| 2007-09-20 07:03:35 | 525 OKEECHOBEE BLVD |
| | INTECH |
| | SEPT.19, 2007 |
| | |
| | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 07030932 |
| | ADD: 525 OKEECHOBEE BLVD PENTHOUSE A & B |
| | CONT: CENTEX/ BALFOUR BEATTY |
| | TEL: (954)214-9415 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3) NOTE IN SOME TITLE BLOCKS THERE IS YCJ DESIGN AND |
| | OTHER TITLE BLOCKS YJ ARCHITECTURAL DESIGNS ( YOUSEF |
| | JALALI) , PLEASE SEE THE FOLLOWING FLORIDA STATUTES FOR |
| | ARCHITECTS AND INTERIOR DESIGNERS: |
| | |
| | 3A)Y J ARCHITECTURAL DESIGN WILL REQUIRE A |
| | CERTIFICATE OF AUTHORIZATION, FLORIDA STATE STATUTE |
| | 481.219(2) (ARCHITECT),THE TITLE BLOCK FOR ANY |
| | SHEET BEARING THE NAME OF AN ARCHITECT PRACTICING UNDER |
| | A FICTITIOUS NAME, A CORPORATION, OR A PARTNERSHIP, |
| | OFFERING ARCHITECTURAL SERVICES, SHALL INCLUDE THE |
| | CERTIFICATE OF AUTHORIZATION NUMBER. |
| | |
| | 3B) YCJ DESIGN, FLORIDA S. S. 481.219(3)(INTERIOR |
| | DECORATORS)FOR THE PURPOSES OF THIS SECTION, A |
| | CERTIFICATE OF AUTHORIZATION SHALL BE REQUIRED FOR A |
| | CORPORATION, LIMITED LIABILITY COMPANY, PARTNERSHIP, OR |
| | PERSON OPERATING UNDER A FICTITIOUS NAME, OFFERING |
| | INTERIOR DESIGN SERVICES TO THE PUBLIC JOINTLY OR |
| | SEPARATELY. HOWEVER, WHEN AN INDIVIDUAL IS PRACTICING |
| | INTERIOR DESIGN IN HER OR HIS OWN NAME, SHE OR HE SHALL |
| | NOT BE REQUIRED TO BE CERTIFIED UNDER THIS SECTION. |
| | |
| | 3C) PLEASE SEE FLORIDA STATE STATUTE 481.2131 (INTERIOR |
| | DESIGNERS) PRACTICE REQUIREMENTS; DISCLOSURE OF |
| | COMPENSATION FOR PROFESSIONAL SERVICES. |
| | |
| | 3D) THE CONSULTING STRUCTURAL ENGINEER NAIM& ASSOCIATES |
| | ARE THE ONLY STRUCTURAL ENGINEERING FIRM LISTED ON THE |
| | SHEET, NO INDIVIDUAL ENGINEER HAS SIGNED AND SEALED THE |
| | PLANS.FLORIDA |
| | ADMINISTRATIVE CODE 61G15-23.002(2) |
| | |
| | 3E) ) 61G15-23.002(2)FL. ADMIN. CODE. PLANS SIGNED & |
| | SEALED BY A PROFESSIONAL ENGINEER |
| | SHALL INCLUDE EITHER: |
| | - THE NAME,ADDRESS AND LICENSE NUMBER OF THE ENGINEER |
| | OR, |
| | - THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE |
| | NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER |
| | OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER |
| | IS PRACTICING |
| | (471.025 F.S. AND471.023 F.S.). |
| | |
| | 4)SECOND REQUEST, SHEET S-1 DOES NOT APPEAR IN THE |
| | INDEX SHEET. STRUCTURAL SHEET S-1 WILL REQUIRE A RAISED |
| | IMPRESSION TYPE SEAL NOT A STAMPED SEAL. FLORIDA |
| | ADMINISTRATIVE CODE 61G15-23.001, THE DESIGN |
| | PROFESSIONAL MUST BE A LICENSED ENGINEER IN THE STATE |
