Plan Review Notes
Plan Review Notes For Permit 07030967
Permit Number 07030967
Review Stop B
Sequence Number 2
Notes
Date Text
2007-10-16 10:29:08RESIDENTIAL ALTERATION BUILDING REVIEW SECOND
 CHECKLIST.
 REVIEW DONE UNDER EXISTING BUILDING CODE 2004,FLORIDA
 RESIDENTIAL CODE 2004 AND FBC 2004 WITH 2007
 REVISIONS.
  
 ***NOTE: SCOPE OF WORK WAS CHANGED.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13FLORIDA STATUTE.
  
 2- DESIGNER OF RECORD NEED TO SPECIFYROOF SHEATHING
 NAILTYPEAND SPACING INCLUDING NAILING AT ZONE 3 AS
 REQUIRED BY SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 3- SPECIFY WALL SHEATHING NAIL TYPE AND SPACING.SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
 ***NOTE: SEE HARDIPLANK PRODUCT APPROVAL FOR SHEATHING
 REQUIREMENTS.
  
 4- HARDIPLANKDRAWINGS ON SHEET A2 ARE NOT LEGIBLE.
 NEED CLEAR AND LEGIBLE DRAWINGS AS REQUIRED BY SEC.
 106.1.3 CITY AMENDMENTS TO FBC 2004.
 ***ALSO,COORDINATE INFORMATION WITH PRODUCT APPROVAL
 TO AVOID DISCREPANCIES AND EXPEDITE THE REVIEW PROCESS.
 SEE REQUIRED STUD SPACING,SHEATHING THICKNESSS, ETC.
  
  
 5- TYPICAL WINDOW/DOOR OPENING FRAMING DETAIL ON SHEET
 A1:REVISE SPECIFIED CONNECTORS. HUGHES IS OUT OF
 BUSINESS.
  
 6- BASE PLATE DETAIL ON SHEET A1: SPECIFY HOW LONG ARE
 THE 1/2" J BOLTS.SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 7- TYPICAL WALL SECTION ON SHEET A1:
 A) REVISE CS-18CONNECTOR SPECIFIED TO ATTACH WALL
 TO STEM WALL.NEED TO SPECIFY WOOD TO MASONRY
 CONNECTOR. SEE CATALOG FOR PROPER CONNECTOR TYPE AND
 TYPE AND NUMBER OF FASTENERS.OTHERWISE PROVIDE
 COMPLETE ENGINEERING ANALYSIS FOR NAIL TYPE AND NUMBER
 THAT DIFFER FROM THOSE TESTED AND PUBLISHED BY THE
 MANUFACTURER. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 B) REVISE NUMBER AND TYPE OF FASTENERS SPECIFIED FOR
 CS-18 AT CONNECTION TO ROOF TRUSS. SEE CATALOG.
 OTHERWISE PROVIDE COMPLETE ENGINEERING ANALYSIS FOR
 FASTENER TYPE AND NUMBER OF FASTENERS THAT DON'T MATCH
 THOSE TESTED AND PUBLISHED BY THE MANUFACTURER. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 8- THE DESIGN PROFESSIONAL MUST ELECT THE ALTERATION
 LEVEL AS REQUIRED BY SEC. 301.5 OF EXISTING BUILDING
 CODE 2004.
  
 9- IDENTIFY WINDOWS IN BEDROOMS THAT ARE GOING TO BE
 REPLACEDTO VERIFY COMPLIANCE WITH THE EGRESS
 REQUIREMENTS OF SEC. 505 OF EXISTING BUILDING 2004.
  
 10 PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) HARDIPLANK.NOA 02-0729.02 SUBMITTED EXPIRED ON
 MAY 01/2007.
  
 B) ALLSIMPSON OR USP STRUCTURAL CONNECTORS
 SPECIFIED ON PLANS.
 ***NOTE: PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL PAGE
 AND PAGE SHOWING THE CONNECTOR TO EXPEDITE REVIEW AND
 SAVE PAPER.
  
 C) ROOF SHINGLES.
  
 11- DESIGNER OF RECORD NEEDS TO REVIEW AND APPROVE IN
 WRITING (NOT SIGNING AND SEALING)ALL PRODUCT
 APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS
 TO FBC 2004
  
 12- ARCHITECT TO REVIEW PRODUCT APPROVAL FOR