Plan Review Notes
Plan Review Notes For Permit 07030932
Permit Number 07030932
Review Stop E
Sequence Number 3
Notes
Date Text
2007-12-11 12:58:222007-12-11 12:58:22
  
 **** DENIED 3RD REVIEW ****
  
 ** PLEASE SEE SOME ITEMS FROM THE PREVIOUS TWO REVIEWS
 ARE STILL IN OF ADDRESSING.
 ** PLEASE SEE THERE NOW NEW COMMENTS WHICH WERE NOT ON
 PREVIOUS REVIEW AS THERE ARE ITEMS ON PLANS AND RISER
 WHICH WERE NEW AND REVISED.
  
  
 1) NOTE:PLEASE SEE COMPLIANCE WITH THE FBC CHAPTER 13
 HAS NOT YET BEEN ACHIEVED.
 PLEASE SEE THERE ARE SEVERAL ITEMS FROM THE PREVIOUS
 REVIEW NOTES WHICH ARE STILL IN NEED OF ADDRESSING.
 PLEASE SEE THE PLANS ARE STILL INDICATING A SUBSTANTIAL
 AMOUNT OF LIGHTING FIXTURES AND WATTAGES ON THE NEW
 LIGHTING CALCULATIONS WHICH DO NOT CORRELATE WITH PLANS
 OR WITH THE MINIMUM REQUIREMENTS AS SET-FORTH IN THE
 FLORIDA BUILDING CODE.
 PLEASE SEE SOME EXAMPLES WILL BE GIVEN HOWEVER THIS IS
 NO WAY ALL LOCATIONS IN WHICH INCONSISTENCIES EXISTS.
 PLEASE SEE 13-415.2.ABC.1.2 WHICH WAS SPECIFICALLY
 NOTED ON PREVIOUS REVIEWS FOR TRACK LIGHTING. PLEASE
 SEE THE MINIMUM VA WHICH MUST BE USED FOR LINE VOLTAGE
 LIGHTING SHALL BE BASED ON THE WATTAGE OF EACH FIXTURE
 OR 30VA PER FT OF LINEAR FT OF TRACK SHOWN ON PLANS,
 WHICH EVER IS HIGHER.
 PLEASE SEE THE PLANS ON ID DRAWINGS AS THE LIGHTING VA
 SHOWN ON TABLES DOES NOT COORDINATE EVEN FOR THE NUMBER
 OF FIXTURES BASED ON THE WATTAGE ON THE FIXTURE
 LEGEND.
  
 PLEASE SEE 1544, 1543, 1546 FOR EXAMPLE: THIS SHOWS A
 TOTAL OF 14 FIXTURES, EACH AT 50WATTS EACH, WHICH IS
 700VA, YET THE TABLE SHOWS 600VA. PLEASE KNOW AS NOTED
 ABOVE THE VA MUST BE BASED ON THE FIXTURES OR THE
 LINEAR FT OF TRACK AT 30VA PER FT WHICH EVER IS HIGHER.
 BASED ON THE LINEAR FEET OF TRACK AS SHOWN ON PLANS THE
 VA PER FT FOR MINIMUM REQUIREMENTS IS MUCH HIGHER THAN
 THE NUMBER OF FIXTURES AND WATTAGES OF EACH.
  
 PLEASE SEE FOR EXAMPLE: THE AREA AS NOTED AS 1636, SAME
 AS ABOVE FOR TRACK AND OTHER AREAS ON PLANS HOWEVER NOT
 ALL AREAS ARE BEING NOTED.
  
 PLEASE SEE FOR EXAMPLE: PLEASE KNOW ANY LOW VOLTAGE
 SYSTEMS, SUCH AS THE *Q* FIXTURES ARE REQUIRED TO USE
 THE VA OUTPUT OF ANY TRANSFORMERS AS THESE INDICATE A
 COLD CATHODE FIXTURES DESIGNATION. THE CALCULATION
 SHEETS NOTE THESE AS 28VA PER FIXTURE? PLEASE SEE THE
 FIXTURE LEGEND FOR THE *Q* FIXTURE IS BLANK AT THIS
 TIME THEREFORE VERIFICATION OF COMPLIANCE MAY NOT BE
 DONE.
  
