| 2007-09-11 19:04:50 | |
| 2007-09-11 07:51:06 | 2007-09-11 07:51:06 |
| | |
| | *** DENIED 2ND REVIEW *** |
| | |
| | |
| | ** PLEASE SEE THERE ARE SEVERAL COMMENTS FROM THE |
| | PREVIOUS REVIEW WHICH ARE STILL IN NEED OF ADDRESSING. |
| | THERE ARE ALSO SEVERAL NEW COMMENTS BASED ON CHANGES TO |
| | PLANS AND NEW INFORMATION NOW SHOWN/SUBMITTED WHICH WAS |
| | NOT ON PREVIOUS PLANS. |
| | |
| | ** PLEASE KNOW THAT SOME OF THE PRELIMINARY COMMENTS |
| | BELOW DO NOT APPLY TO KAMM CONSULTING ENGINEERS. |
| | |
| | 1) NOTE:AS REQUESTED ON PREVIOUS REVIEW PLEASE BE |
| | SURE ALL ADOPTED RELEVANT CODES ARE STATED ON PLANS. |
| | PLEASE SEE SHEETS I-16 LS AND I-15 LS WHICH INDICATE A |
| | 2004 NATIONAL ELECTRICAL CODE AND A LIFE SAFETY CODE |
| | WHICH IS SHOWN AS 2004 ALSO. |
| | PLEASE ADJUST. |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE SEE THE FOLLOWING ADOPTED CODES SHOULD BE STATED |
| | ON PLANS AS THE STATE ADOPTED NEW CODES AS OF DECEMBER |
| | 8TH, 2006. |
| | PLEASE SEE THE WRONG NEC WAS STATED. |
| | 2004 FBC W/2006 REVISIONS, |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72. |
| | SOME OF THESE ARE STATED ON THE FRONT ARCHITECTURAL |
| | SHEETS AND SOME ARE NOT. PLEASE ALSO INCLUDE THE STATED |
| | CODE ON THE ELECTRICAL PLANS. |
| | ** PLEASE KNOW THAT ANY OTHER CODES WHICH MAY BE STATED |
| | FROM OTHER TRADES SHOULD BE NOTED BY OTHER TRADES. |
| | |
| | 2) NOTE:PLEASE SEE MISSING LICENSE INFORMATION FOR |
| | THE YJ DESIGN, PER FLORIDA STATUTES 481.221/471.023 |
| | PLEASE SEE FAC WHICH REQUIRES ALL INFORMATION ON TITLE |
| | BLOCKS FOR SAID FIRM PER 61G1-16.004. |
| | THIS WAS THE SAME AS PREVIOUS REVIEW. THE RESPONSE |
| | LETTER MENTIONS THIS WAS DONE AND DOES LIST A LICENSE |
| | NUMBER OF SOME TYPE HOWEVER THE NUMBER AS LISTED IS NOT |
| | LISTED WITH THE STATE OF FLORIDA DEPARTMENT OF BUSINESS |
| | AND PROFESSIONAL REGULATION. |
| | *THIS IS REQUIRED FOR ALL TRADES AND FOR ALL SHEETS |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE |
| | REVIEWER(S). |
| | |
| | 3) NOTE: PLEASE SEE *S* SHEETS WHICH CONTAIN A *RUBBER |
| | STAMP* BY THE ENGINEER WHICH IS REQUIRED TO BE A RAISED |
| | IMPRESSION TYPE SEAL IN THE STATE OF FLORIDA PER |
| | FAC61G15-23.001. |
| | PLEASE SEE TWO SETS DO NOT CONTAIN ANY SIGNATURE OR |
| | SEAL OF ANY KIND AND THE THIRD SET STILL INDICATES A |
| | *RUBBER STAMP* FOR THE ENGINEER. |
| | PLEASE ALSO SEE THE SEAL WHICH IS FROM THE STATE OF |
| | CALIFORNIA. THIS MUST BE LICENSED IN THE STATE OF |
| | FLORIDA. |
