Plan Review Notes
Plan Review Notes For Permit 07030932
Permit Number 07030932
Review Stop E
Sequence Number 2
Notes
Date Text
2007-09-11 19:04:50 
2007-09-11 07:51:062007-09-11 07:51:06
  
 *** DENIED 2ND REVIEW ***
  
  
 ** PLEASE SEE THERE ARE SEVERAL COMMENTS FROM THE
 PREVIOUS REVIEW WHICH ARE STILL IN NEED OF ADDRESSING.
 THERE ARE ALSO SEVERAL NEW COMMENTS BASED ON CHANGES TO
 PLANS AND NEW INFORMATION NOW SHOWN/SUBMITTED WHICH WAS
 NOT ON PREVIOUS PLANS.
  
 ** PLEASE KNOW THAT SOME OF THE PRELIMINARY COMMENTS
 BELOW DO NOT APPLY TO KAMM CONSULTING ENGINEERS.
  
 1) NOTE:AS REQUESTED ON PREVIOUS REVIEW PLEASE BE
 SURE ALL ADOPTED RELEVANT CODES ARE STATED ON PLANS.
 PLEASE SEE SHEETS I-16 LS AND I-15 LS WHICH INDICATE A
 2004 NATIONAL ELECTRICAL CODE AND A LIFE SAFETY CODE
 WHICH IS SHOWN AS 2004 ALSO.
 PLEASE ADJUST.
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE THE FOLLOWING ADOPTED CODES SHOULD BE STATED
 ON PLANS AS THE STATE ADOPTED NEW CODES AS OF DECEMBER
 8TH, 2006.
 PLEASE SEE THE WRONG NEC WAS STATED.
 2004 FBC W/2006 REVISIONS,
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72.
 SOME OF THESE ARE STATED ON THE FRONT ARCHITECTURAL
 SHEETS AND SOME ARE NOT. PLEASE ALSO INCLUDE THE STATED
 CODE ON THE ELECTRICAL PLANS.
 ** PLEASE KNOW THAT ANY OTHER CODES WHICH MAY BE STATED
 FROM OTHER TRADES SHOULD BE NOTED BY OTHER TRADES.
  
 2) NOTE:PLEASE SEE MISSING LICENSE INFORMATION FOR
 THE YJ DESIGN, PER FLORIDA STATUTES 481.221/471.023
 PLEASE SEE FAC WHICH REQUIRES ALL INFORMATION ON TITLE
 BLOCKS FOR SAID FIRM PER 61G1-16.004.
 THIS WAS THE SAME AS PREVIOUS REVIEW. THE RESPONSE
 LETTER MENTIONS THIS WAS DONE AND DOES LIST A LICENSE
 NUMBER OF SOME TYPE HOWEVER THE NUMBER AS LISTED IS NOT
 LISTED WITH THE STATE OF FLORIDA DEPARTMENT OF BUSINESS
 AND PROFESSIONAL REGULATION.
 *THIS IS REQUIRED FOR ALL TRADES AND FOR ALL SHEETS
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE
 REVIEWER(S).
  
 3) NOTE: PLEASE SEE *S* SHEETS WHICH CONTAIN A *RUBBER
 STAMP* BY THE ENGINEER WHICH IS REQUIRED TO BE A RAISED
 IMPRESSION TYPE SEAL IN THE STATE OF FLORIDA PER
 FAC61G15-23.001.
 PLEASE SEE TWO SETS DO NOT CONTAIN ANY SIGNATURE OR
 SEAL OF ANY KIND AND THE THIRD SET STILL INDICATES A
 *RUBBER STAMP* FOR THE ENGINEER.
 PLEASE ALSO SEE THE SEAL WHICH IS FROM THE STATE OF
 CALIFORNIA. THIS MUST BE LICENSED IN THE STATE OF
 FLORIDA.
 PLEASE ALSO SEE MISSING INFORMATION REQUIRED IN TITLE
 BLOCKS FOR FIRM LICENSE NUMBER ALSO KNOW AS THE
 CERTIFICATE OF AUTHORIZATION NUMBER, THE PRINTED NAME
 AND LICENSE NUMBER OF DESIGNER OF RECORD.
 ** THIS COMMENT AND INFORMATION WAS FORWARDED TO THE
 BUILDING REVIEWER.
  
 4) NOTE: PLEASE SEE COMPLIANCE WITH THE FBC CHAPTER 13
 HAS NOT YET BEEN ACHIEVED.
 PLEASE SEE THERE ARE SEVERAL ITEMS FROM THE PREVIOUS
 REVIEW NOTES WHICH ARE STILL IN NEED OF ADDRESSING.
 PLEASE SEE THE PLANS ARE STILL INDICATING A SUBSTANTIAL
 AMOUNT OF *STANDARD* LIGHTING SWITCHES WHERE CONTROLS
 OF SOME TYPE ARE NEEDED.
 13-415.1.ABC.1.1. (SEE AREAS ON PLANS WHICH CONTAIN
 REDLINED LOCATIONS)
 PLEASE SEE THERE ARE NUMEROUS LIGHTING CONTROLS MISSING
 WHICH REQUIRES THE OCCUPANT TO VISUALLY SEE THE
 LIGHTING IN WHICH IS BEING OVER
 RIDDEN.13-415.1.ABC.1.1, .1.2.
 PLEASE SEE THERE ARE A SUBSTANTIAL AMOUNT OF LIGHTING
 FIXTURES WITH OUT ANY LIGHTING CONTROLS AS REQUIRED PER
 13-415.1.ABC.1.1, .1.2 AND .1.3. ::
 FOR EXAMPLE PLEASE SEE ALL LIGHTING WHICH IS BEING
 SHOWN ON POWER PLANS WHICH IS NOT LOCATED ON LIGHTING
 PLANS AND CONTAINS NOT CONTROLS AS REQUIRED. SEE ONE
 FIXTURE ALONE WOULD BE FIXTURE TYPE *F*. PLEASE SEE
 THERE ARE SEVERAL FIXTURES WITH THIS SAME SCENARIO.
 THERE IS NO INFORMATION SUBMITTED FOR ROOMS SUCH AS
 ROOMS 1604, 1634 ETC THESE ROOMS REQUIRE INFORMATION
 FOR LIGHTING CONTROLS PER THE SAME SECTIONS AS NOTED.
 THIS IS REQUIRED AT THIS TIME.
 PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED DO NOT
 CORRELATE WITH THE LIGHTING OR POWER PLANS FOR THE
 NUMBER OF FIXTURES, THE TYPES OF LIGHTING FIXTURES, AND
 THE WATTAGE OF LIGHTING FIXTURES. ONE EXAMPLE IS THE
 FACT THE ENERGY CALCULATIONS INDICATE ONLY TWO TYPES OF
 LIGHT FIXTURES YET THE FIXTURE LEGEND INDICATES MORE
 THAN TWENTY DIFFERENT KIND OF FIXTURES. (PLEASE SEE
 COMMENTS WITH RESPECT TO LIGHTING FIXTURES ON PLANS
 WHICH ARE NOT ON LEGEND).
 PLEASE SEE THE TOTAL AMOUNT OF LIGHTING FIXTURES ON
 PLANS IS SUBSTANTIALLY HIGHER THAN THE 235 TOTAL SHOWN
 ON ENERGY CALCULATIONS. IN FACT THERE ARE HUNDREDS OF
 FIXTURES NOT INCLUDED ON THE INPUT DATA REPORT WHICH
 ARE INDEED ON PLANS AND ARE REQUIRED ON THE IDR> PLEASE
 SEE THE ENERGY CALCULATIONS ARE STILL ONLY INDICATING
 ONLY SQ FT FOR ONE FLOOR AND THE SQ FT WHICH IS SHOWN
 ON PLANS IS NOT THE SAME AS ON ENERGY CALCULATIONS.
 PLEASE SEE THE LIGHTING CONTACTORS ON PLANS CONTAIN A
 REFERENCE NUMBER, THIS REFERENCE NUMBER IS E2.1 WHICH
 IS FOR 15TH FLOOR LIGHTING. THIS IS NOT POSSIBLE FOR
 16TH FLOOR.
 PLEASE SEE THERE ARE PLACES WHICH OVER RIDES FOR COMMON
 AREA ARE NEEDED. (EXAMPLE, EXIT FROM EXECUTIVE
 VESTIBULE) **PLEASE KNOW AS THERE ARE COMMENTS BELOW
 WITH RESPECT TO THIS ENTRANCE AND LOCATION, PLEASE KNOW
 THAT POSSIBLE LOCATION MAY CHANGE).
 PLEASE SEE TRACK LIGHTING PER 13-415.2.ABC .1.2. PLEASE
 CLARIFY LIGHTING CONTROL PANELS CONTROLLING LIGHTING
 OUTSIDE SPACE WHICH IS NOT PERMITTED PER
 13-415.1.ABC.1.1. (BUILDING SIGN?)
 PLEASE SEE THERE ARE NUMEROUS LIGHTING FIXTURES WHICH
 CONTAIN NO CONTROLS WHICH ARE REQUIRED PER
 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 ** ONCE AGAIN AS THERE ARE NUMEROUS ITEMS STILL MISSING
 WHICH ARE REQUIRED A FULL AND COMPLETE REVIEW OF
 SYSTEMS CAN NOT BE DONE AT THIS TIME.
 ******************************************************
 * *
 ** PREVIOUS NOTE FROM FIRST REVIEW **
 PLEASE SEE FBC 2004 W/ 2006 REVISIONS FOR CHAPTER 13.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.,
 13-415.1.AB.1, 13-415.2, 13-415.2.ABC.1.2
 PLEASE SEE SEVERAL AREAS WHICH ARE MISSING THE REQUIRED
 OVER RIDE DEVICES, OR OTHER TYPE DEVICES REQUIRED FOR
 CONTROL OF LIGHTING.
 PLEASE SEE SEVERAL LOCATIONS WHICH LIGHTING CONTROL IS
 REQUIRED FOR AREAS IN WHICH THE OCCUPANT CAN SEE THE
 LIGHTING WHICH IS BEING CONTROLLED.
 PLEASE SEE THE NORTH-SIDE ENTRANCE INTO THE 15TH FLOOR
 WHICH SHOWS NO CONTROL.
 PLEASE SEE THE SOUTH-SIDE ENTRANCE ON THE 16TH FLOOR
 WHICH SHOWS NO CONTROL.
 PLEASE SEE SEVERAL ROOMS WHICH CONTAIN ONLY A STANDARD
 WALL SWITCH.
 PLEASE SEE THE DETAIL FOR EACH CONTROL PANEL DOES NOT
 PROVIDE ENOUGH DETAILS FOR PROPOSED SYSTEM AND OVER
 RIDES.
 PLEASE SEE THAT NO MAXIMUM TIMES FOR OVER RIDES ARE
 STATED ON LEGEND.
 PLEASE SEE THAT NO CONTROLS ARE SHOWN FOR NUMEROUS
 LOCATIONS OF ACCENT LIGHTING.
 PLEASE SEE THAT THE CIRCUITING SHOWN ON THE LIGHTING
 CONTROL PANELS DO NOT CORRELATE WITH THE PLANS AS THERE
 ARE SEVERAL LIGHTING CIRCUITS ON PLANS NOT ON THE LCP.
 PLEASE SEE THAT THE LIGHTING WHICH IS BEING SHOWN UNDER
 A SEPARATE VOLTAGE OTHER THAN THE 277/480V WILL BE
 REQUIRED TO BE UNDER SEPARATE SYSTEM YET TO BE SHOWN.
 PLEASE SEE THAT THE LIGHTING SHOWN ON PLANS DO NOT
 CORRELATE WITH THE SUBMITTED ENERGY CALCULATIONS
 SUBMITTED FOR THE NUMBER OF FIXTURES, THE TYPE OF
 FIXTURES, THE WATTAGE ON THE FIXTURES ETC. THERE WERE
 ONLY TWO TYPES OF FIXTURES ON THE ENERGY CALCULATIONS
 SUBMITTED WHEN THERE IS AS MANY AS 20+ DIFFERENT TYPES
 OF FIXTURES?
 PLEASE INDICATE THE ZONES WHERE APPLICABLE.
 PLEASE SEE THE SQUARE FOOT LIMITS. PLEASE SEE THE
 ENERGY CALCULATIONS INDICATE A TOTAL OF 21,425 SQ. FT
 AND THE PLANS INDICATE A TOTAL OF 25,157 SQ FT PER
 FLOOR. PLEASE COORDINATE PLANS AND CALCULATIONS. PLEASE
 SEE BATHROOMS DO NOT PROVIDE DEVICES FOR SAFE COVERAGE
 FOR CONTROL OF LIGHTING.
  
 5) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS
 FOR THE IT ROOM EQUIPMENT. THIS WAS NOT SUBMITTED AS
 RESPONSE LETTER MENTIONS.
 PLEASE SEE THE DISCONNECTING MEANS AS PER NFPA-75
 10.4.7, AND NEC 645.10 COULD NOT BE LOCATED. PLEASE SEE
 THE REQUIRED RATING FOR THIS ROOM IS NOT MEETING THE
 MINIMUM WALL CONSTRUCTION STANDARDS OF CHAPTER 3 OF
 NFPA-75. PLEASE SEE AREA OF EXITING AND ENTRANCE FROM
 EXECUTIVE ELEVATOR WHICH IS SHOWN A PART OF THE IT ROOM
 WHICH DOES NOT SEEM THIS WOULD BE PERMITTED AND ALSO
 INFORMATION BASED ON THE FM200 SYSTEM. THIS
 INFORMATION IS ALSO BE GIVEN TO THE OTHER TRADES FOR
 SPECIFIC REVIEW COMMENTS FROM THOSE TRADES. **PART OF
 PREVIOUS NOTE **
 PLEASE SUBMIT INFORMATION FOR THE TWO SYSTEMS WHICH
 APPEAR TO SHOW SOME SORT OF SHUNT TRIP BUT NOT SURE HOW
 THIS PROPOSED SYSTEM DEVICES ARE BEING INSTALLED TO
 PROVIDE THIS SHUNT OF ALL REQUIRED.
 **PLEASE SEE REVIEW COMMENTS FROM OTHER TRADES WHICH
 MAY AFFECT PLANS WITH RESPECT TO RATING OF WALLS, ROOM,
 ETC. PLEASE SEE NFPA-75
 FBC 106.1.2, NEC 90.7, 110.3
  
 6) NOTE: PLEASE PROVIDE THE PHOTO-METRICS FOR STAIR
 AREAS ( NOT EXIT STAIR TOWERS) IN THE SPACE FROM 16TH
 FLOOR TO THE 15TH FLOOR. PROVIDE LEVELS UNDER NORMAL
 AND LEVELS UNDER EMERGENCY CONDITIONS. SOME WERE
 SUBMITTED HOWEVER THE LEVEL(S) FOR EACH IS NOT
 SPECIFIED.
 PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.2.
  
 7) NOTE: PLEASE SEE SHEET E2.1 WHICH INDICATES LIGHTING
 FOR FLOOR 17 IN TITLE BLOCK? THIS SEEMS TO BE A
 MISPRINT WHICH SHOULD READ 15TH FLOOR AS SHOWN ON
 PLANS. THIS IS THE SAME COMMENT FROM PREVIOUS REVIEW.
 FBC 106.1.2
  
 8) NOTE: PLEASE SEE THE FIXTURE TYPES AS LISTED ON
 LEGEND ARE NOT THE SAME FOR FIXTURES ON PLANS.
 *EXAMPLE: PLEASE SEE MANY OF THE EMERGENCY FIXTURES ARE
 SHOWN WITH DESIGNATIONS FOR NORMAL FIXTURE TYPES.
 PLEASE SEE SOME OF THE STRIP LIGHTING IS BEING SHOWN
 HAVING CIRCUITS TO FIXTURES WHICH ARE BEING SHOWN FROM
 TWO SEPARATE SERVICES/SYSTEMS.
 PLEASE SEE THE EMERGENCY LIGHTING FIXTURES ARE BEING
 SHOWN COMING FROM A *HOUSE PANEL* OF SORTS AND THE
 OCCUPANT/TENANT HAS NO ACCESS IN TURNING THESE FIXTURES
 OR BRANCH CIRCUITS OFF IN AN EMERGENCY OR OTHER
 SITUATION. A DISCONNECTING MEANS IN THE ELECTRICAL ROOM
 AT A MINIMUM WOULD BE REQUIRED AND LABELED AS SUCH. THE
 STRIP FIXTURES WHICH CONTAIN FEEDS FROM TWO SEPARATE
 PANELS AND SYSTEMS
 ARE NOT PERMITTED.
  
 9) NOTE: PLEASE PROVIDE INFORMATION ON DOOR CLOSURES
 WHICH ARE REQUIRED TO MEET NFPA-101 7.2.1.5. THESE ARE
 STILL BEING REFERENCED ON PLANS AND IN NOTES FOR DOORS,
 MAGNETIC LOCKS/CLOSURES/HOLDERS ETC.
 IF NOT INCLUDED, THEN PLEASE ADJUST PLANS ACCORDINGLY.
  
 10) NOTE: PLEASE SUBMIT AND COMPLETE THE PANEL
 SCHEDULE(S) LOAD CALCULATIONS ON PLANS. PLEASE INCLUDE
 ALL CONTINUOUS LOADS AT 125%. PLEASE KNOW THAT ANY
 ELECTRICAL WATER HEATERS UNDER THE 2005 NEC ARE NOW
 ALSO REQUIRED TO BE SHOWN AT 125%. 422.13
 220.12, 220.14, 220.42,220.43 220.44 ETC.
 RESPONSE MENTIONS THIS WAS DONE, HOWEVER IT IS UNCLEAR
 WHERE/HOW LOADS ARE DERIVED.
 FBC 106.3.5.1.2
  
 11) NOTE: PLEASE SEE THE PLANS ARE NOW INDICATING
 INFORMATION ON TRANSFORMERS FOR LOCATIONS COMPARED TO
 ELECTRICAL ROOMS ETC WHICH WAS NOT ON PREVIOUS PLANS.
 PLEASE SEE THE TAPPED CONDUCTORS ON THE LOAD SIDE OF
 THE TRANSFORMERS NEED TO BE INCREASED AS THEY DO NOT
 MEET 240.21, 408.36, 240.4 AND 310.16.
 PLEASE KNOW THAT TAPPED CONDUCTORS SHALL TERMINATE IN
 OVER CURRENT PROTECTION WHICH LIMITS THE LOAD ON THE
 CONDUCTORS.
 ON THE SECONDARY SIDE OF A TRANSFORMER WHEN THE
 CONDUCTORS DO NOT CORRELATE WITH THE STANDARD OVER
 CURRENT PROTECTION DEVICE PER 240.6 IT IS NOT PERMITTED
 TO GO TO THE NEXT SIZE UP.
 PLEASE ADJUST.
 PLEASE ALSO SEE THE SAME SECTIONS IN 240.21 AS THE
 LOCATIONS OF THE TRANSFORMERS COMPARED TO THE
 DISCONNECTING MEANS AND TERMINATION OF THE CONDUCTORS
 EXCEED THE LENGTH OF CONDUCTORS PERMITTED. PLEASE
 ADJUST THE LOCATIONS OF THE TRANSFORMERS OR ADDED OVER
 CURRENT PROTECTION/DISCONNECTING MEANS ON THE SECONDARY
 SIDE OF THE TRANSFORMERS.
 PLEASE BE SURE ALL CLEARANCES ARE MET PER 110.26
  
 12) NOTE: PLEASE SEE 110.26 AS THE ELECTRICAL PANELS IN
 THE TENANT ELECTRICAL ROOM DO NOT MEET THE MINIMUM
 CLEARANCES PER SCALE ON PLANS.
  
 13) NOTE: THE PLANS INDICATE A PANEL ER, THE PANEL
 SCHEDULE SHEETS INDICATE A PANEL ER HOWEVER THIS IS NOT
 INCLUDED ON THE RISER DIAGRAM.
 PLEASE VERIFY 645.5A AND INDICATE WHERE THE 125% HAS
 BEEN FIGURED.
  
 14) NOTE: PLEASE SEE THERE ARE SEVERAL STANDARD
 LIGHTING FIXTURES WHICH CONTAIN THE NOTE WHICH MENTIONS
 TO WIRED TO EMERGENCY CIRCUIT YET THE FIXTURE IS NOT AN
 EMERGENCY FIXTURE.
 PLEASE SEE FOR EXAMPLE ROOM 1657 ON SHEET E2.2 (NOT THE
 ONLY LOCATION)
  
 15) NOTE: PLEASE INDICATE HOW THE CONDUCTORS ARE RUN,
 SIZED AND CONNECTED TO THE IT EQUIPMENT. PLEASE SEE
 2003 NFPA-75 AND INSTALLATION STANDARDS.
 PER 645.5
  
 16) NOTE: PLEASE INDICATE THE AIC RATINGS FOR ALL NEW
 ELECTRICAL SERVICE EQUIPMENT. THIS NOTE IS TO REMAIN AS
 THERE ARE ITEMS WHICH WILL BE CHANGING, NOT INCLUDED AT
 THIS TIME WHICH MAY ALSO REQUIRE THE RATINGS TO BE
 INDICATED.
 110.9, FBC 106.1.2
  
 17) NOTE: PLEASE KNOW AS THE BUILDING IS STILL UNDER
 CONSTRUCTION AND THE RESPONSIBILITY OF THE BASE
 BUILDING DESIGN TEAM, PLANS SHALL BEAR A *SHOP DRAWING*
 REVIEW STAMP OF SOME TYPE. THESE ITEMS WHICH ARE BEING
 DESIGNED INTO A SHELL BUILDING NEED TO BE KNOWN TO THE
 BASE BUILDING DESIGN TEAM FOR SEVERAL ITEMS INCLUDING
 ENERGY LOADS, ELECTRICAL LOADS ETC.
 THIS HAS BEEN CONFIRMED WITH THE BUILDING OFFICIAL.
  
 18) NOTE: PLEASE SEE ONE SET OF PLANS HAS NUMEROUS
 LOCATIONS REDLINED FOR MANY OF THE NOTES ABOVE HOWEVER
 NOT ALL.
  
 19) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE BEING GIVEN AT THIS TIME.
 THIS OFFICE MAY RETAIN SET(S) OF PLANS.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-09-10 07:11:232007-09-10 07:11:23
  
 IN PROGRESS
2007-09-09 14:57:282007-09-09 14:57:28
  
 NOTES TO FOLLOW ONCE REVIEW IS COMPLETED.
2007-09-07 20:14:222007-09-07 20:14:22
  
 IN ELEC FOR REVIEW. REVIEW TO COMMENCE ON 9/8