| 2007-12-11 12:58:22 | 2007-12-11 12:58:22 |
| | |
| | **** DENIED 3RD REVIEW **** |
| | |
| | ** PLEASE SEE SOME ITEMS FROM THE PREVIOUS TWO REVIEWS |
| | ARE STILL IN OF ADDRESSING. |
| | ** PLEASE SEE THERE NOW NEW COMMENTS WHICH WERE NOT ON |
| | PREVIOUS REVIEW AS THERE ARE ITEMS ON PLANS AND RISER |
| | WHICH WERE NEW AND REVISED. |
| | |
| | |
| | 1) NOTE:PLEASE SEE COMPLIANCE WITH THE FBC CHAPTER 13 |
| | HAS NOT YET BEEN ACHIEVED. |
| | PLEASE SEE THERE ARE SEVERAL ITEMS FROM THE PREVIOUS |
| | REVIEW NOTES WHICH ARE STILL IN NEED OF ADDRESSING. |
| | PLEASE SEE THE PLANS ARE STILL INDICATING A SUBSTANTIAL |
| | AMOUNT OF LIGHTING FIXTURES AND WATTAGES ON THE NEW |
| | LIGHTING CALCULATIONS WHICH DO NOT CORRELATE WITH PLANS |
| | OR WITH THE MINIMUM REQUIREMENTS AS SET-FORTH IN THE |
| | FLORIDA BUILDING CODE. |
| | PLEASE SEE SOME EXAMPLES WILL BE GIVEN HOWEVER THIS IS |
| | NO WAY ALL LOCATIONS IN WHICH INCONSISTENCIES EXISTS. |
| | PLEASE SEE 13-415.2.ABC.1.2 WHICH WAS SPECIFICALLY |
| | NOTED ON PREVIOUS REVIEWS FOR TRACK LIGHTING. PLEASE |
| | SEE THE MINIMUM VA WHICH MUST BE USED FOR LINE VOLTAGE |
| | LIGHTING SHALL BE BASED ON THE WATTAGE OF EACH FIXTURE |
| | OR 30VA PER FT OF LINEAR FT OF TRACK SHOWN ON PLANS, |
| | WHICH EVER IS HIGHER. |
| | PLEASE SEE THE PLANS ON ID DRAWINGS AS THE LIGHTING VA |
| | SHOWN ON TABLES DOES NOT COORDINATE EVEN FOR THE NUMBER |
| | OF FIXTURES BASED ON THE WATTAGE ON THE FIXTURE |
| | LEGEND. |
| | |
| | PLEASE SEE 1544, 1543, 1546 FOR EXAMPLE: THIS SHOWS A |
| | TOTAL OF 14 FIXTURES, EACH AT 50WATTS EACH, WHICH IS |
| | 700VA, YET THE TABLE SHOWS 600VA. PLEASE KNOW AS NOTED |
| | ABOVE THE VA MUST BE BASED ON THE FIXTURES OR THE |
| | LINEAR FT OF TRACK AT 30VA PER FT WHICH EVER IS HIGHER. |
| | BASED ON THE LINEAR FEET OF TRACK AS SHOWN ON PLANS THE |
| | VA PER FT FOR MINIMUM REQUIREMENTS IS MUCH HIGHER THAN |
| | THE NUMBER OF FIXTURES AND WATTAGES OF EACH. |
| | |
| | PLEASE SEE FOR EXAMPLE: THE AREA AS NOTED AS 1636, SAME |
| | AS ABOVE FOR TRACK AND OTHER AREAS ON PLANS HOWEVER NOT |
| | ALL AREAS ARE BEING NOTED. |
| | |
| | PLEASE SEE FOR EXAMPLE: PLEASE KNOW ANY LOW VOLTAGE |
| | SYSTEMS, SUCH AS THE *Q* FIXTURES ARE REQUIRED TO USE |
| | THE VA OUTPUT OF ANY TRANSFORMERS AS THESE INDICATE A |
| | COLD CATHODE FIXTURES DESIGNATION. THE CALCULATION |
| | SHEETS NOTE THESE AS 28VA PER FIXTURE? PLEASE SEE THE |
| | FIXTURE LEGEND FOR THE *Q* FIXTURE IS BLANK AT THIS |
| | TIME THEREFORE VERIFICATION OF COMPLIANCE MAY NOT BE |
| | DONE. |
| | |
| | PLEASE SEE FOR EXAMPLE: THE ROOM DESIGNATIONS ON |