 PLEASE SEE FOR EXAMPLE: THE ROOM DESIGNATIONS ON
 CALCULATION SHEETS FOR 16TH FLOOR ARE NOT COMPLETE,
 SOME ROOM ARE NOT LABELED ON CALCULATIONS. (CAN NOT
 VERIFY AT THIS TIME).
  
 PLEASE SEE FOR EXAMPLE: PLEASE SEE ROOM/AREA 1578 AS NO
 LIGHTING FIXTURES ARE SHOWN ON PLANS ON ID PLANS OR ON
 E-SHEETS. THIS WAS GONE OVER IN MEETING WITH THE
 ARCHITECT AND ELECTRICAL DESIGNER AND FIXTURES WERE
 GOING TO BE ADDED?
  
 PLEASE SEE FOR EXAMPLE: AREA 1564 AS 27 TYPE *X*
 FIXTURES ARE IN CALCULATIONS AND 29 OF THESE SAME TYPES
 FOR THIS SAME AREA ARE ON PLANS THEREFORE SHOWING A
 SHORTAGE IN TOTAL WATTAGES.
  
 PLEASE SEE FOR EXAMPLE: AREA 1660 AS TYPE *F* FIXTURES
 ARE SHOWING 16 ON ID SHEETS AND YET THE ELECTRICAL
 PLANS SEEM TO INDICATE 17-J-BOXES FOR FIXTURES?
  
 PLEASE SEE FOR EXAMPLE: PLEASE SEE AREA 1575 AS THE
 PLANS AND LAYOUTS ON ID PLANS AND ELECTRICAL PLANS ARE
 NOT THE SAME.
 PLEASE COORDINATE.
  
 PLEASE SEE FOR EXAMPLE: AREA 1564 AS THE ID PLANS
 INDICATE A TYPE *X* FIXTURE ON CEILING IN BETWEEN SOME
 OFFICE DOORS, YET THE ELECTRICAL PLANS DO NOT SHOW
 THESE. THIS WILL ALSO BE NOTED IN THE NEXT COMMENT FOR
 CONTROLS OF LIGHTING.
  
 PLEASE PROVIDE A TOTAL OF DESIGN WATTAGE AND
 ALLOWANCES. THE 1.72 AND 1.55 AS SHOWN ON ID PLANS
 EXCEED THAT OF ALLOWANCES. PLEASE SHOW HOW THESE MAY BE
 OVER AND HOW THIS WAS FIGURED. PLEASE ALSO KEEP IN MIND
 AS THE TOTALS FOR FIXTURES AND FIXTURES SUCH AS TRACK
 LIGHTING WILL ADJUST SIGNIFICANTLY THIS WILL AFFECT THE
 OVER ALL CALCULATIONS.
 THE MAXIMUM DESIGN ALLOWANCES FOR BASE BUILDING MUST BE
 MET. IF THE BASE BUILDING DESIGN TEAM/ENGINEERING FIRM
 OF RECORD HAS DESIGNED A MAXIMUM OF 1.1 PER SQ FT FOR
 OFFICE AREA THEN THIS MUST BE FOLLOWED. ALLOWANCES ON
 ORIGINAL METHOD *B* ASSUMPTIONS MUST MEET FBC CHAPTER
 13 AND -13-415.1.B ETC
 THE LIGHTING POWER DENSITIES CALCULATIONS AND DESIGNS
 IS THE RESPONSIBILITY OF THE ELECTRICAL DESIGNER OF
 RECORD PER FAC 61G15-33.004. PLEASE ADJUST PLANS AND
 CALCULATIONS ACCORDINGLY. FS 471.003
  
 ** PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2. PLEASE
 SEE SOME OF THE ITEMS AS NOTED ABOVE WERE LOCATED ON
 PLANS, HOWEVER NOT ALL ARE NOTED. THERE ARE OTHER
 AREAS.
  
  
  
 2) NOTE: PLEASE SEE CONTROLS FOR LIGHTING STILL NEED
 SOME ADJUSTMENTS TO MEET 13-415.1.ABC.1.1, .1.2 AND
 .1.3.
  
