| 2007-04-11 16:16:53 | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} THE #2 CU GROUNDING ELECTRODE CONDUCTOR WHILE NOT A |
| | VIOLATION, MUST BE INSTALLED IF IT IS ON THE PLAN. THE |
| | REQUIRED SIZE IS #4 CU PER 250.66. |
| | |
| | 2} PLEASE INDICATE THE CONDUCTOR SIZE FROM THE METER TO |
| | THE DISCONNECT. PER 310.15 (B)(6), OR 310.16. |
| | |
| | 3} 230.70 GENERAL. |
| | MEANS SHALL BE PROVIDED TO DISCONNECT ALL CONDUCTORS IN |
| | A BUILDING OR OTHER STRUCTURE FROM THE SERVICE-ENTRANCE |
| | CONDUCTORS. THE PANEL IS LISTED AS MAIN LUG ONLY. IF IT |
| | DOES NOT HAVE A MAIN BREAKER THEN A DISCONNECT MUST BE |
| | INSTALLED AFTER THE METER. |
| | |
| | 4} PER 110.9 AND 110.10: OBTAIN THE |
| | AVAILABLE FAULT CURRENT AT THE UTILITY |
| | AND CALCULATE THE SAME AT THE EQUIPMENT. |
| | INDICATE THE AIC RATING FOR THE |
| | EQUIPMENT IS EQUAL TO OR GREATER THAN |
| | THE AVAILABLE FAULT. |
| | |
| | 5} ALSO VERIFY FROM FPL THAT THE SERVICE IS 3 PHASE |
| | 120/208 VOLT. THAT AREA IS ONLY KNOWN TO HAVE SINGLE |
| | PHASE 120/240 VOLT TRANSFORMERS. THE VOLTAGE RATING OF |
| | THE PANEL ON THE PLAN IS NOT RATED FOR A 120/240 |
| | VOLTAGE. |
| | |
| | 6} THE AIR HANDLER OVERCURRENT PROTECTION, CIRCUIT |
| | #20,22, IS NOT COMPLIANT PER 424.3(B) NEC.- |
| | BRANCH-CIRCUIT SIZING FIXED ELECTRIC SPACE HEATING |
| | EQUIPMENT SHALL BE CONSIDERED CONTINUOUS LOAD.(125%) |
| | 10000/240=41.66X125%=52 AMPS= 60 AMP BREAKER(240.4) AND |
| | #6 CONDUCTORS (310.16). |
| | |
| | 7} PLEASE INDICATE THE CODE THE PLAN WAS DESIGNED AND |
| | APPLICATION WAS MADE UNDER. 2004 FBC AND 2005 NEC. |
| | |
| | 8} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A) (2), |
| | SEE MASTER BEDROOM WALL BETWEEN ENTRY AND THE |
| | BATHROOM. |
| | |
| | 9} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.1 |
| | RESIDENTIAL FLORIDA BUILDING CODE. THIS IS IN ALL |
| | BEDROOMS. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | [email protected] |