| | CALCULATION SHEETS FOR 16TH FLOOR ARE NOT COMPLETE, |
| | SOME ROOM ARE NOT LABELED ON CALCULATIONS. (CAN NOT |
| | VERIFY AT THIS TIME). |
| | |
| | PLEASE SEE FOR EXAMPLE: PLEASE SEE ROOM/AREA 1578 AS NO |
| | LIGHTING FIXTURES ARE SHOWN ON PLANS ON ID PLANS OR ON |
| | E-SHEETS. THIS WAS GONE OVER IN MEETING WITH THE |
| | ARCHITECT AND ELECTRICAL DESIGNER AND FIXTURES WERE |
| | GOING TO BE ADDED? |
| | |
| | PLEASE SEE FOR EXAMPLE: AREA 1564 AS 27 TYPE *X* |
| | FIXTURES ARE IN CALCULATIONS AND 29 OF THESE SAME TYPES |
| | FOR THIS SAME AREA ARE ON PLANS THEREFORE SHOWING A |
| | SHORTAGE IN TOTAL WATTAGES. |
| | |
| | PLEASE SEE FOR EXAMPLE: AREA 1660 AS TYPE *F* FIXTURES |
| | ARE SHOWING 16 ON ID SHEETS AND YET THE ELECTRICAL |
| | PLANS SEEM TO INDICATE 17-J-BOXES FOR FIXTURES? |
| | |
| | PLEASE SEE FOR EXAMPLE: PLEASE SEE AREA 1575 AS THE |
| | PLANS AND LAYOUTS ON ID PLANS AND ELECTRICAL PLANS ARE |
| | NOT THE SAME. |
| | PLEASE COORDINATE. |
| | |
| | PLEASE SEE FOR EXAMPLE: AREA 1564 AS THE ID PLANS |
| | INDICATE A TYPE *X* FIXTURE ON CEILING IN BETWEEN SOME |
| | OFFICE DOORS, YET THE ELECTRICAL PLANS DO NOT SHOW |
| | THESE. THIS WILL ALSO BE NOTED IN THE NEXT COMMENT FOR |
| | CONTROLS OF LIGHTING. |
| | |
| | PLEASE PROVIDE A TOTAL OF DESIGN WATTAGE AND |
| | ALLOWANCES. THE 1.72 AND 1.55 AS SHOWN ON ID PLANS |
| | EXCEED THAT OF ALLOWANCES. PLEASE SHOW HOW THESE MAY BE |
| | OVER AND HOW THIS WAS FIGURED. PLEASE ALSO KEEP IN MIND |
| | AS THE TOTALS FOR FIXTURES AND FIXTURES SUCH AS TRACK |
| | LIGHTING WILL ADJUST SIGNIFICANTLY THIS WILL AFFECT THE |
| | OVER ALL CALCULATIONS. |
| | THE MAXIMUM DESIGN ALLOWANCES FOR BASE BUILDING MUST BE |
| | MET. IF THE BASE BUILDING DESIGN TEAM/ENGINEERING FIRM |
| | OF RECORD HAS DESIGNED A MAXIMUM OF 1.1 PER SQ FT FOR |
| | OFFICE AREA THEN THIS MUST BE FOLLOWED. ALLOWANCES ON |
| | ORIGINAL METHOD *B* ASSUMPTIONS MUST MEET FBC CHAPTER |
| | 13 AND -13-415.1.B ETC |
| | THE LIGHTING POWER DENSITIES CALCULATIONS AND DESIGNS |
| | IS THE RESPONSIBILITY OF THE ELECTRICAL DESIGNER OF |
| | RECORD PER FAC 61G15-33.004. PLEASE ADJUST PLANS AND |
| | CALCULATIONS ACCORDINGLY. FS 471.003 |
| | |
| | ** PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2. PLEASE |
| | SEE SOME OF THE ITEMS AS NOTED ABOVE WERE LOCATED ON |
| | PLANS, HOWEVER NOT ALL ARE NOTED. THERE ARE OTHER |
| | AREAS. |
| | |
| | |
| | |
| | 2) NOTE: PLEASE SEE CONTROLS FOR LIGHTING STILL NEED |
| | SOME ADJUSTMENTS TO MEET 13-415.1.ABC.1.1, .1.2 AND |
| | .1.3. |
| | |
| | PLEASE SEE FOR EXAMPLE: AREA 1564, 1540, 1558 ETC FOR |
