Plan Review Notes
Plan Review Notes For Permit 07030967
Permit Number 07030967
Review Stop E
Sequence Number 4
Notes
Date Text
2008-02-25 08:33:57 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} INCREASE THE VALUE OF THE JOB TO INCLUDE THE
 ADDITIONAL WORK, LABOR AND MATERIAL ADJUST THE VALUE AT
 THE PERMIT CLERK?S DESK, AND PAY THE DIFFERENCE IN FEES
 PRIOR TO RESUBMITTING.
  
 2} THE ARCHITECT?S SIGNATURE IS A PHOTOCOPY. WHEN
 SUBMITTING FOR PERMITTING THE SIGNATURE MUST BE WET PER
 481.221(1)(A) FLORIDA STATUTES.PLEASE NOTE THAT HAND
 DRAWN CHANGES TO THE PLAN ARE NOT ACCEPTABLE AS THEY
 CANNOT BE VERIFIED AS BEING MADE BY THE DESIGNER OF
 RECORD AS REQUIRED BY FS 481.
  
 3} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT
 SIZE AND TYPE, GROUNDING DETAILS, LOAD CALCULATIONS,
 PANEL SCHEDULES, SERVICE EQUIPMENT AND PANEL LOCATIONS
 PER 106.3.5.4 FBC. 215.5NEC.
  
 4} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  