| Date |
Text |
| 2007-09-19 18:41:41 | REVIEW #: 2 |
| | ACTION: |
| | |
| | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC |
| | CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| | RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| | |
| | 1. OK |
| | |
| | 2. OK |
| | |
| | 3. DAMPER IN NON-RATED WALL HAS BEEN REMOVED. HOWEVER, |
| | PLEASE SEE ELECTRICAL AND POSSIBLY BUILDING REVIEWS AS |
| | A RATED WALL MAY BE REQUIRED IN THIS LOCATION. |
| | |
| | 4. EXAMPLE: WORK ROOM 1542 HAS TYPE "B" WALLS ON ALL |
| | SIDES. BASED ON DETAIL 4 ON PG I-D.1, THE DRYWALL STOPS |
| | 6 INCHES ABOVE THE CEILING, BUT THE WALL INSULATION |
| | CONTINUES TO THE UNDERSIDE OF THE DECK, THUS IMPEDING |
| | FREE FLOW OF RETURN AIR FROM THIS SPACE. THIS CONDITION |
| | WOULD ALSO PRECLUDE THE WALL CAVITY FROM BEING SEALED |
| | AT THE TOP WITH AN APPROVED AIR BARRIER AS REQUIRED PER |
| | FBC,M 603.8. |
| | |
| | 5. OK |
| | |
| | 6. OK |
| | |
| | 7. OK |
| | |
| | 8. OK |
| | |
| | 9. THERE IS A FLEX DUCT PASSING THROUGH THE RATED WALL |
| | RIGHT NEXT TO THE NEWLY ADDED 54X12 FIRE DAMPER. THIS |
| | DUCT PENETRATION DOES JOT SHOW ANY OPENING PROTECTIVES |
| | AS REQUIRED BY FBC,M 607.5. AND 607.7. |
| | |
| | 10. THE 72X12 R/A FSD AT ROOMS 1633 AND 1601 IS SHOWN |
| | HALF WAY OUT OF THE RATED WALL. PLEASE SHOW HOW |
| | OOPENING PROTECTION IS TO BE MAINTAINED AT THE RATED |
| | WALL ASSEMBLY. ALSO, SEE NEW COMMENTS RELATED TO NEW |
| | FSD'D AND SMOKE CONTROL. |
| | |
| | 11. OK |
| | |
| | 12. OK |
| | |
| | 13. OK |
| | |
| | 14. VAV 16-13, EVEN THOUGH THE SCHEDULE HAS BEEN |
| | REVISED TO SHOW THE REQUIRED CFM AT 1150, THE FLOOR |
| | PLAN STILL SHOWS 1350 CFM. THERE ARE FOUR DROPS AT 300 |
| | CFM EACH PLUS ONE DROP AT 150 CFM. PLEASE SHOW |
| | CORRELATION BETWEEN SCHEDULE AND FLOOR PLANS. |
| | |
| | 15. OK PENDING FIELD VERIFICATION THAT THERE WILL BE NO |
| | EXHAUST DUCT UNDER POSITIVE PRESSURE EXPOSED TO THE |
| | PLENUM. FBC,M 601.3 |
| | |
| | 16. OK |
| | |
| | 17. OK |
| | |
| | 18. REGARDLESS OF THE LOCATION OF THE CONDENSERS ON THE |
| | ROOF, THEY ARE STILL OUTDOOR EQUIPMENT AND THEY ARE |
| | STILL ON THE ROOF. THEY ARE NOT PART OF THE BASE |
| | BUILDING SCOPE OF WORK. THEREFORE, CODE COMPLIANCE |
| | SHALL BE DEMONSTRATED AS PART OF THIS PERMIT |
| | APPLICATION. SHOW COMPLIANCE WITH FBC,M 301.13, FBC |
| | 1509.7 AND FBC CH.16. |
| | NOTE: IF PRE-ENGINEERED A/C STANDS ARE USED, PRODUCT |
| | APPROVAL IS REQUIRED BY FAC RULE 9B-72. FOR MORE |
| | INFORMATION ON THE FLORIDA PRODUCT APPROVAL SYSTEM |
| | PLEASE VISIT: WWW.FLORIDABUILDING.ORG |
| | |
| | 19. OK |
| | |
| | 20. IT IS AGREED THAT THE COMPUTER ROOM A/C UNITS NEED |
| | NOT BE INCLUDED IN CALCULATIONS. HOWEVER, AS THE BASE |
| | BUILDING WAS PERMITTED AS A SHELL BUILDING AND IS NOT |
| | COMPLETED, COMPLIANCE WITH FBC 13-101.1.6 IS REQUIRED. |
| | THE ENERGY USAGE OF THIS SPACE SHALL BE INCORPORATED |
| | INTO THE BASE BUILDING ENERGY CALCULATIONS PRIOR TO |
| | C.O. OF THE BASE BUILDING. |
| | |
| | IN ORDER TO DEMONSTRATE CODE COMPLIANCE, PROVIDE AT A |
