| Plan Review Notes For Permit 07030973 |
| Permit Number |
07030973 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-04-03 12:00:47 | | | | | | | | | | NONCOMPLIANT | | | | | | 1} THE ARHCHITECTS SEAL ON THE PLANS SUBMITTED IS NOT | | | AN "IMPRESSION TYPE" AS REQUIRED BY ARTICLE | | | 481.221FLORIDA STATUTES. | | | | | | 2} THE TITLE BLOCK FOR THE DESIGNER OF RECORD MUST | | | CONTAIN A CERTIFICATE OF AUTHORIZATION PER F.A.C. | | | | | | 3} THE DISCONNECTS MUST BE GROUPED PER 230.72. IN THIS | | | CASE ALL IN THE SAME ROOM. A METER OUTSIDE WITH THE | | | EXISTING ONE AND A NIPPLE TO A NEW 200 AMP DISCONNECT | | | WOULD MEET THIS REQUIREMENT. PLEASE INDICATE COMPLIANCE | | | ON THE PLANS. | | | | | | 4} CHANGE THE DESCRIPTION OF THE PROJECT ON THE | | | APPLICATION TO MATCH THE WORK INTENDED. SEE " SERVICE | | | UPGRADE-----", THIS IS ADDING TO SERVICE. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|