| Date |
Text |
| 2007-09-12 17:59:50 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. ALL SHEETS. THE BUSINESS NUMBER FOR "YJ |
| | ARCHITECTURAL DESIGN" IS REQUIRED IN THE TITLE BLOCK. |
| | FAC 61G1-16.004(2) & FS 481.219, 481.2055. |
| | ****NO RESPONSE, NOT ADDRESSED. THE FLORIDA STATE DBPR |
| | FIRM LICENSE NUMBER IS REQUIRED. |
| | |
| | 2. SHT 1-16.C PER TABLE 403.1 3 DRINKING FOUNTAINS ARE |
| | REQUIRED. PLEASE INDICATE THE LOCATION OF EACH DRINKING |
| | FOUNTAIN. |
| | ****RESPONSE NOTED, BUT ON THE 16TH FLOOR PLAN, ONE |
| | DRINKING FOUNTAIN HAS SANITARY, BUT NO WATER SUPPLY & |
| | ONE DRINKING FOUNTAIN SHOWS NO SANITARY OR WATER |
| | SUPPLY. WATER AND DRAINAGE ARE REQUIRED AT EACH |
| | FIXTURE. SECTIOND 301.3 & 301.4. |
| | |
| | 3. SHT 1-16.C BATHROOM (1608) SHALL BE ACCESSIBLE OR |
| | ADAPTABLE PER SECTIONS 11-4.22 OR 11-4.1.3(11). PLEASE |
| | SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTIONS |
| | 11-4.16, 11-4.19 & 11-4.21 WITH ALL SUBSECTIONS IF |
| | BATHROOM IS TO BE ACCESSIBLE. SUBMIT A DETAIL SHOWING |
| | ALL BACKING FOR GRAB BARS FOR THE W/C & SHOWER, SPACING |
| | FOR THE W/C, (MIN. 33" WITH THE W/C BEING 18" OFF THE |
| | WALL AND MIN. 15" OFF THE SHOWER), A TURNING AREA IN |
| | THE BATHROOM, THE VALVE LOCATION FOR THE SHOWER, AND A |
| | CURB DETAIL OF THE SHOWER, (MAX 1/2"). |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 4. SHT 1-16.C THE SINKS IN ROOMS 1613, 1628, 1633, 1643 |
| | & 1656 SHALL BE ACCESSIBLE. PLEASE SUBMIT A DETAIL |
| | SHOWING COMPLIANCE WITH SECTION 11-4.24 AND ALL |
| | SUBSECTIONS. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 5. SHT 1-16.C MORE INFORMATION IS REQUIRED FOR THE |
| | PLANTERS. PLEASE INDICATE IF THE PLANTERS WILL HAVE |
| | WATER SUPPLY OR DRAINAGE CONNECTED TO THEM. SECTION |
| | 106.1.2. IF SO THE DRAINAGE PIPING & SUPPLY PIPING |
| | SHALL BE SHOWN ON THE FLOOR PLANS AND ON THE RISER |
| | DIAGRAMS. SECTION 106.3.5.1.3. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 6. OK |
| | |
| | 7. SHT 1-16.C ROOMS 1613 & 1628. PLEASE INDICATE THE |
| | FIXTURE TYPE, (BS), IN EACH ROOM. SECTION 106.1.2. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 8. SUBMIT DETAILS FOR THE MEN'S & WOMEN'S TOILET ROOMS |
| | SHOWING COMPLIANCE WITH SECTIONS 11-4.16, 11-4.17, |
| | 11-4.18, 11-4.19 & 11-4.22 WITH ALL SUBSECTIONS. ****NO |
| | RESPONSE, NOT ADDRESSED.--THIS SHALL APPLY FOR THE |
| | NEW TOILET ROOMS ADDED TO EACH FLOOR ALSO. |
| | |
| | 9. SUBMIT A DETAIL FOR THE ACCESSIBLE DRINKING |
| | FOUNTAINS. SHOW COMPLIANCE WITH SECTION 11-4.15 WILL |