| | TYPE *X* FIXTURES WHICH ARE SHOWN ON ID PLANS SHEET |
| | I-15.R, YET ELECTRICAL PLANS FOR LIGHTING EITHER E2.1 |
| | OR POWER E3.1 INDICATES ANY OF THESE FIXTURES. |
| | |
| | PLEASE SEE FOR EXAMPLE: PLEASE SEE AREAS 1638 AND 1634 |
| | AS TYPE *Q* FIXTURES CONTAIN A NOTE #8 FOR A J-BOX TO |
| | BE PROVIDED FOR ELECTRICAL CONNECTION YET NO CONTROLS |
| | FOR LIGHTING COULD BE FOUND? NO ADDITIONAL NOTES FOR |
| | LIGHTING CONTROL PANEL, OCCUPANCY SENSORS, OVER-RIDE |
| | DEVICES ETC WERE FOUND ON PLANS. |
| | |
| | PLEASE SEE FOR EXAMPLE: AREA 1564 AS HALLWAY LIGHTING |
| | FOR *J* FIXTURES DO NOT CONTAIN THE NOTE #2 FOR CONTROL |
| | AS NOTED ON OTHER AREAS FOR THIS SAME TYPE OF |
| | FIXTURES. |
| | |
| | ** PLEASE SEE THAT SOME OF THE ABOVE ARE NOTED FOR |
| | EXAMPLE, HOWEVER NOT ALL ARE NOTED. |
| | |
| | 3) NOTE: PLEASE SEE THE POWER PLANS ARE MISSING |
| | ELECTRICAL PANELS AND DISCONNECTS NOT SHOWN. PLEASE SEE |
| | FOR EXAMPLE: SHEET E3.1 WHICH SHOWS PANELS BEING NOTED, |
| | HOWEVER THESE ARE NOT SHOWN ON LAYOUT. PLEASE SEE FOR |
| | EXAMPLE: THE ELECTRICAL ROOM 1577 WHICH INDICATES THE |
| | TRANSFORMER BEING INSTALLED IN THIS ROOM YET DISCONNECT |
| | WHICH IS SHOWN ON RISER IS SHOWN ON PLANS? |
| | PLEASE SEE THIS IS THE SAME FOR MAIN ELECTRICAL ROOM ON |
| | THE 16TH FLOOR. |
| | |
| | 4) NOTE: PLEASE COORDINATE PLANS WITH DOORS AND ROOM |
| | LOCATIONS AS SHOWN ON PLANS. |
| | PLEASE SEE ELECTRICAL PLANS FOR PANELS ON FLOOR 16 AS |
| | ONE ELECTRICAL PANEL DOES NOT SEEM IT IS LOCATED IN |
| | ROOM OR ON WALL IT SEEMS TO BE PARTIALLY IN WALL? |
| | PLEASE SEE FOR EXAMPLE: THE AREA FOR ACCESS TO THE MAIN |
| | ELECTRICAL ROOM IN 1542 ON SHEET E3.1 SHOWS WHAT |
| | APPEARS TO BE COUNTER SPACES BEING INSTALLED IN FRONT |
| | OF DOOR. THIS MUST BE A MISPRINT OF SOME TYPE. I-15C |
| | DOES NOT SHOW THIS COUNTER SPACE BEING EXTENDED AROUND |
| | THE CORNER. |
| | 110.26 |
| | PLEASE SEE THE AREA 1575 WHERE THE CLOSET/DOOR/ACCESS |
| | IS NOT THE SAME ON ID PLANS AND ELECTRICAL. |
| | PLEASE COORDINATE PLANS AND ADJUST. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 5) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS |
| | FOR THE IT ROOM EQUIPMENT WHICH CORRELATE WITH THE |
| | PLANS AND RISER DIAGRAM. |
| | PLEASE SEE FOR EXAMPLE: THE SHEET LABELED DRAWING |
| | ISX-40K40R2G1XF-SD SHOWS A TRANSFORMER AND EQUIPMENT |
| | WHICH IS NOT SHOWN ON OR A PART OF THE ELECTRICAL |
| | RISER. |
| | PLEASE COORDINATE ALL EQUIPMENT. |
| | 110.3, 90.7 |
| | FBC 106.1.2 |
| | |
| | 6) NOTE: PLEASE SEE PREVIOUS NOTE #11 WITH RESPECT TO |
| | TAPPED CONDUCTORS ON THE SECONDARY SIDE OF THE |
