| Plan Review Notes For Permit 07030967 |
| Permit Number |
07030967 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-04-12 09:56:05 | *** DENIED *** | | | 1) ENERGY CALCULATIONS NEED TO BE ON FORM600A-04R, | | | SEE 2004 FBC 13-600.3.A (12-8-06 REVISION). | | | | | | 2) PLANS SHOW THE SOUTH EXTERIOR WALL OF THE NEW | | | ADDITION TO BE 6" WHICH WILL REQUIRE AN R-19 MINIMUM | | | INSULATION, SEE 2004 FBC 13-602.1C.1, PLEASE SHOW ON | | | PLANS. | | | | | | 3) ENERGY CALCULATIONS AND THE MECHANICAL PLANS ARE | | | CALLING FOR A FIVE TON A/C SYSTEM 48,000 SENSIBLE BTU'S | | | WHICH IS TO LARGE, SEE THE COOLING LOAD CALCULATIONS | | | ARE CALLING FOR 29,044 SENSIBLE BTU'S, THE PLANS CAL | | | ONLY CALL FOR 15% MORE THAN THE COOLING LOAD CAL'S, SEE | | | 2004 FBC 13-607.1.ABC.1.1, PLEASE CORRECT. | | | | | | 4) SEE THE MECHANICAL PLANS "WALL CAP DETAIL" IS | | | CALLING FOR AN INSECT/BIRD SCREEN, A SCREEN MAY NOT BE | | | IN THE CLOTHS DRYER VENT BUT WILL NEED A BACKDRAFT | | | DAMPER, SEE 2004 FBC/R M1501.1, PLEASE CORRECT. | | | | | | 5) CLOTHES DRYER VENT TERMINATION MAY NOT DISCHARGE | | | NEAR THE A/C CONDENSER UNIT, SEE2004 FBC/M 501.2, | | | PLEASE CORRECT . | | | | | | 6) SEE MECHANICAL PLANS SHOWING A 10" SUPPLY AIR DUCT | | | TO THE MASTER BATHROOM, BELIEVED TO BE A TYPE-O, PLEASE | | | CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|