| | ALL SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A) |
| | PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR |
| | STOOPING. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 10. OK |
| | 11. OK |
| | |
| | 12. SHT 1-15.C THE SINK IN ROOM 1520SHALL BE |
| | ACCESSIBLE. PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE |
| | WITH SECTION 11-4.24 AND ALL SUBSECTIONS. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 13. SHT S-1 SHALL BE SEALED WITH AN EMBOSSED OR |
| | IMPRESSION TYPE SEAL. NAIM & ASSOCIATES SHALL INDICATE |
| | THEIR BUSINESS NUMBER, (CERTIFICATE OF AUTHORIZATION), |
| | IN THE TITLE BLOCK. A PROFESSIONAL ENGINEER SHALL SIGN |
| | HIS NAME AND AFFIX HIS SEAL TO ALL PLANS, |
| | SPECIFICATIONS, REPORTS AND FINAL BID DOCUMENTS |
| | PROVIDED TO THE OWNER OR THE OWNER'S REPRESENTATIVE, OR |
| | OTHER DOCUMENTS PREPARED OR ISSUED BY SAID REGISTRANT |
| | AND BEING FILED FOR PUBLIC RECORD. THE DATE THAT THE |
| | SIGNATURE AND SEAL IS AFFIXED AS PROVIDED HEREIN SHALL |
| | BE ENTERED ON SAID PLANS, SPECIFICATIONS, REPORTS, OR |
| | OTHER DOCUMENTS IMMEDIATELY UNDER THE SIGNATURE OF THE |
| | PROFESSIONAL |
| | ENGINEER, FAC 61G15-23.002(1) FS 471.025. ENGINEERS |
| | SHALL LEGIBLY INDICATE THEIR NAME, ADDRESS AND LICENSE |
| | NUMBER ON EACH SHEET. IF PRACTICING THROUGH A DULY |
| | AUTHORIZED ENGINEERING BUSINESS, ENGINEERS, ENGINEERS |
| | SHALL LEGIBLY INDICATE THEIR NAME AND LICENSE NUMBER, |
| | AS WELL AS, THE NAME, ADDRESS AND CERTIFICATE OF |
| | AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS ON |
| | EACH SHEET. A TITLE BLOCK WILL SATISFY THIS |
| | REQUIREMENT. (THE CERTIFICATE OF AUTHORIZATION IS NOT |
| | INDICATED IN THE TITLE BLOCK).FAC 61G15-23.002(2) - |
| | FS 471.025.--PLANS APPEAR TO BE SIGNED WITH |
| | INITIALS. INITIALS ARE NOT APPROVED, THE LEGAL |
| | SIGNATURE IS REQUIRED. IF INDEED THIS IS THE LEGAL |
| | SIGNATURE, A SIGNED, SEALED, NOTORIZED LETTER SHALL BE |
| | SUBMITTED INDICATING THE LEGAL SIGNATURE FOR OUR |
| | FILES. |
| | ****NO RESPONSE, NOT ADDRESSED. --NEW SHEET S-2 SHALL |
| | MEET THE SAME REQUIREMENTS. S-2 NOT SIGNED, SEALED, |
| | DATED ETC. |
| | |
| | 14. OK |
| | 15. OK |
| | 16. OK |
| | 17. OK |
| | 18. OK |
| | 19. OK |
| | 20. OK |
| | |
| | 21. SHT P2.2 NOTE INDICATES PLUMBING FIXTURE SCHEDULE |
| | PROVIDED BY THE ARCHITECT. NO FIXTURE SCHEDULE HAS BEEN |
| | LOCATED, AND NOTHING TO INDICATED WHAT FIXTURE "BS" |
| | REPRESENTS.( SEE ROOMS 1613 & 1628).PLEASE INDICATE |
| | WHERE THE FIXTURE SCHEDULE CAN BE FOUND. SECTION |
| | 106.1.2. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 22. OK |
| | |