| | TRANSFORMER(S). |
| | PLEASE SEE 240.21, 240.4, 310.16 AS THE 500MCM AS SHOWN |
| | ARE ONLY RATED FOR 380AMPS PER 110.14 AND 310.16. |
| | PLEASE KNOW THE CONDUCTORS MUST TERMINATE IN OVER |
| | CURRENT PROTECTION WHICH LIMITS THE LOAD ON THE |
| | CONDUCTORS.THIS MAY NOT GO TO THE NEXT STANDARD SIZE |
| | AS OVER CURRENT PROTECTION DOES NOT CORRELATE WITH |
| | 240.6 |
| | PLEASE ADJUST. |
| | |
| | 7) NOTE: PLEASE SEE PREVIOUS NOTE #13 AND PLEASE |
| | CLARIFY THE LOADING OF THE CIRCUITS AS NOTED PER 645.A |
| | ** PREVIOUS NOTE ** |
| | THE PLANS INDICATE A PANEL ER, THE PANEL SCHEDULE |
| | SHEETS INDICATE A PANEL ER HOWEVER THIS IS NOT INCLUDED |
| | ON THE RISER DIAGRAM. |
| | PLEASE VERIFY 645.5A AND INDICATE WHERE THE 125% HAS |
| | BEEN FIGURED. |
| | |
| | 8) NOTE: PLEASE SEE PREVIOUS NOTE #16 AS THE NOTE |
| | MENTIONED IT WOULD REMAIN AS NEW ELECTRICAL EQUIPMENT |
| | FOR SERVICE WOULD BE ADDED TO PLANS AND RISER AND TO |
| | PLEASE BE SURE THE AIC RATINGS WERE INCLUDED FOR ALL. |
| | PLEASE SEE NOT INFORMATION FOR NEW MAINS ON THE |
| | SECONDARY SIDE OF THE TRANSFORMER WAS INCLUDED. THIS IS |
| | ALSO FOR AIC RATINGS. |
| | PLEASE ADJUST AND COMPLETE. |
| | 110.9, |
| | FBC 106.1.2 |
| | ** PREVIOUS REVIEW NOTE ** |
| | 16) NOTE: PLEASE INDICATE THE AIC RATINGS FOR ALL NEW |
| | ELECTRICAL SERVICE EQUIPMENT. THIS NOTE IS TO REMAIN AS |
| | THERE ARE ITEMS WHICH WILL BE CHANGING, NOT INCLUDED AT |
| | THIS TIME WHICH MAY ALSO REQUIRE THE RATINGS TO BE |
| | INDICATED. |
| | 110.9, FBC 106.1.2 |
| | |
| | 9) NOTE: PLEASE BE SURE ALL NEW REVISED SHEETS CONTAIN |
| | STAMPS FROM THE BASE BUILDING DESIGN TEAM WHOM IS STILL |
| | RESPONSIBLE FOR THIS BUILDING UNTIL SUCH TIME THE |
| | CERTIFICATE OF OCCUPANCY (CO) IS ISSUED. |
| | 10) NOTE: PLEASE KNOW ONE COPY OF ID PLANS FOR LIGHTING |
| | AND ELECTRICAL HAS BEEN RETAINED BY THIS OFFICE. PLEASE |
| | SEE FS 553.80(2)(B). |
| | THE FEE WAS ASSESSED DUE TO PLUMBING REVIEW REPEAT |
| | COMMENTS ALREADY ON PROJECT. THE FEE IS NOT ASSESSED |
| | PER TRADE. |
| | THE FEE OF $38,175.51 IS DUE BEFORE RE-SUBMITTAL OF |
| | PLANS. THIS IS ONLY BEING NOTED FOR INFORMATION. ** |
| | PLEASE BE SURE TO COORDINATE ALL PLANS WITH RESPECT TO |
| | LIGHTING CALCULATIONS |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-12-10 17:12:01 | 2007-12-10 17:12:01 |
| | REVIEW COMMENCED AND NOTES TO FOLLOW. |
| 2007-12-03 13:01:30 | 12/3/07 13:01:30 |
| | PROJECT ON HOLD, RESUBMITTAL FEES WERE NOT PAID. CALLED |
| | AND SPOKE TO TERESAFROM BALFOUR BEATTY. ALSO LEFT |
| | MESSAGE ON JAMES TURNER'S VOICEMAIL. DV PALMER |