Plan Review Notes
Plan Review Notes For Permit 07030932
Permit Number 07030932
Review Stop P
Sequence Number 3
Notes
Date Text
2007-11-30 07:44:23DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
 ******FROM PREVIOUS REVIEWS:
  
 1. OK
  
 2. SHT 1-16.C PER TABLE 403.1 3 DRINKING FOUNTAINS ARE
 REQUIRED. PLEASE INDICATE THE LOCATION OF EACH DRINKING
 FOUNTAIN.
 ****RESPONSE NOTED, BUT ON THE 16TH FLOOR PLAN, ONE
 DRINKING FOUNTAIN HAS SANITARY, BUT NO WATER SUPPLY &
 ONE DRINKING FOUNTAIN SHOWS NO SANITARY OR WATER
 SUPPLY. WATER AND DRAINAGE ARE REQUIRED AT EACH
 FIXTURE. SECTIOND 301.3 & 301.4.
 ******NO RESPONSE, BUT THE DRINKING FOUNTAIN IN ROOM
 1633 STILL SHOWS NO WATER SUPPLY. SEE SHEET P3.2.
  
 3. SHT 1-16.C BATHROOM (1608) SHALL BE ACCESSIBLE OR
 ADAPTABLE PER SECTIONS 11-4.22 OR 11-4.1.3(11). PLEASE
 SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTIONS
 11-4.16, 11-4.19 & 11-4.21 WITH ALL SUBSECTIONS IF
 BATHROOM IS TO BE ACCESSIBLE. SUBMIT A DETAIL SHOWING
 ALL BACKING FOR GRAB BARS FOR THE W/C & SHOWER, SPACING
 FOR THE W/C, (MIN. 33" WITH THE W/C BEING 18" OFF THE
 WALL AND MIN. 15" OFF THE SHOWER), A TURNING AREA IN
 THE BATHROOM, THE VALVE LOCATION FOR THE SHOWER, AND A
 CURB DETAIL OF THE SHOWER, (MAX 1/2").
 ****NO RESPONSE, NOT ADDRESSED.
 ******NO RESPONSE, AND NO DETAIL HAS BEEN SUBMITTED
 SHOWING THE BACKING REQUIRED FOR THE GRAB BARS FOR THE
 W/C AND SHOWER.
  
 4. SHT 1-16.C THE SINKS IN ROOMS 1613, 1628, 1633, 1643
 & 1674 SHALL BE ACCESSIBLE. PLEASE SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS.
 ****NO RESPONSE, NOT ADDRESSED.
 ******NO RESPONSE, BUT THE CLEAR FLOOR SPACE SHALL BE
 SHOWN ON THE FLOOR PLAN FOR EACH SINK. THE FLOOR PLAN
 FOR THE 16TH FLOOR DOES NOT SHOW THE BAR SINKS
 INDICATED ON THE PLUMBING SHEETS. PLEASE CORRELATE THE
 INFORMATION ON THE ARCHITECTUAL SHEETS AND THE PLUMBING
 SHEETS. SHEET 1-PA-2 DETAILS 1&2 ONLY SHOW A 24"
 OPENING UNDER THE SINKS WHERE 30" CLEAR FLOOR SPACE IS
 REQUIRED. SECTIONS 106.1.1 & 11-4.24.5.
  
 5. OK NO WATER OR DRAIN INDICATED AT MEETING WITH
 REPRESENTATIVES OF THE DESIGN TEAM.
 6. OK
 7. OK
  
 8. SUBMIT DETAILS FOR THE MEN'S & WOMEN'S TOILET ROOMS
 SHOWING COMPLIANCE WITH SECTIONS 11-4.16, 11-4.17,
 11-4.18, 11-4.19 & 11-4.22 WITH ALL SUBSECTIONS. ****NO
 RESPONSE, NOT ADDRESSED.--THIS SHALL APPLY FOR THE
 NEW TOILET ROOMS ADDED TO EACH FLOOR ALSO. ******NO
 RESPONSE, BUT DETAILS FOR ROOMS 1672, 1673, 1584 & 1585
 WERE NOT SUBMITTED. THESE TOILET ROOMS SHALL BE
 ACCESSIBLE.
  
 9. SUBMIT A DETAIL FOR THE ACCESSIBLE DRINKING
 FOUNTAINS. SHOW COMPLIANCE WITH SECTION 11-4.15 WILL
 ALL SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
 ****NO RESPONSE, NOT ADDRESSED.
 ******NO RESPONSE. SHOW THE CLEAR FLOOR SPACE FOR ALL
 ACCESSIBLE DRINKING FOUNTAINS. MINIMUM 50% OF THE
 DRINKING FOUNTAINS SHALL BE ACCESSIBLE AND ONLY ONE IS
 INDICATED ACCESSIBLE ON EACH FLOOR.
  
 10. OK
 11. OK
  
 12. SHT 1-15.C THE SINK IN ROOM 1520SHALL BE
 ACCESSIBLE. PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE
 WITH SECTION 11-4.24 AND ALL SUBSECTIONS.
 ****NO RESPONSE, NOT ADDRESSED.
 ******NO RESPONSE, NOT ADDRESSED.
  