| | PLEASE ALSO SEE MISSING INFORMATION REQUIRED IN TITLE |
| | BLOCKS FOR FIRM LICENSE NUMBER ALSO KNOW AS THE |
| | CERTIFICATE OF AUTHORIZATION NUMBER, THE PRINTED NAME |
| | AND LICENSE NUMBER OF DESIGNER OF RECORD. |
| | ** THIS COMMENT AND INFORMATION WAS FORWARDED TO THE |
| | BUILDING REVIEWER. |
| | |
| | 4) NOTE: PLEASE SEE COMPLIANCE WITH THE FBC CHAPTER 13 |
| | HAS NOT YET BEEN ACHIEVED. |
| | PLEASE SEE THERE ARE SEVERAL ITEMS FROM THE PREVIOUS |
| | REVIEW NOTES WHICH ARE STILL IN NEED OF ADDRESSING. |
| | PLEASE SEE THE PLANS ARE STILL INDICATING A SUBSTANTIAL |
| | AMOUNT OF *STANDARD* LIGHTING SWITCHES WHERE CONTROLS |
| | OF SOME TYPE ARE NEEDED. |
| | 13-415.1.ABC.1.1. (SEE AREAS ON PLANS WHICH CONTAIN |
| | REDLINED LOCATIONS) |
| | PLEASE SEE THERE ARE NUMEROUS LIGHTING CONTROLS MISSING |
| | WHICH REQUIRES THE OCCUPANT TO VISUALLY SEE THE |
| | LIGHTING IN WHICH IS BEING OVER |
| | RIDDEN.13-415.1.ABC.1.1, .1.2. |
| | PLEASE SEE THERE ARE A SUBSTANTIAL AMOUNT OF LIGHTING |
| | FIXTURES WITH OUT ANY LIGHTING CONTROLS AS REQUIRED PER |
| | 13-415.1.ABC.1.1, .1.2 AND .1.3. :: |
| | FOR EXAMPLE PLEASE SEE ALL LIGHTING WHICH IS BEING |
| | SHOWN ON POWER PLANS WHICH IS NOT LOCATED ON LIGHTING |
| | PLANS AND CONTAINS NOT CONTROLS AS REQUIRED. SEE ONE |
| | FIXTURE ALONE WOULD BE FIXTURE TYPE *F*. PLEASE SEE |
| | THERE ARE SEVERAL FIXTURES WITH THIS SAME SCENARIO. |
| | THERE IS NO INFORMATION SUBMITTED FOR ROOMS SUCH AS |
| | ROOMS 1604, 1634 ETC THESE ROOMS REQUIRE INFORMATION |
| | FOR LIGHTING CONTROLS PER THE SAME SECTIONS AS NOTED. |
| | THIS IS REQUIRED AT THIS TIME. |
| | PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED DO NOT |
| | CORRELATE WITH THE LIGHTING OR POWER PLANS FOR THE |
| | NUMBER OF FIXTURES, THE TYPES OF LIGHTING FIXTURES, AND |
| | THE WATTAGE OF LIGHTING FIXTURES. ONE EXAMPLE IS THE |
| | FACT THE ENERGY CALCULATIONS INDICATE ONLY TWO TYPES OF |
| | LIGHT FIXTURES YET THE FIXTURE LEGEND INDICATES MORE |
| | THAN TWENTY DIFFERENT KIND OF FIXTURES. (PLEASE SEE |
| | COMMENTS WITH RESPECT TO LIGHTING FIXTURES ON PLANS |
| | WHICH ARE NOT ON LEGEND). |
| | PLEASE SEE THE TOTAL AMOUNT OF LIGHTING FIXTURES ON |
| | PLANS IS SUBSTANTIALLY HIGHER THAN THE 235 TOTAL SHOWN |
| | ON ENERGY CALCULATIONS. IN FACT THERE ARE HUNDREDS OF |
| | FIXTURES NOT INCLUDED ON THE INPUT DATA REPORT WHICH |
| | ARE INDEED ON PLANS AND ARE REQUIRED ON THE IDR> PLEASE |
| | SEE THE ENERGY CALCULATIONS ARE STILL ONLY INDICATING |
| | ONLY SQ FT FOR ONE FLOOR AND THE SQ FT WHICH IS SHOWN |
