| 2007-09-19 00:04:58 | *****DENIED***** |
| | *COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW WHICH |
| | STILL NEEDS TO BE ADDRESSED: |
| | |
| | 01.IN ADDITION TO THE 2003 EDITION OF NFPA 101, THE |
| | FLORIDA FIRE PREVENTION CODE (2004 EDITION) SHALL BE |
| | REFERENCED.PLAN SHEET I-16-LS &I -15-LS UNDER LIFE |
| | SAFETY AND CODE COMPLIANCE INCORRECTLY REFERS TO THE |
| | 2004 EDITION OF NFPA 101 |
| | |
| | 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD |
| | TO APPLICABLE CODES UNDER LIFE AND CODE COMPLIANCE |
| | SUMMARY ON SHEET I-16-LS AND/OR I-15-LS |
| | |
| | 03.ACCUMULATIONS OF COMBUSTIBLE WASTE MATERIALS, |
| | DUST, AND DEBRIS SHALL BE REMOVED FROM THE SITE AT THE |
| | END OF EACH OF SHIFT OR MORE FREQUENTLY AS NECESSARY |
| | FOR SAFE OPERATION.ADD TO GENERAL NOTES (SHEET |
| | I-G.1) |
| | |
| | 04.THE SCOPE OF WORK (ON THE 15TH AND 16TH FLOORS) |
| | SHALL NOT INTERFERE OR HINDER ACCESS TO OR EGRESS FROM |
| | OTHER FLOORS AND/OR AREAS OF THE BUILDING.ADD TO |
| | SHEET I-G.1 |
| | |
| | 05.DOORS LEADING DIRECTLY TO THE CORRIDORS SHALL BE |
| | AN APPROVED, LISTED, AND LABELED FIRE DOOR AND ASSEMBLY |
| | IN ACCORDANCE WITH NFPA 80.ADD/SHOW ON THE APPROPIATE |
| | PLAN SHEET WHERE THIS HAS BEEN ACKNOWLEDGEDSHEET |
| | I-DR-1 ? |
| | |
| | 09.ON SHEET E2.1, THE DESCRIPTION IS FOR THE 17TH |
| | FLOOR.PER YOUR APPLICATION, THE SCOPE OF WORK IS FOR |
| | THE 15TH AND 16TH FLOOR. DELETE REFERENCE TO THE 17TH |
| | FLOOR |
| | |
| | 11.TWO (OF THE FOUR) SPECIFICATION/DETAIL SHEETS ARE |
| | NOT LEGIBLE ENOUGH FOR REVIEW.PLEASE SEE SHEET FS0.1 |
| | |
| | |
| | *NEW COMMENT |
| | |
| | A.SHEET INDEX ON SHEET I-G.1 IS INCOMPLETE.ALTHOUGH |
| | SHEETS S-1 THRU FS2.3 WERE INCLUDED IN THE PLAN SET, NO |
| | REFLECTIONS OF THESE SHEETS IN THE SHEET INDEX |
| | |
| | B.CARD READERS(CR) AS SHOWN ON SHEET I-DR-1ON DOOR |
| | D6W SHALL NOT BE INCLUDED IN THIS PROJECTED SCOPE OF |
| | WORK.PLEASE BE ADVISED THAT SEPARATE PLANS AND PERMIT |
| | WILL BE REQUIRED FOR ENTRANCE/EGRESS ACCESS CONTROL |
| | SYSTEMS PROVIDED THAT THE CRITERIA AS PER NFPA 101 |
| | 7.2.1.6.2 ARE MET. |
| | |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED |
| | |
| | |