 13. OK (NEW ENGINEER)
 14. OK
 15. OK
 16. OK
 17. OK
 18. OK
 19. OK
 20. OK
 21. OK
 22. OK
 23. OK
 24. OK
 25. OK
 26. OK
 27. OK
 28. OK
  
 29. SHT P51 THERMAL EXPANSION CONTROL IS REQUIRED FOR
 THE WATER HEATERS ON THE 15TH & 16TH FLOORS. PLEASE
 INDICATE THE METHOD OF CONTROL. SECTION 607.3.2.
 ****RESPONSE NOTED, BUT CALCULATIONS SHALL BE PROVIDED
 SHOWING THE CORRECT SIZE REQUIRED FOR 130 GALLONS,
 (TOTAL OF BOTH WATER HEATERS). SEE ATTACHED SHEET FOR
 AN EXAMPLE OF CALCULATIONS. INDICATE MANUF. AND MODEL
 WHEN SUMBITTING CALCULATIONS.
 ******NO RESPONSE, NOT ADDRESSED.
  
 30. OK
 31. OK
  
 ***********NEW COMMENTS***********
  
 1B. OK
  
 2B. SHT P61 DELETE THE CHECK VALVES FROM THE WATER
 RISER DIAGRAMS WHERE THE TOILET ROOMS 1573/1581 &
 1663/1665 CONNECT TO THE WATER RISER OR ANY OTHER
 LOCATION ON THE RISER DIAGRAM. CHECK VALVES ARE NOT
 APPROVED FOR BACKFLOW PREVENTION. TABLE 608.1. ******NO
 RESPONSE, BUT THE CHECK VALVES WERE CHANGED TO VACUUM
 BREAKERS. THIS IS NOT THE CORRECT APPLICATION FOR
 VACUUM BREAKERS AND ARE NOT APPROVED. PLEASE DELETE
 FROM THE FLOOR PLAN AND THE RISER DIAGRAM.
  
 3B. SHT P0.1 DETAIL FOR THE PLATFORM MOUNTED WATER
 HEATERS. THE 80 GALLON EWH-2 WILL HAVE A TOTAL WEIGHT
 APPROX. 850 LBS. PLEASE SUBMIT INFORMATION ON THE
 SUPPORT FOR THE PLATFORM ATTACHMENT TO THE WALL. WILL
 THE STUDS BEHIND THE WALL BE STRUCTURAL STUDS OR
 DRYWALL STUDS. PLEASE INDICATE THE GUAGE OF THE STUDS
 AND THE SIZE OF THE BLOCKING THAT THE PLATFORM ANGLE
 BRACKETS WILL ATTACH TO. THIS INFORMATION SHOULD BE
 SUBMITTED BY THE STRUCTURAL ENGINEER. SECTION 106.1.2.
 ******NO RESPONSE, AND THE SECTION OF THE COMMENT ABOUT
 THE STUDS HAS NOT BEEN ADDRESSED.
  
 *****NEW COMMENTS 3RD REVIEW*****
  
 1C. SHT 1-16.C JANITOR MOP SINK IS IN FRONT OF THE DOOR
 TO EXIT JANITOR ROOM 1662. PLEASE CLARIFY. SECTION
 106.1.1.
  
 2C. SHT 1-E.5 DETAILS 5, 4, 3 & 2 TOILET ROOMS TO BE
 ACCESSIBLE. PLEASE DELETE THE NOTE REFERING TO
 ADAPTABILITY. SECTION 11-4.1.3(11). PLEASE SUBMIT A
 DETAIL SHOWING COMPLIANCE WITH SECTIONS 11-4.16,
 11-4.19 & 11-4.22 WITH ALL SUBSECTIONS.
  
 3C. SHT 1-PA.2 DETAIL 5 NOTE "ADA SINK SECTION FOR ALL
 PANTRIES" SHALL INCLUDE THE COFFEE ROOMS AND THE
 EMPLOYEE LOUNGE OR SEPARATE DETAILS WILL BE REQUIRED TO
 SHOW COMPLIANCE WITH SECTION 11-4.24. PLEASE INDICATE
 IN NOTE.
  
 4C. SHT 1-PA.2 DETAILS 1 & 2 SHOWS THE CLEAR FLOOR
 SPACE FOR THE SINK AT 24" WIDE. 30" WIDTH CLEAR FLOOR
 SPACE REQUIRED. SECTION 11-4.24.5.
  
 5C. SHT P0.1 HORIZONTAL DRAINAGE PIPE CHART DOES NOT
 SHOW THE SLOPE. PLEASE INDICATE THE SLOPE PER TABLE
 704.1.
  
 6C. SHTS P2.2 & P3.2 ROOM 1628 DOES NOT SHOW THE BAR
 SINK, BUT IS SHOWN ON THE SANITARY AND WATER ISOMETRIC
 RISER DIAGRAMS. PLEASE CLARIFY. SECTION 106.1.1.
  
 7C. SHT P61 CHECK VALVES HAVE BEEN CHANGED TO VACUUM
 BREAKERS AT THE SUPPLY TO THE TENANT SPACE. VACUUM
 BREAKERS ARE NOT DESIGNED FOR THIS APPLICATION. PLEASE
 DELETE. THE ONLY REQUIREMENT IS A FULL OPEN VALVE PER
 SECTION 606.1(5).
  
 8C. SHT P61 THE WATER LINES DO NOT REFLECT THE FLOOR
 PLANS WHERE THEY HAVE BEEN EXTENDED PAST AND AROUND THE
 "IT" ROOM. PLEASE CORRELATE THE FLOOR PLAN PIPING AND
 THE RISER DIAGRAM PIPING.
  
 9C. SEE ATTACHED SHEET CONCERNING THE DESIGN
 PROFESSIONAL AND FS 553.80(2)(B).
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL
 VOID SHEETS FROM ALL PLANS AND PLACE ONE SET
 OF THEM LOOSELY ON TOP OF THE COLLATED PLANS
 TO BE REVIEWED. THANK YOU FOR YOU
 ANTICIPATED COOPERATION.
 ******NO RESPONSE, NOT ADDRESSED
  
 REVIEW BY KEN STEVENS