| Plan Review Notes For Permit 07030949 |
| Permit Number |
07030949 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-04-18 13:24:56 | DENIED; | | | | | | 1.PAGE LS-1 (APPLICABLE CODES) THE BUILDING IS | | | SEPERATED INTO TWO OCCUPANCY CLASSIFICATIONS, EACH | | | OCCUPANCY MUST MEET FBC- 2004 PLUMBING CODE TABLE | | | 403.1. A DRINKING FOUNTAIN IS REQUIRED IN THE OFFICE | | | AREA. | | | 2. PAGE P-1.1 ( WATER RISER DIAGRAM) WATER HAMMER | | | ARRESTORS ARE REQUIRED IN KITCHEN, PER SECTION 604.9. | | | PLEASE SHOW ON PLANS AND SPEC OUT TYPE TO BE USED. | | | 3. PAGE P-1.1 PLUMBING FIXTURES, SK-2 KITCHEN SINK MUST | | | MEET THE HANDICAP CODE SECTION 11-4.24.4 DEPTH OF SINK | | | TO BE NO DEEPER THAN 6 1/2 INCH. THE FAUSET MUST BE | | | LEVER TYPE, SECTION 11-4.24.7. GARBAGE DISPOSER CAN NOT | | | INTERFERE WITH THE KNEE SPACE REQUIRED PER SECTION | | | 11-4.24.3. A INTERIOR DESIGNER MAY NOT COMPLY WITH THE | | | HANDICAP CODE, THIS WOULD CAUSE NON-COMPLIANCE TO THE | | | CODE REQUIREMENTS. | | | 4. THE BATHROOMS ARE NOT PRIVATE. MORE THAN ONE PERSON | | | WILL BE USING THE BATHROOMS. SEE SECTION 11-4.1.3(11). | | | PAGE A-5 DETAIL 17, MISSING TOTLE WIDTH OF BATHROOM | | | SHOW TOILET AT 18" OF SIDE WALL SEE FIGURE 28 IN H/C | | | CODE. GRAB BARS ARE REQUIRED. | | | 5. WALL AND FLOOR FINISHES NOT FOUND ON PLANS FOR | | | BATHROOM WALLS AND FLOOR. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|