | | | OVERCURRENT PROTECTION FOR THE EQUIPMENT PER 240 AND | | | 430, ALL CONDUIT AND CONDUCTOR TYPES AND SIZES. ALL | | | DISCONNECT LOCATIONS AS REQUIRED PER 225. | | | | | | SUBMIT SPECIFICATIONS FOR THE GEAR BEING INSTALLED. | | | | | | THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. | | | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417 | | | FS, RESPECTIVELY. THE CONTRACTOR OF RECORD MAY BE THE | | | DESIGN PROFESSIONAL IF EXEMPTIONS UNDER THOSE STATUTES | | | ARE APPLICABLE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|