| 2007-04-24 16:53:40 | BUILDING REVIEW CHECKLIST: |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| | SEC. 713. 13 FLORIDA STATUTE. |
| | |
| | 2- AFTER DRAWINGS ARE REVISED BRING THEM TO PALM BEACH |
| | COUNTY TO PAY IMPACT FEES. BRING BACK STAMPED PLANS AND |
| | COPY OF PAID RECEIPT. |
| | |
| | 3- ARCHITECT TO PROVIDE THE FIRM'S NUMBER IN THE TITLE |
| | BLOCK AS REQUIRED BY SEC. 61G1-16.004OF FLORIDA |
| | ADMINISTRATIVE CODE. |
| | |
| | 4- SURVEY, SITE PLAN AND FLOOR PLAN DON'T MATCH. REVISE |
| | AS REQUIRED. |
| | |
| | 5- AREA CALCULATIONS DON'T ADD UP. REVISE AS REQUIRED. |
| | |
| | 6- REVISE INFORMATION IN SURVEY REGARDING THE FLOOD |
| | ZONE ELEVATION.FLOOD ZONE IN THE CITY OF WEST PALM |
| | BEACH IS DETERMINED BY REFERRING TO MAP DATED MARCH |
| | 1ST, 1979.SEE MAP AND REVISE AS REQUIRED. |
| | |
| | 7- SHEET A-1: |
| | A) SPECIFYALL DESIGN LOADS INCLUDING ALL DEAD, |
| | LIVE AND WIND LOADS AS REQUIRED BY SEC. R301 AND TABLE |
| | R301.5OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | B) REVISE DESIGN WIND LOADS FOR ROOF FOR CORNER |
| | AREAS. SEE REVISED TABLE 1609.6.2.1(2) FBC 2004. |
| | |
| | C) SPECIFY ATTIC ACCESS SIZE. SEC. R807 OF 2004 |
| | FLORIDA RESIDENTIAL CODE. |
| | |
| | D) THICKNESS OF ROOF SHEATHING TO MATCH. SEE DETAIL |
| | 2 AND ROOF FRAMING PLAN. REVISE AS REQUIRED. |
| | |
| | E) POST & BEARING WALL CONNECTION DETAIL AND |
| | CONNECTION SCHEDULE TO MATCH.ALSO, SEE CURRENT |
| | SIMPSON CATALOG AND REVISE TYPE,NUMBER OF FASTENERS |
| | AND SPECIFIC LOADS. OTHERWISE, PROVIDE COMPLETE |
| | ENGINEERING ANALYSIS FOR INFORMATION THAT DIFFER FROM |
| | THAT TESTED AND PUBLISHED BY THE MANUFACTURER. SEC. |
| | 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | F) PROVIDE COMPLETE DETAIL AND SPECS FOR GABLE END |
| | AT ENTRY PORCH. SPECIFY ALL FASTENERS, ETC. SEC. |
| | 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | G) POST & BEARING WALL CONNECTION DETAILAND WALL |
| | SECTION -1 DON'T MATCH. REVISE AS REQUIRED. |
| | |
| | H) ROOF FRAMING PLAN: |
| | * SPECIFY SIZE AND NUMBER OF HEADERS. SEC. 106.1.2 CITY |
| | AMENDMENT STO FBC 2004. |
| | ** CLARIFY HOW ARE WINDOWS AT MEDIA ROOM INSTALLED. |
| | ROOF FRAMING PLAN SHOWS 3 SEPARATEHEADERS?. PROVIDE |
| | COMPLETE DETAILS AND SPECS. SEC. 106.1.2 CITY |
| | AEMNDMENTS TO FBC 2004. |
| | |
| | I) STRUCTURAL BUCK DETAIL FOR DOORS AND WINDOWS |
| | DON'T APPLY TO THIS TYPE OF CONSTRUCTION. PROVIDE |
| | DETAILS THAT APPLY TO THIS PROJECT.SEE SEC. R613.6.2 |
| | TO SEE PROPER WAY OF INSTALLING STRUCTURAL BUCKS AND |
| | PROVIDE INFORMATION AS REQUIRED. |
| | |
| | J) SEE SECTION R803.2.3.1 OF 2004 FLORIDA |
| | RESIDENTIAL CODE AND REVISE ROOF SHEATHING FASTENING AS |
| | REQUIRED. |
| | |
| | K) 2X4 EXTERIOR FRAMED WALLS REQUIRE R11 MIN. WHILE, |
| | 2X6 EXTERIOR WALLS REQUIRE R-19 MIN. SEE SEC. |
| | 13-602.1.C.1.1 OF 2004 FBC AND REVISE PLANS/DETAILS AS |
| | REQUIRED. |
| | |
| | |
| | 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| | 9B-72 FOR: |
| | A) GABLE END ALUMINUM VENT. |
| | ***NOTE: ARCHITECT TO SPECIFY IN PLANS SIZE OF VENT AND |
| | CONSIDER THIS VENTS IN THE ATTIC VENTILATION |
| | CALCUALTIONS. |
| | |
| | 9- ARCHITECT TO REVIEW AN APPROVE IN WRITING (NOT |
| | SIGNING AND SEALING)ALL PRODUCT APPROVALS AS REQUIRED |
| | BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 10- TYPICAL WALL SECTION TO PROVIDE COMPLETE |
| | SPECIFICATIONS FOR WALL SHEATHING THICKNESS AND |
| | FASTENING. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 11- PROVIDE COMPLETE FRAMING DETAILS FOR EXTERIOR DOORS |
| | AND WINDOWS. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 12- ENERGY CALCULATIONS: |
| | A) PROVIDE REVISED FORM 600A-2004 R. |
| | |
| | B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM. |
| | |
| | 13- ENERGY CALCULATIONS ARE TAKEN THE CEILING FAN |
| | CREDIT. THEREFORE, NEED TO SPECIFY ON PLANS SPECIFIC |
| | SIZE OF FAN TO BE INSTALLED AS REQUIRED BY TABLE |
| | 13-607.1.A.1 OF 2004 FBC. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |