Plan Review Notes
Plan Review Notes For Permit 07030932
Permit Number 07030932
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2007-09-19 00:04:58*****DENIED*****
 *COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW WHICH
 STILL NEEDS TO BE ADDRESSED:
  
 01.IN ADDITION TO THE 2003 EDITION OF NFPA 101, THE
 FLORIDA FIRE PREVENTION CODE (2004 EDITION) SHALL BE
 REFERENCED.PLAN SHEET I-16-LS &I -15-LS UNDER LIFE
 SAFETY AND CODE COMPLIANCE INCORRECTLY REFERS TO THE
 2004 EDITION OF NFPA 101
  
 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD
 TO APPLICABLE CODES UNDER LIFE AND CODE COMPLIANCE
 SUMMARY ON SHEET I-16-LS AND/OR I-15-LS
  
 03.ACCUMULATIONS OF COMBUSTIBLE WASTE MATERIALS,
 DUST, AND DEBRIS SHALL BE REMOVED FROM THE SITE AT THE
 END OF EACH OF SHIFT OR MORE FREQUENTLY AS NECESSARY
 FOR SAFE OPERATION.ADD TO GENERAL NOTES (SHEET
 I-G.1)
  
 04.THE SCOPE OF WORK (ON THE 15TH AND 16TH FLOORS)
 SHALL NOT INTERFERE OR HINDER ACCESS TO OR EGRESS FROM
 OTHER FLOORS AND/OR AREAS OF THE BUILDING.ADD TO
 SHEET I-G.1
  
 05.DOORS LEADING DIRECTLY TO THE CORRIDORS SHALL BE
 AN APPROVED, LISTED, AND LABELED FIRE DOOR AND ASSEMBLY
 IN ACCORDANCE WITH NFPA 80.ADD/SHOW ON THE APPROPIATE
 PLAN SHEET WHERE THIS HAS BEEN ACKNOWLEDGEDSHEET
 I-DR-1 ?
  
 09.ON SHEET E2.1, THE DESCRIPTION IS FOR THE 17TH
 FLOOR.PER YOUR APPLICATION, THE SCOPE OF WORK IS FOR
 THE 15TH AND 16TH FLOOR. DELETE REFERENCE TO THE 17TH
 FLOOR
  
 11.TWO (OF THE FOUR) SPECIFICATION/DETAIL SHEETS ARE
 NOT LEGIBLE ENOUGH FOR REVIEW.PLEASE SEE SHEET FS0.1
  
  
 *NEW COMMENT
  
 A.SHEET INDEX ON SHEET I-G.1 IS INCOMPLETE.ALTHOUGH
 SHEETS S-1 THRU FS2.3 WERE INCLUDED IN THE PLAN SET, NO
 REFLECTIONS OF THESE SHEETS IN THE SHEET INDEX
  
 B.CARD READERS(CR) AS SHOWN ON SHEET I-DR-1ON DOOR
 D6W SHALL NOT BE INCLUDED IN THIS PROJECTED SCOPE OF
 WORK.PLEASE BE ADVISED THAT SEPARATE PLANS AND PERMIT
 WILL BE REQUIRED FOR ENTRANCE/EGRESS ACCESS CONTROL
 SYSTEMS PROVIDED THAT THE CRITERIA AS PER NFPA 101
 7.2.1.6.2 ARE MET.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722