Plan Review Notes
Plan Review Notes For Permit 07030967
Permit Number 07030967
Review Stop M
Sequence Number 1
Notes
Date Text
2007-04-12 09:56:05*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON FORM600A-04R,
 SEE 2004 FBC 13-600.3.A (12-8-06 REVISION).
  
 2) PLANS SHOW THE SOUTH EXTERIOR WALL OF THE NEW
 ADDITION TO BE 6" WHICH WILL REQUIRE AN R-19 MINIMUM
 INSULATION, SEE 2004 FBC 13-602.1C.1, PLEASE SHOW ON
 PLANS.
  
 3) ENERGY CALCULATIONS AND THE MECHANICAL PLANS ARE
 CALLING FOR A FIVE TON A/C SYSTEM 48,000 SENSIBLE BTU'S
 WHICH IS TO LARGE, SEE THE COOLING LOAD CALCULATIONS
 ARE CALLING FOR 29,044 SENSIBLE BTU'S, THE PLANS CAL
 ONLY CALL FOR 15% MORE THAN THE COOLING LOAD CAL'S, SEE
 2004 FBC 13-607.1.ABC.1.1, PLEASE CORRECT.
  
 4) SEE THE MECHANICAL PLANS "WALL CAP DETAIL" IS
 CALLING FOR AN INSECT/BIRD SCREEN, A SCREEN MAY NOT BE
 IN THE CLOTHS DRYER VENT BUT WILL NEED A BACKDRAFT
 DAMPER, SEE 2004 FBC/R M1501.1, PLEASE CORRECT.
  
 5) CLOTHES DRYER VENT TERMINATION MAY NOT DISCHARGE
 NEAR THE A/C CONDENSER UNIT, SEE2004 FBC/M 501.2,
 PLEASE CORRECT .
  
 6) SEE MECHANICAL PLANS SHOWING A 10" SUPPLY AIR DUCT
 TO THE MASTER BATHROOM, BELIEVED TO BE A TYPE-O, PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.