Plan Review Notes
Plan Review Notes For Permit 07030967
Permit Number 07030967
Review Stop B
Sequence Number 1
Notes
Date Text
2007-04-24 16:53:40BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713. 13 FLORIDA STATUTE.
  
 2- AFTER DRAWINGS ARE REVISED BRING THEM TO PALM BEACH
 COUNTY TO PAY IMPACT FEES. BRING BACK STAMPED PLANS AND
 COPY OF PAID RECEIPT.
  
 3- ARCHITECT TO PROVIDE THE FIRM'S NUMBER IN THE TITLE
 BLOCK AS REQUIRED BY SEC. 61G1-16.004OF FLORIDA
 ADMINISTRATIVE CODE.
  
 4- SURVEY, SITE PLAN AND FLOOR PLAN DON'T MATCH. REVISE
 AS REQUIRED.
  
 5- AREA CALCULATIONS DON'T ADD UP. REVISE AS REQUIRED.
  
 6- REVISE INFORMATION IN SURVEY REGARDING THE FLOOD
 ZONE ELEVATION.FLOOD ZONE IN THE CITY OF WEST PALM
 BEACH IS DETERMINED BY REFERRING TO MAP DATED MARCH
 1ST, 1979.SEE MAP AND REVISE AS REQUIRED.
  
 7- SHEET A-1:
 A) SPECIFYALL DESIGN LOADS INCLUDING ALL DEAD,
 LIVE AND WIND LOADS AS REQUIRED BY SEC. R301 AND TABLE
 R301.5OF 2004 FLORIDA RESIDENTIAL CODE.
  
 B) REVISE DESIGN WIND LOADS FOR ROOF FOR CORNER
 AREAS. SEE REVISED TABLE 1609.6.2.1(2) FBC 2004.
  
 C) SPECIFY ATTIC ACCESS SIZE. SEC. R807 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 D) THICKNESS OF ROOF SHEATHING TO MATCH. SEE DETAIL
 2 AND ROOF FRAMING PLAN. REVISE AS REQUIRED.
  
 E) POST & BEARING WALL CONNECTION DETAIL AND
 CONNECTION SCHEDULE TO MATCH.ALSO, SEE CURRENT
 SIMPSON CATALOG AND REVISE TYPE,NUMBER OF FASTENERS
 AND SPECIFIC LOADS. OTHERWISE, PROVIDE COMPLETE
 ENGINEERING ANALYSIS FOR INFORMATION THAT DIFFER FROM
 THAT TESTED AND PUBLISHED BY THE MANUFACTURER. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 F) PROVIDE COMPLETE DETAIL AND SPECS FOR GABLE END
 AT ENTRY PORCH. SPECIFY ALL FASTENERS, ETC. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 G) POST & BEARING WALL CONNECTION DETAILAND WALL
 SECTION -1 DON'T MATCH. REVISE AS REQUIRED.
  
 H) ROOF FRAMING PLAN:
 * SPECIFY SIZE AND NUMBER OF HEADERS. SEC. 106.1.2 CITY
 AMENDMENT STO FBC 2004.
 ** CLARIFY HOW ARE WINDOWS AT MEDIA ROOM INSTALLED.
 ROOF FRAMING PLAN SHOWS 3 SEPARATEHEADERS?. PROVIDE
 COMPLETE DETAILS AND SPECS. SEC. 106.1.2 CITY
 AEMNDMENTS TO FBC 2004.
  
 I) STRUCTURAL BUCK DETAIL FOR DOORS AND WINDOWS
 DON'T APPLY TO THIS TYPE OF CONSTRUCTION. PROVIDE
 DETAILS THAT APPLY TO THIS PROJECT.SEE SEC. R613.6.2
 TO SEE PROPER WAY OF INSTALLING STRUCTURAL BUCKS AND
 PROVIDE INFORMATION AS REQUIRED.
  
 J) SEE SECTION R803.2.3.1 OF 2004 FLORIDA
 RESIDENTIAL CODE AND REVISE ROOF SHEATHING FASTENING AS
 REQUIRED.
  
 K) 2X4 EXTERIOR FRAMED WALLS REQUIRE R11 MIN. WHILE,
 2X6 EXTERIOR WALLS REQUIRE R-19 MIN. SEE SEC.
 13-602.1.C.1.1 OF 2004 FBC AND REVISE PLANS/DETAILS AS
 REQUIRED.
  
  
 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) GABLE END ALUMINUM VENT.
 ***NOTE: ARCHITECT TO SPECIFY IN PLANS SIZE OF VENT AND
 CONSIDER THIS VENTS IN THE ATTIC VENTILATION
 CALCUALTIONS.
  
 9- ARCHITECT TO REVIEW AN APPROVE IN WRITING (NOT
 SIGNING AND SEALING)ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 10- TYPICAL WALL SECTION TO PROVIDE COMPLETE
 SPECIFICATIONS FOR WALL SHEATHING THICKNESS AND
 FASTENING. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 11- PROVIDE COMPLETE FRAMING DETAILS FOR EXTERIOR DOORS
 AND WINDOWS. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 12- ENERGY CALCULATIONS:
 A) PROVIDE REVISED FORM 600A-2004 R.
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM.
  
 13- ENERGY CALCULATIONS ARE TAKEN THE CEILING FAN
 CREDIT. THEREFORE, NEED TO SPECIFY ON PLANS SPECIFIC
 SIZE OF FAN TO BE INSTALLED AS REQUIRED BY TABLE
 13-607.1.A.1 OF 2004 FBC.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712