 PLEASE SEE FOR EXAMPLE: AREA 1564, 1540, 1558 ETC FOR
 TYPE *X* FIXTURES WHICH ARE SHOWN ON ID PLANS SHEET
 I-15.R, YET ELECTRICAL PLANS FOR LIGHTING EITHER E2.1
 OR POWER E3.1 INDICATES ANY OF THESE FIXTURES.
  
 PLEASE SEE FOR EXAMPLE: PLEASE SEE AREAS 1638 AND 1634
 AS TYPE *Q* FIXTURES CONTAIN A NOTE #8 FOR A J-BOX TO
 BE PROVIDED FOR ELECTRICAL CONNECTION YET NO CONTROLS
 FOR LIGHTING COULD BE FOUND? NO ADDITIONAL NOTES FOR
 LIGHTING CONTROL PANEL, OCCUPANCY SENSORS, OVER-RIDE
 DEVICES ETC WERE FOUND ON PLANS.
  
 PLEASE SEE FOR EXAMPLE: AREA 1564 AS HALLWAY LIGHTING
 FOR *J* FIXTURES DO NOT CONTAIN THE NOTE #2 FOR CONTROL
 AS NOTED ON OTHER AREAS FOR THIS SAME TYPE OF
 FIXTURES.
  
 ** PLEASE SEE THAT SOME OF THE ABOVE ARE NOTED FOR
 EXAMPLE, HOWEVER NOT ALL ARE NOTED.
  
 3) NOTE: PLEASE SEE THE POWER PLANS ARE MISSING
 ELECTRICAL PANELS AND DISCONNECTS NOT SHOWN. PLEASE SEE
 FOR EXAMPLE: SHEET E3.1 WHICH SHOWS PANELS BEING NOTED,
 HOWEVER THESE ARE NOT SHOWN ON LAYOUT. PLEASE SEE FOR
 EXAMPLE: THE ELECTRICAL ROOM 1577 WHICH INDICATES THE
 TRANSFORMER BEING INSTALLED IN THIS ROOM YET DISCONNECT
 WHICH IS SHOWN ON RISER IS SHOWN ON PLANS?
 PLEASE SEE THIS IS THE SAME FOR MAIN ELECTRICAL ROOM ON
 THE 16TH FLOOR.
  
 4) NOTE: PLEASE COORDINATE PLANS WITH DOORS AND ROOM
 LOCATIONS AS SHOWN ON PLANS.
 PLEASE SEE ELECTRICAL PLANS FOR PANELS ON FLOOR 16 AS
 ONE ELECTRICAL PANEL DOES NOT SEEM IT IS LOCATED IN
 ROOM OR ON WALL IT SEEMS TO BE PARTIALLY IN WALL?
 PLEASE SEE FOR EXAMPLE: THE AREA FOR ACCESS TO THE MAIN
 ELECTRICAL ROOM IN 1542 ON SHEET E3.1 SHOWS WHAT
 APPEARS TO BE COUNTER SPACES BEING INSTALLED IN FRONT
 OF DOOR. THIS MUST BE A MISPRINT OF SOME TYPE. I-15C
 DOES NOT SHOW THIS COUNTER SPACE BEING EXTENDED AROUND
 THE CORNER.
 110.26
 PLEASE SEE THE AREA 1575 WHERE THE CLOSET/DOOR/ACCESS
 IS NOT THE SAME ON ID PLANS AND ELECTRICAL.
 PLEASE COORDINATE PLANS AND ADJUST.
 FBC 106.1.2, 106.3.5.1.2
  
 5) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS
 FOR THE IT ROOM EQUIPMENT WHICH CORRELATE WITH THE
 PLANS AND RISER DIAGRAM.
 PLEASE SEE FOR EXAMPLE: THE SHEET LABELED DRAWING
 ISX-40K40R2G1XF-SD SHOWS A TRANSFORMER AND EQUIPMENT
 WHICH IS NOT SHOWN ON OR A PART OF THE ELECTRICAL
 RISER.
 PLEASE COORDINATE ALL EQUIPMENT.
 110.3, 90.7
 FBC 106.1.2
  
 6) NOTE: PLEASE SEE PREVIOUS NOTE #11 WITH RESPECT TO
 TAPPED CONDUCTORS ON THE SECONDARY SIDE OF THE
 TRANSFORMER(S).
 PLEASE SEE 240.21, 240.4, 310.16 AS THE 500MCM AS SHOWN
 ARE ONLY RATED FOR 380AMPS PER 110.14 AND 310.16.
 PLEASE KNOW THE CONDUCTORS MUST TERMINATE IN OVER
 CURRENT PROTECTION WHICH LIMITS THE LOAD ON THE
 CONDUCTORS.THIS MAY NOT GO TO THE NEXT STANDARD SIZE
 AS OVER CURRENT PROTECTION DOES NOT CORRELATE WITH
 240.6
 PLEASE ADJUST.
  
 7) NOTE: PLEASE SEE PREVIOUS NOTE #13 AND PLEASE
 CLARIFY THE LOADING OF THE CIRCUITS AS NOTED PER 645.A
 ** PREVIOUS NOTE **
 THE PLANS INDICATE A PANEL ER, THE PANEL SCHEDULE
 SHEETS INDICATE A PANEL ER HOWEVER THIS IS NOT INCLUDED
 ON THE RISER DIAGRAM.
 PLEASE VERIFY 645.5A AND INDICATE WHERE THE 125% HAS
 BEEN FIGURED.
  
 8) NOTE: PLEASE SEE PREVIOUS NOTE #16 AS THE NOTE
 MENTIONED IT WOULD REMAIN AS NEW ELECTRICAL EQUIPMENT
 FOR SERVICE WOULD BE ADDED TO PLANS AND RISER AND TO
 PLEASE BE SURE THE AIC RATINGS WERE INCLUDED FOR ALL.
 PLEASE SEE NOT INFORMATION FOR NEW MAINS ON THE
 SECONDARY SIDE OF THE TRANSFORMER WAS INCLUDED. THIS IS
 ALSO FOR AIC RATINGS.
 PLEASE ADJUST AND COMPLETE.
 110.9,
 FBC 106.1.2
 ** PREVIOUS REVIEW NOTE **
 16) NOTE: PLEASE INDICATE THE AIC RATINGS FOR ALL NEW
 ELECTRICAL SERVICE EQUIPMENT. THIS NOTE IS TO REMAIN AS
 THERE ARE ITEMS WHICH WILL BE CHANGING, NOT INCLUDED AT
 THIS TIME WHICH MAY ALSO REQUIRE THE RATINGS TO BE
 INDICATED.
 110.9, FBC 106.1.2
  
 9) NOTE: PLEASE BE SURE ALL NEW REVISED SHEETS CONTAIN
 STAMPS FROM THE BASE BUILDING DESIGN TEAM WHOM IS STILL
 RESPONSIBLE FOR THIS BUILDING UNTIL SUCH TIME THE
 CERTIFICATE OF OCCUPANCY (CO) IS ISSUED.
 10) NOTE: PLEASE KNOW ONE COPY OF ID PLANS FOR LIGHTING
 AND ELECTRICAL HAS BEEN RETAINED BY THIS OFFICE. PLEASE
 SEE FS 553.80(2)(B).
 THE FEE WAS ASSESSED DUE TO PLUMBING REVIEW REPEAT
 COMMENTS ALREADY ON PROJECT. THE FEE IS NOT ASSESSED
 PER TRADE.
 THE FEE OF $38,175.51 IS DUE BEFORE RE-SUBMITTAL OF
 PLANS. THIS IS ONLY BEING NOTED FOR INFORMATION. **
 PLEASE BE SURE TO COORDINATE ALL PLANS WITH RESPECT TO
 LIGHTING CALCULATIONS
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-12-10 17:12:012007-12-10 17:12:01
 REVIEW COMMENCED AND NOTES TO FOLLOW.
2007-12-03 13:01:3012/3/07 13:01:30
 PROJECT ON HOLD, RESUBMITTAL FEES WERE NOT PAID. CALLED
 AND SPOKE TO TERESAFROM BALFOUR BEATTY. ALSO LEFT
 MESSAGE ON JAMES TURNER'S VOICEMAIL. DV PALMER