| | ON PLANS IS NOT THE SAME AS ON ENERGY CALCULATIONS. |
| | PLEASE SEE THE LIGHTING CONTACTORS ON PLANS CONTAIN A |
| | REFERENCE NUMBER, THIS REFERENCE NUMBER IS E2.1 WHICH |
| | IS FOR 15TH FLOOR LIGHTING. THIS IS NOT POSSIBLE FOR |
| | 16TH FLOOR. |
| | PLEASE SEE THERE ARE PLACES WHICH OVER RIDES FOR COMMON |
| | AREA ARE NEEDED. (EXAMPLE, EXIT FROM EXECUTIVE |
| | VESTIBULE) **PLEASE KNOW AS THERE ARE COMMENTS BELOW |
| | WITH RESPECT TO THIS ENTRANCE AND LOCATION, PLEASE KNOW |
| | THAT POSSIBLE LOCATION MAY CHANGE). |
| | PLEASE SEE TRACK LIGHTING PER 13-415.2.ABC .1.2. PLEASE |
| | CLARIFY LIGHTING CONTROL PANELS CONTROLLING LIGHTING |
| | OUTSIDE SPACE WHICH IS NOT PERMITTED PER |
| | 13-415.1.ABC.1.1. (BUILDING SIGN?) |
| | PLEASE SEE THERE ARE NUMEROUS LIGHTING FIXTURES WHICH |
| | CONTAIN NO CONTROLS WHICH ARE REQUIRED PER |
| | 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | |
| | ** ONCE AGAIN AS THERE ARE NUMEROUS ITEMS STILL MISSING |
| | WHICH ARE REQUIRED A FULL AND COMPLETE REVIEW OF |
| | SYSTEMS CAN NOT BE DONE AT THIS TIME. |
| | ****************************************************** |
| | * * |
| | ** PREVIOUS NOTE FROM FIRST REVIEW ** |
| | PLEASE SEE FBC 2004 W/ 2006 REVISIONS FOR CHAPTER 13. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3., |
| | 13-415.1.AB.1, 13-415.2, 13-415.2.ABC.1.2 |
| | PLEASE SEE SEVERAL AREAS WHICH ARE MISSING THE REQUIRED |
| | OVER RIDE DEVICES, OR OTHER TYPE DEVICES REQUIRED FOR |
| | CONTROL OF LIGHTING. |
| | PLEASE SEE SEVERAL LOCATIONS WHICH LIGHTING CONTROL IS |
| | REQUIRED FOR AREAS IN WHICH THE OCCUPANT CAN SEE THE |
| | LIGHTING WHICH IS BEING CONTROLLED. |
| | PLEASE SEE THE NORTH-SIDE ENTRANCE INTO THE 15TH FLOOR |
| | WHICH SHOWS NO CONTROL. |
| | PLEASE SEE THE SOUTH-SIDE ENTRANCE ON THE 16TH FLOOR |
| | WHICH SHOWS NO CONTROL. |
| | PLEASE SEE SEVERAL ROOMS WHICH CONTAIN ONLY A STANDARD |
| | WALL SWITCH. |
| | PLEASE SEE THE DETAIL FOR EACH CONTROL PANEL DOES NOT |
| | PROVIDE ENOUGH DETAILS FOR PROPOSED SYSTEM AND OVER |
| | RIDES. |
| | PLEASE SEE THAT NO MAXIMUM TIMES FOR OVER RIDES ARE |
| | STATED ON LEGEND. |
| | PLEASE SEE THAT NO CONTROLS ARE SHOWN FOR NUMEROUS |
| | LOCATIONS OF ACCENT LIGHTING. |
| | PLEASE SEE THAT THE CIRCUITING SHOWN ON THE LIGHTING |
| | CONTROL PANELS DO NOT CORRELATE WITH THE PLANS AS THERE |
| | ARE SEVERAL LIGHTING CIRCUITS ON PLANS NOT ON THE LCP. |
| | PLEASE SEE THAT THE LIGHTING WHICH IS BEING SHOWN UNDER |
| | A SEPARATE VOLTAGE OTHER THAN THE 277/480V WILL BE |
| | REQUIRED TO BE UNDER SEPARATE SYSTEM YET TO BE SHOWN. |
| | PLEASE SEE THAT THE LIGHTING SHOWN ON PLANS DO NOT |
| | CORRELATE WITH THE SUBMITTED ENERGY CALCULATIONS |
| | SUBMITTED FOR THE NUMBER OF FIXTURES, THE TYPE OF |
| | FIXTURES, THE WATTAGE ON THE FIXTURES ETC. THERE WERE |
| | ONLY TWO TYPES OF FIXTURES ON THE ENERGY CALCULATIONS |
| | SUBMITTED WHEN THERE IS AS MANY AS 20+ DIFFERENT TYPES |
| | OF FIXTURES? |
| | PLEASE INDICATE THE ZONES WHERE APPLICABLE. |
| | PLEASE SEE THE SQUARE FOOT LIMITS. PLEASE SEE THE |
| | ENERGY CALCULATIONS INDICATE A TOTAL OF 21,425 SQ. FT |
| | AND THE PLANS INDICATE A TOTAL OF 25,157 SQ FT PER |
| | FLOOR. PLEASE COORDINATE PLANS AND CALCULATIONS. PLEASE |
| | SEE BATHROOMS DO NOT PROVIDE DEVICES FOR SAFE COVERAGE |
| | FOR CONTROL OF LIGHTING. |
| | |
| | 5) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS |
| | FOR THE IT ROOM EQUIPMENT. THIS WAS NOT SUBMITTED AS |
| | RESPONSE LETTER MENTIONS. |
| | PLEASE SEE THE DISCONNECTING MEANS AS PER NFPA-75 |
| | 10.4.7, AND NEC 645.10 COULD NOT BE LOCATED. PLEASE SEE |
| | THE REQUIRED RATING FOR THIS ROOM IS NOT MEETING THE |
| | MINIMUM WALL CONSTRUCTION STANDARDS OF CHAPTER 3 OF |
| | NFPA-75. PLEASE SEE AREA OF EXITING AND ENTRANCE FROM |
| | EXECUTIVE ELEVATOR WHICH IS SHOWN A PART OF THE IT ROOM |
| | WHICH DOES NOT SEEM THIS WOULD BE PERMITTED AND ALSO |
| | INFORMATION BASED ON THE FM200 SYSTEM. THIS |
| | INFORMATION IS ALSO BE GIVEN TO THE OTHER TRADES FOR |
| | SPECIFIC REVIEW COMMENTS FROM THOSE TRADES. **PART OF |
| | PREVIOUS NOTE ** |
| | PLEASE SUBMIT INFORMATION FOR THE TWO SYSTEMS WHICH |
| | APPEAR TO SHOW SOME SORT OF SHUNT TRIP BUT NOT SURE HOW |
| | THIS PROPOSED SYSTEM DEVICES ARE BEING INSTALLED TO |
| | PROVIDE THIS SHUNT OF ALL REQUIRED. |
| | **PLEASE SEE REVIEW COMMENTS FROM OTHER TRADES WHICH |
| | MAY AFFECT PLANS WITH RESPECT TO RATING OF WALLS, ROOM, |
| | ETC. PLEASE SEE NFPA-75 |
| | FBC 106.1.2, NEC 90.7, 110.3 |
| | |
| | 6) NOTE: PLEASE PROVIDE THE PHOTO-METRICS FOR STAIR |
| | AREAS ( NOT EXIT STAIR TOWERS) IN THE SPACE FROM 16TH |
| | FLOOR TO THE 15TH FLOOR. PROVIDE LEVELS UNDER NORMAL |
| | AND LEVELS UNDER EMERGENCY CONDITIONS. SOME WERE |
| | SUBMITTED HOWEVER THE LEVEL(S) FOR EACH IS NOT |
| | SPECIFIED. |
| | PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.2. |
| | |
| | 7) NOTE: PLEASE SEE SHEET E2.1 WHICH INDICATES LIGHTING |
| | FOR FLOOR 17 IN TITLE BLOCK? THIS SEEMS TO BE A |
| | MISPRINT WHICH SHOULD READ 15TH FLOOR AS SHOWN ON |
| | PLANS. THIS IS THE SAME COMMENT FROM PREVIOUS REVIEW. |
| | FBC 106.1.2 |
| | |
| | 8) NOTE: PLEASE SEE THE FIXTURE TYPES AS LISTED ON |
| | LEGEND ARE NOT THE SAME FOR FIXTURES ON PLANS. |
| | *EXAMPLE: PLEASE SEE MANY OF THE EMERGENCY FIXTURES ARE |
| | SHOWN WITH DESIGNATIONS FOR NORMAL FIXTURE TYPES. |
| | PLEASE SEE SOME OF THE STRIP LIGHTING IS BEING SHOWN |
| | HAVING CIRCUITS TO FIXTURES WHICH ARE BEING SHOWN FROM |
| | TWO SEPARATE SERVICES/SYSTEMS. |
| | PLEASE SEE THE EMERGENCY LIGHTING FIXTURES ARE BEING |
| | SHOWN COMING FROM A *HOUSE PANEL* OF SORTS AND THE |
| | OCCUPANT/TENANT HAS NO ACCESS IN TURNING THESE FIXTURES |
| | OR BRANCH CIRCUITS OFF IN AN EMERGENCY OR OTHER |
| | SITUATION. A DISCONNECTING MEANS IN THE ELECTRICAL ROOM |
| | AT A MINIMUM WOULD BE REQUIRED AND LABELED AS SUCH. THE |
| | STRIP FIXTURES WHICH CONTAIN FEEDS FROM TWO SEPARATE |
| | PANELS AND SYSTEMS |
| | ARE NOT PERMITTED. |
| | |
| | 9) NOTE: PLEASE PROVIDE INFORMATION ON DOOR CLOSURES |
| | WHICH ARE REQUIRED TO MEET NFPA-101 7.2.1.5. THESE ARE |
| | STILL BEING REFERENCED ON PLANS AND IN NOTES FOR DOORS, |
| | MAGNETIC LOCKS/CLOSURES/HOLDERS ETC. |
| | IF NOT INCLUDED, THEN PLEASE ADJUST PLANS ACCORDINGLY. |
| | |
| | 10) NOTE: PLEASE SUBMIT AND COMPLETE THE PANEL |
| | SCHEDULE(S) LOAD CALCULATIONS ON PLANS. PLEASE INCLUDE |
| | ALL CONTINUOUS LOADS AT 125%. PLEASE KNOW THAT ANY |
| | ELECTRICAL WATER HEATERS UNDER THE 2005 NEC ARE NOW |
| | ALSO REQUIRED TO BE SHOWN AT 125%. 422.13 |
| | 220.12, 220.14, 220.42,220.43 220.44 ETC. |
| | RESPONSE MENTIONS THIS WAS DONE, HOWEVER IT IS UNCLEAR |
| | WHERE/HOW LOADS ARE DERIVED. |
| | FBC 106.3.5.1.2 |
| | |
| | 11) NOTE: PLEASE SEE THE PLANS ARE NOW INDICATING |
| | INFORMATION ON TRANSFORMERS FOR LOCATIONS COMPARED TO |
| | ELECTRICAL ROOMS ETC WHICH WAS NOT ON PREVIOUS PLANS. |
| | PLEASE SEE THE TAPPED CONDUCTORS ON THE LOAD SIDE OF |
| | THE TRANSFORMERS NEED TO BE INCREASED AS THEY DO NOT |
| | MEET 240.21, 408.36, 240.4 AND 310.16. |
| | PLEASE KNOW THAT TAPPED CONDUCTORS SHALL TERMINATE IN |
| | OVER CURRENT PROTECTION WHICH LIMITS THE LOAD ON THE |
| | CONDUCTORS. |
| | ON THE SECONDARY SIDE OF A TRANSFORMER WHEN THE |
| | CONDUCTORS DO NOT CORRELATE WITH THE STANDARD OVER |
| | CURRENT PROTECTION DEVICE PER 240.6 IT IS NOT PERMITTED |
| | TO GO TO THE NEXT SIZE UP. |
| | PLEASE ADJUST. |
| | PLEASE ALSO SEE THE SAME SECTIONS IN 240.21 AS THE |
| | LOCATIONS OF THE TRANSFORMERS COMPARED TO THE |
| | DISCONNECTING MEANS AND TERMINATION OF THE CONDUCTORS |
| | EXCEED THE LENGTH OF CONDUCTORS PERMITTED. PLEASE |
| | ADJUST THE LOCATIONS OF THE TRANSFORMERS OR ADDED OVER |
| | CURRENT PROTECTION/DISCONNECTING MEANS ON THE SECONDARY |
| | SIDE OF THE TRANSFORMERS. |
| | PLEASE BE SURE ALL CLEARANCES ARE MET PER 110.26 |
| | |
| | 12) NOTE: PLEASE SEE 110.26 AS THE ELECTRICAL PANELS IN |
| | THE TENANT ELECTRICAL ROOM DO NOT MEET THE MINIMUM |
| | CLEARANCES PER SCALE ON PLANS. |
| | |
| | 13) NOTE: THE PLANS INDICATE A PANEL ER, THE PANEL |
| | SCHEDULE SHEETS INDICATE A PANEL ER HOWEVER THIS IS NOT |
| | INCLUDED ON THE RISER DIAGRAM. |
| | PLEASE VERIFY 645.5A AND INDICATE WHERE THE 125% HAS |
| | BEEN FIGURED. |
| | |
| | 14) NOTE: PLEASE SEE THERE ARE SEVERAL STANDARD |
| | LIGHTING FIXTURES WHICH CONTAIN THE NOTE WHICH MENTIONS |
| | TO WIRED TO EMERGENCY CIRCUIT YET THE FIXTURE IS NOT AN |
| | EMERGENCY FIXTURE. |
| | PLEASE SEE FOR EXAMPLE ROOM 1657 ON SHEET E2.2 (NOT THE |
| | ONLY LOCATION) |
| | |
| | 15) NOTE: PLEASE INDICATE HOW THE CONDUCTORS ARE RUN, |
| | SIZED AND CONNECTED TO THE IT EQUIPMENT. PLEASE SEE |
| | 2003 NFPA-75 AND INSTALLATION STANDARDS. |
| | PER 645.5 |
| | |
| | 16) NOTE: PLEASE INDICATE THE AIC RATINGS FOR ALL NEW |
| | ELECTRICAL SERVICE EQUIPMENT. THIS NOTE IS TO REMAIN AS |
| | THERE ARE ITEMS WHICH WILL BE CHANGING, NOT INCLUDED AT |
| | THIS TIME WHICH MAY ALSO REQUIRE THE RATINGS TO BE |
| | INDICATED. |
| | 110.9, FBC 106.1.2 |
| | |
| | 17) NOTE: PLEASE KNOW AS THE BUILDING IS STILL UNDER |
| | CONSTRUCTION AND THE RESPONSIBILITY OF THE BASE |
| | BUILDING DESIGN TEAM, PLANS SHALL BEAR A *SHOP DRAWING* |
| | REVIEW STAMP OF SOME TYPE. THESE ITEMS WHICH ARE BEING |
| | DESIGNED INTO A SHELL BUILDING NEED TO BE KNOWN TO THE |
| | BASE BUILDING DESIGN TEAM FOR SEVERAL ITEMS INCLUDING |
| | ENERGY LOADS, ELECTRICAL LOADS ETC. |
| | THIS HAS BEEN CONFIRMED WITH THE BUILDING OFFICIAL. |
| | |
| | 18) NOTE: PLEASE SEE ONE SET OF PLANS HAS NUMEROUS |
| | LOCATIONS REDLINED FOR MANY OF THE NOTES ABOVE HOWEVER |
| | NOT ALL. |
| | |
| | 19) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A |
| | NOTICE BEING GIVEN AT THIS TIME. |
| | THIS OFFICE MAY RETAIN SET(S) OF PLANS. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-09-10 07:11:23 | 2007-09-10 07:11:23 |
| | |
| | IN PROGRESS |
| 2007-09-09 14:57:28 | 2007-09-09 14:57:28 |
| | |
| | NOTES TO FOLLOW ONCE REVIEW IS COMPLETED. |
| 2007-09-07 20:14:22 | 2007-09-07 20:14:22 |
| | |
| | IN ELEC FOR REVIEW. REVIEW TO COMMENCE ON 9/8 |