| | MINIMUM AN INPUT DATA REPORT WHICH ACCURATELY REFLECTS |
| | ALL EQUIPMENT AND DEVICES SHOWN ON PLANS WHICH ARE |
| | SUBJECT TO FBC CH. 13. THIS INFORMATION SHALL BE |
| | PROVIDED TO THE DESIGNER OF RECORD FOR BASE BUILDING |
| | ENERGY CALCULATIONS. THIS DATA SHALL BE REVIEWED BY THE |
| | BASE BUILDING DESIGNER TO DETERMINE IF THE ENERGY |
| | USEAGE IN THIS SPACE CONFORMS TO BASE BUILDING |
| | ASSUMPTIONS AND/OR FALLS WITHIN PARAMETERS WHICH WILL |
| | ALLOW FINAL REVISED ENERGY CALCULATIONS FOR THE WHOLE |
| | BUILDING TO COMPLY WITH FBC CH.13. |
| | NOTE: IT IS RECOMMENDED THAT FOR THIS SPACE THE INPUT |
| | DATA BE SEPARATED INTO FLOORS AND LABELED "ZONE 15" AND |
| | "ZONE 16" TO FACILITATE INCORPORATION OF THE DATA INTO |
| | THE BASE BUILDING CALCULATIONS. PROOF OF ACCEPTANCE BY |
| | THE BASE BUILDING DESIGNER SHALL BE PROVIDED (A SIGNED |
| | SHOP DRAWING REVIEW STAMP IS SUFFICIENT) AT TIME OF |
| | RESUBMITTAL. |
| | |
| | NEW COMMENTS: |
| | |
| | A. SMOKE CONTROL SEQUENCE, THE STATEMENTS CONTAINED |
| | WITHIN THE SEQUENCE ARE IN CONFLICT WITH EACH OTHER. |
| | HOW CAN FLOORS 15 AND 16 BE CONSIDERED A SINGLE ZONE |
| | WHEN THE SEQUENCE ALSO STATES THAT THE 15TH AND 16TH |
| | FLOORS ARE TO BE INDEPENDENTLY PRESSURIZED DEPENDING ON |
| | THE FLOOR OF INCIDENT? IN ORDER FOR FLOORS 15 AND 16 TO |
| | BE CONSIDERED A SINGLE ZONE, BOTH FLOORS WOULD HAVE TO |
| | BE PRESSURIZED OR EXHAUSTED AS ONE FLOOR (OR ZONE). IF |
| | FLOORS 15 AND 16 ARE TO BE CONTROLLED INDEPENDENTLY, |
| | PROVIDE A SEQUENCE WHICH INCLUDES THE CONTROL OF ALL |
| | FIRE/SMOKE DAMPERS THAT MAY ALLOW THE FLOORS TO |
| | COMMUNICATE WITH EACH OTHER VIA THE MONUMENTAL STAIR |
| | AREA. THIS SYSTEM SHALL BE INCORPORATED INTO THE BASE |
| | BUILDING SMOKE CONTROL SYSTEM AND BE INCLUDED IN THE |
| | BASE BUILDING RATIONAL ANALYSIS AS WELL AS THE BASE |
| | BUILDING SEQUENCE OF OPERATIONS. |
| | |
| | B. SUPPLEMENTAL EXHAUST AND SUPPLY FANS, IF PART OF THE |
| | SMOKE CONTROL SYSTEM, SHALL ALSO BE CONTROLLED BY THE |
| | BASE BUILDING SYSTEM. RELATED FIRE/SMOKE DAMPERS ARE |
| | ALSO REQUIRED TO BE CONTROLLED BY THE BASE BUILDING |
| | SMOKE CONTROL SYSTEM PER FBC,M 513.5.2. |
| | |
| | C. NEW EF 15 IS SHOWN ON ROOF, BUT NEW SUPPLY FAN IS |
| | NOT SHOWN. THE NOTE STATES THAT THE EF AND SF ARE BASE |
| | BUILDING SUPPLIED. BASE BUILDING REVISED PAGE H1.17 |
| | DATED 8/29/07 DOES NOT SHOW EITHER FAN. THE LOCATIONS |
| | FOR THESE FANS AS SHOWN ON M2.2 AND M3.1 OF THIS PLAN |
| | ARE IN CONFLICT WITH BASE BUILDING PLANS. SHOW LOCATIN |
| | OF FANS ON PLAN IN LOCATIONS WHICH ARE NOT IN CONFLICT |
| | WITH BASE BUILDING EQUIPMENT AND DEMONSTRATE COMPLIANCE |
| | WITH FBC,M 401.5.1 AND 501.2. |
| | |
| | NOTE: ALL WORK RELATED TO THIS APPLICATION REQUIRES |
| | APPROVAL BY BASE BUILDING DESIGNER(S) OF RECORD AND MAY |
| | BE DEMONSTRATED VIA SIGNED SHOP DRAWING REVIEW STAMP |
| | FROM SAME. |
| | |
| | ONE SET OF OLD/VOIDED SHEETS ALONG WITH ONE SET OF NEW |
| | PLANS ALONG WITH CALCULATIONS HAVE BEEN RETAINED BY |
| | THIS OFFICE. |
| | |