| | 23. SHT P3.1 PLEASE INDICATE WHAT THE COLD WATER LINE |
| | TO ROOM 1544 CONNECTS TO. PER SECTION 608, BACKFLOW |
| | PROTECTION MAY BE REQUIRED. |
| | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. NO |
| | INDICATION AS TO WHAT THE COLD WATER LINE CONNECTS TO. |
| | ALSO NO DRAIN SHOWN. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 24. OK |
| | |
| | 25. SHT P3.2 BACKFLOW PREVENTION IS REQUIRED ON THE |
| | COLD WATER SUPPLY TO THE WATER WALL. PLEASE INDICATE |
| | METHOD. SECTION 608. |
| | ****RESPONSE NOTED, BUT CHECK VALVES ARE NOT APPROVED. |
| | SEE TABLE 608.1.--A VACUUM BREAKER INSTALLED AT THE |
| | HIGHEST POINT OF THE SUPPLY LINE TO THE WATER WALL IS |
| | REQUIRED. (A WATTS MODEL N-36 OR EQUAL IS REQUIRED). |
| | |
| | 26. OK |
| | 27. OK |
| | 28. OK |
| | |
| | 29. SHT P51 THERMAL EXPANSION CONTROL IS REQUIRED FOR |
| | THE WATER HEATERS ON THE 15TH & 16TH FLOORS. PLEASE |
| | INDICATE THE METHOD OF CONTROL. SECTION 607.3.2. |
| | ****RESPONSE NOTED, BUT CALCULATIONS SHALL BE PROVIDED |
| | SHOWING THE CORRECT SIZE REQUIRED FOR 130 GALLONS, |
| | (TOTAL OF BOTH WATER HEATERS). SEE ATTACHED SHEET FOR |
| | AN EXAMPLE OF CALCULATIONS. INDICATE MANUF. AND MODEL |
| | WHEN SUMBITTING CALCULATIONS. |
| | |
| | 30. OK |
| | 31. OK |
| | |
| | ***********NEW COMMENTS*********** |
| | |
| | 1B. SHT P61 UPON REVIEW OF THE WATER RISER DIAGRAM FOR |
| | THE 15TH FLOOR, POTABLE WATER IS SHOWN TO A/C UNITS. |
| | THIS IS NOT APPROVED. PLEASE CLARIFY THE USE FOR THE |
| | WATER TO AN A/C UNIT SECTION 106.1.1.--PER 2003 |
| | NFPA-75 SECTION 5.2* & A.5.2 WATER SHOULD NOT BE IN THE |
| | SPACE ABOVE THE SUSPENDED CEILING AND OVER INFORMATION |
| | TECHNOLOGY EQUIPMENT OTHE THAN FOR SPRINKLER SYSTEM |
| | USE. |
| | |
| | 2B. SHT P61 DELETE THE CHECK VALVES FROM THE WATER |
| | RISER DIAGRAMS WHERE THE TOILET ROOMS 1573/1581 & |
| | 1663/1665 CONNECT TO THE WATER RISER OR ANY OTHER |
| | LOCATION ON THE RISER DIAGRAM. CHECK VALVES ARE NOT |
| | APPROVED FOR BACKFLOW PREVENTION. TABLE 608.1. |
| | |
| | 3B. SHT P0.1 DETAIL FOR THE PLATFORM MOUNTED WATER |
| | HEATERS. THE 80 GALLON EWH-2 WILL HAVE A TOTAL WEIGHT |
| | APPROX. 850 LBS. PLEASE SUBMIT INFORMATION ON THE |
| | SUPPORT FOR THE PLATFORM ATTACHMENT TO THE WALL. WILL |
| | THE STUDS BEHIND THE WALL BE STRUCTURAL STUDS OR |
| | DRYWALL STUDS. PLEASE INDICATE THE GUAGE OF THE STUDS |
| | AND THE SIZE OF THE BLOCKING THAT THE PLATFORM ANGLE |
| | BRACKETS WILL ATTACH TO. THIS INFORMATION SHOULD BE |
| | SUBMITTED BY THE STRUCTURAL ENGINEER. SECTION 106.1.2. |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |