| Date |
Text |
| 2007-11-30 07:44:23 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | ******FROM PREVIOUS REVIEWS: |
| | |
| | 1. OK |
| | |
| | 2. SHT 1-16.C PER TABLE 403.1 3 DRINKING FOUNTAINS ARE |
| | REQUIRED. PLEASE INDICATE THE LOCATION OF EACH DRINKING |
| | FOUNTAIN. |
| | ****RESPONSE NOTED, BUT ON THE 16TH FLOOR PLAN, ONE |
| | DRINKING FOUNTAIN HAS SANITARY, BUT NO WATER SUPPLY & |
| | ONE DRINKING FOUNTAIN SHOWS NO SANITARY OR WATER |
| | SUPPLY. WATER AND DRAINAGE ARE REQUIRED AT EACH |
| | FIXTURE. SECTIOND 301.3 & 301.4. |
| | ******NO RESPONSE, BUT THE DRINKING FOUNTAIN IN ROOM |
| | 1633 STILL SHOWS NO WATER SUPPLY. SEE SHEET P3.2. |
| | |
| | 3. SHT 1-16.C BATHROOM (1608) SHALL BE ACCESSIBLE OR |
| | ADAPTABLE PER SECTIONS 11-4.22 OR 11-4.1.3(11). PLEASE |
| | SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTIONS |
| | 11-4.16, 11-4.19 & 11-4.21 WITH ALL SUBSECTIONS IF |
| | BATHROOM IS TO BE ACCESSIBLE. SUBMIT A DETAIL SHOWING |
| | ALL BACKING FOR GRAB BARS FOR THE W/C & SHOWER, SPACING |
| | FOR THE W/C, (MIN. 33" WITH THE W/C BEING 18" OFF THE |
| | WALL AND MIN. 15" OFF THE SHOWER), A TURNING AREA IN |
| | THE BATHROOM, THE VALVE LOCATION FOR THE SHOWER, AND A |
| | CURB DETAIL OF THE SHOWER, (MAX 1/2"). |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******NO RESPONSE, AND NO DETAIL HAS BEEN SUBMITTED |
| | SHOWING THE BACKING REQUIRED FOR THE GRAB BARS FOR THE |
| | W/C AND SHOWER. |
| | |
| | 4. SHT 1-16.C THE SINKS IN ROOMS 1613, 1628, 1633, 1643 |
| | & 1674 SHALL BE ACCESSIBLE. PLEASE SUBMIT A DETAIL |
| | SHOWING COMPLIANCE WITH SECTION 11-4.24 AND ALL |
| | SUBSECTIONS. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******NO RESPONSE, BUT THE CLEAR FLOOR SPACE SHALL BE |
| | SHOWN ON THE FLOOR PLAN FOR EACH SINK. THE FLOOR PLAN |
| | FOR THE 16TH FLOOR DOES NOT SHOW THE BAR SINKS |
| | INDICATED ON THE PLUMBING SHEETS. PLEASE CORRELATE THE |
| | INFORMATION ON THE ARCHITECTUAL SHEETS AND THE PLUMBING |
| | SHEETS. SHEET 1-PA-2 DETAILS 1&2 ONLY SHOW A 24" |
| | OPENING UNDER THE SINKS WHERE 30" CLEAR FLOOR SPACE IS |
| | REQUIRED. SECTIONS 106.1.1 & 11-4.24.5. |
| | |
| | 5. OK NO WATER OR DRAIN INDICATED AT MEETING WITH |
| | REPRESENTATIVES OF THE DESIGN TEAM. |
| | 6. OK |
| | 7. OK |
| | |
| | 8. SUBMIT DETAILS FOR THE MEN'S & WOMEN'S TOILET ROOMS |
| | SHOWING COMPLIANCE WITH SECTIONS 11-4.16, 11-4.17, |
| | 11-4.18, 11-4.19 & 11-4.22 WITH ALL SUBSECTIONS. ****NO |
| | RESPONSE, NOT ADDRESSED.--THIS SHALL APPLY FOR THE |
| | NEW TOILET ROOMS ADDED TO EACH FLOOR ALSO. ******NO |
| | RESPONSE, BUT DETAILS FOR ROOMS 1672, 1673, 1584 & 1585 |
| | WERE NOT SUBMITTED. THESE TOILET ROOMS SHALL BE |
| | ACCESSIBLE. |
| | |
| | 9. SUBMIT A DETAIL FOR THE ACCESSIBLE DRINKING |
| | FOUNTAINS. SHOW COMPLIANCE WITH SECTION 11-4.15 WILL |
| | ALL SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A) |
| | PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR |
| | STOOPING. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******NO RESPONSE. SHOW THE CLEAR FLOOR SPACE FOR ALL |
| | ACCESSIBLE DRINKING FOUNTAINS. MINIMUM 50% OF THE |
| | DRINKING FOUNTAINS SHALL BE ACCESSIBLE AND ONLY ONE IS |
| | INDICATED ACCESSIBLE ON EACH FLOOR. |
| | |
| | 10. OK |
| | 11. OK |
| | |
| | 12. SHT 1-15.C THE SINK IN ROOM 1520SHALL BE |
| | ACCESSIBLE. PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE |
| | WITH SECTION 11-4.24 AND ALL SUBSECTIONS. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******NO RESPONSE, NOT ADDRESSED. |
| | |
| | 13. OK (NEW ENGINEER) |
| | 14. OK |
| | 15. OK |
| | 16. OK |
| | 17. OK |
| | 18. OK |
| | 19. OK |
| | 20. OK |
| | 21. OK |
| | 22. OK |
| | 23. OK |
| | 24. OK |
| | 25. OK |
| | 26. OK |
| | 27. OK |
| | 28. OK |
| | |
| | 29. SHT P51 THERMAL EXPANSION CONTROL IS REQUIRED FOR |
| | THE WATER HEATERS ON THE 15TH & 16TH FLOORS. PLEASE |
| | INDICATE THE METHOD OF CONTROL. SECTION 607.3.2. |
| | ****RESPONSE NOTED, BUT CALCULATIONS SHALL BE PROVIDED |
| | SHOWING THE CORRECT SIZE REQUIRED FOR 130 GALLONS, |
| | (TOTAL OF BOTH WATER HEATERS). SEE ATTACHED SHEET FOR |
| | AN EXAMPLE OF CALCULATIONS. INDICATE MANUF. AND MODEL |
| | WHEN SUMBITTING CALCULATIONS. |
| | ******NO RESPONSE, NOT ADDRESSED. |
| | |
| | 30. OK |
| | 31. OK |
| | |
| | ***********NEW COMMENTS*********** |
| | |
| | 1B. OK |
| | |
| | 2B. SHT P61 DELETE THE CHECK VALVES FROM THE WATER |
| | RISER DIAGRAMS WHERE THE TOILET ROOMS 1573/1581 & |
| | 1663/1665 CONNECT TO THE WATER RISER OR ANY OTHER |
| | LOCATION ON THE RISER DIAGRAM. CHECK VALVES ARE NOT |
| | APPROVED FOR BACKFLOW PREVENTION. TABLE 608.1. ******NO |
| | RESPONSE, BUT THE CHECK VALVES WERE CHANGED TO VACUUM |
| | BREAKERS. THIS IS NOT THE CORRECT APPLICATION FOR |
| | VACUUM BREAKERS AND ARE NOT APPROVED. PLEASE DELETE |
| | FROM THE FLOOR PLAN AND THE RISER DIAGRAM. |
| | |
| | 3B. SHT P0.1 DETAIL FOR THE PLATFORM MOUNTED WATER |
| | HEATERS. THE 80 GALLON EWH-2 WILL HAVE A TOTAL WEIGHT |
| | APPROX. 850 LBS. PLEASE SUBMIT INFORMATION ON THE |
| | SUPPORT FOR THE PLATFORM ATTACHMENT TO THE WALL. WILL |
| | THE STUDS BEHIND THE WALL BE STRUCTURAL STUDS OR |
| | DRYWALL STUDS. PLEASE INDICATE THE GUAGE OF THE STUDS |
| | AND THE SIZE OF THE BLOCKING THAT THE PLATFORM ANGLE |
| | BRACKETS WILL ATTACH TO. THIS INFORMATION SHOULD BE |
| | SUBMITTED BY THE STRUCTURAL ENGINEER. SECTION 106.1.2. |
| | ******NO RESPONSE, AND THE SECTION OF THE COMMENT ABOUT |
| | THE STUDS HAS NOT BEEN ADDRESSED. |
| | |
| | *****NEW COMMENTS 3RD REVIEW***** |
| | |
| | 1C. SHT 1-16.C JANITOR MOP SINK IS IN FRONT OF THE DOOR |
| | TO EXIT JANITOR ROOM 1662. PLEASE CLARIFY. SECTION |
| | 106.1.1. |
| | |
| | 2C. SHT 1-E.5 DETAILS 5, 4, 3 & 2 TOILET ROOMS TO BE |
| | ACCESSIBLE. PLEASE DELETE THE NOTE REFERING TO |
| | ADAPTABILITY. SECTION 11-4.1.3(11). PLEASE SUBMIT A |
| | DETAIL SHOWING COMPLIANCE WITH SECTIONS 11-4.16, |
| | 11-4.19 & 11-4.22 WITH ALL SUBSECTIONS. |
| | |
| | 3C. SHT 1-PA.2 DETAIL 5 NOTE "ADA SINK SECTION FOR ALL |
| | PANTRIES" SHALL INCLUDE THE COFFEE ROOMS AND THE |
| | EMPLOYEE LOUNGE OR SEPARATE DETAILS WILL BE REQUIRED TO |
| | SHOW COMPLIANCE WITH SECTION 11-4.24. PLEASE INDICATE |
| | IN NOTE. |
| | |
| | 4C. SHT 1-PA.2 DETAILS 1 & 2 SHOWS THE CLEAR FLOOR |
| | SPACE FOR THE SINK AT 24" WIDE. 30" WIDTH CLEAR FLOOR |
| | SPACE REQUIRED. SECTION 11-4.24.5. |
| | |
| | 5C. SHT P0.1 HORIZONTAL DRAINAGE PIPE CHART DOES NOT |
| | SHOW THE SLOPE. PLEASE INDICATE THE SLOPE PER TABLE |
| | 704.1. |
| | |
| | 6C. SHTS P2.2 & P3.2 ROOM 1628 DOES NOT SHOW THE BAR |
| | SINK, BUT IS SHOWN ON THE SANITARY AND WATER ISOMETRIC |
| | RISER DIAGRAMS. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 7C. SHT P61 CHECK VALVES HAVE BEEN CHANGED TO VACUUM |
| | BREAKERS AT THE SUPPLY TO THE TENANT SPACE. VACUUM |
| | BREAKERS ARE NOT DESIGNED FOR THIS APPLICATION. PLEASE |
| | DELETE. THE ONLY REQUIREMENT IS A FULL OPEN VALVE PER |
| | SECTION 606.1(5). |
| | |
| | 8C. SHT P61 THE WATER LINES DO NOT REFLECT THE FLOOR |
| | PLANS WHERE THEY HAVE BEEN EXTENDED PAST AND AROUND THE |
| | "IT" ROOM. PLEASE CORRELATE THE FLOOR PLAN PIPING AND |
| | THE RISER DIAGRAM PIPING. |
| | |
| | 9C. SEE ATTACHED SHEET CONCERNING THE DESIGN |
| | PROFESSIONAL AND FS 553.80(2)(B). |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL |
| | VOID SHEETS FROM ALL PLANS AND PLACE ONE SET |
| | OF THEM LOOSELY ON TOP OF THE COLLATED PLANS |
| | TO BE REVIEWED. THANK YOU FOR YOU |
| | ANTICIPATED COOPERATION. |
| | ******NO RESPONSE, NOT ADDRESSED |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |