| Date |
Text |
| 2008-07-18 11:24:00 | ** DENIED ** |
| | |
| | ** REVISIONS SUBMITTED. |
| | SOME SHEETS ARE OK HOWEVER SHEET E2.2 HAS NOTES BELOW. |
| | RESPONSE LETTER FROM DESIGNER MENTIONS A SHEET 3.2 |
| | HOWEVER NO SHEET 3.2 WAS SUBMITTED. |
| | SHEETS 4.1,4.2 AND 6.2 OK |
| | |
| | 1) NOTE: PLEASE SEE NEW NOTE #12 ON 2.2 WHICH STATES |
| | LIGHTING CONTROLS/SYSTEM BY OTHERS HOWEVER TO DATE NO |
| | PLANS OR PERMIT APPLICATION HAS BEEN SUBMITTED. IF THE |
| | LIGHTING CONTROLS ARE GOING TO BE BY OTHER THEN PLANS |
| | WILL NEED TO BE SUBMITTED ALONG WITH PERMIT |
| | APPLICATION. |
| | 13-415.1.ABC.1.1,.1.2,.1.3. |
| | |
| | IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |