2007-04-19 11:40:07 
 INCOMPLETE INFORMATION
  
 PROVIDE INFORMATION REGARDING SERVICE RATING, 1 OR 3
 PHASE, VOLTAGE AND AMPERAGE. PROVIDE A RISER PER 215.5,
 OVERCURRENT PROTECTION FOR THE EQUIPMENT PER 240 AND
 430, ALL CONDUIT AND CONDUCTOR TYPES AND SIZES. ALL
 DISCONNECT LOCATIONS AS REQUIRED PER 225.
  
 SUBMIT SPECIFICATIONS FOR THE GEAR BEING INSTALLED.
  
 THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY. THE CONTRACTOR OF RECORD MAY BE THE
 DESIGN PROFESSIONAL IF EXEMPTIONS UNDER THOSE STATUTES
 ARE APPLICABLE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  