| | OF FLORIDA. FL S. S.471.025. THE RESPONSE INDICATES |
| | THAT THE STRUCTURAL SHEETS WILL HAVE A RAISED |
| | IMPRESSION SEAL BY A LICENSED ENGINEER IN FLORIDA BUT |
| | THIS SET OF PLANS THE CONSULTING STRUCTURAL ENGINEER |
| | NAIM& ASSOCIATES ARE THE ONLY STRUCTURAL ENGINEERING |
| | FIRM LISTED ON THE SHEET, NO INDIVIDUAL ENGINEER HAS |
| | SIGNED AND SEALED THE PLANS. |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.002(2).PLANS |
| | SIGNED & SEALED BY A PROFESSIONAL ENGINEER SHALL |
| | INCLUDE EITHER THE NAME, ADDRESS AND LICENSE NUMBER OF |
| | THE ENGINEER OR, THE NAME AND LICENSE NUMBER OF THE |
| | ENGINEER AND THE NAME, ADDRESS AND CERTIFICATE OF |
| | AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS |
| | THROUGH WHICH THE ENGINEER IS PRACTICING |
| | |
| | 5) SECOND REQUEST, THE SAME HOLDS TRUE FOR THE |
| | CALCULATIONS SUBMITTED FOR THE STAIRS BETWEEN THE 15TH |
| | & 16TH FLOOR. MUST BE A LICENSED ENGINEER FOR THE STATE |
| | OF FLORIDA AND IF THE ENGINEER OF RECORD DOES NOT SEAL |
| | EACH SHEET THEN A SEALED COVER SHEET LISTING HOW MANY |
| | PAGES ARE COVERED UNDER THIS SEAL. 61G15-23.002. |
| | |
| | 6) COMPLIED. |
| | |
| | 7A) LS-01 THERE IS A DISCREPANCY IN FLOOR AREA FROM THE |
| | LIFE SAFETY PLAN & THE ENERGY CALCS PLEASE CORRECT. |
| | |
| | 7B) LIFE SAFETY PLANS HAVE THE WRONG WIND CRITERIA |
| | PLEASE CORRECT THE REFERENCE TO ASCE 7-98. |
| | 8)COMPLIED. |
| | |
| | 9) COMPLIED. |
| | |
| | 10) SECOND REQUEST, SHEET 1-16C INDICATE TWO TYPE OF |
| | DOORS THAT WILL BE PENETRATING THE 1 HR RATED WALL DOOR |
| | TYPED-6 WHICH DOES HAVE 45 MINUTE RATING AND DOOR TYPE |
| | D-3 WHICH DOES NOT PLEASE CORRECT. TABLE 715.3. |
| | |
| | 11) SECOND REQUEST, RESPONSE INDICATES THE NOTE IS |
| | ADDED TO THE GENERAL NOTES NOT NUMBER 58, SHEET I-G.1 |
| | THE GENERAL NOTES ONLY GO UP TO 44.PLEASE TAKE NOTE |
| | OF : 404.7 INTERIOR FINISH. THE INTERIOR FINISH OF |
| | WALLS AND CEILINGS OF THE ATRIUM SHALL NOT BE LESS THAN |
| | CLASS B WITH NO REDUCTION IN CLASS FOR SPRINKLER |
| | PROTECTION. |
| | |
| | 12) COMPLIED. |
| | |
| | 13-15) COMPLIED. |
| | |
| | 16) 2ND REQUEST, A FLORIDA REGISTERED ENGINEER, |
| | PLEASE PROVIDE ADDITIONAL INFORMATION ON THE GLASS |
| | HANDRAILS AND GUARDS SEE 2407. |
| | 2407.1.1 LOADS. |
| | THE PANELS AND THEIR SUPPORT SYSTEM SHALL BE DESIGNED |
| | TO WITHSTAND THE LOADS SPECIFIED IN SECTION 1607.7 . A |
| | SAFETY FACTOR OF FOUR SHALL BE USED. |
| | |
| | 2407.1.2 SUPPORT. |
| | EACH HANDRAIL OR GUARD SECTION SHALL BE SUPPORTED BY A |
| | MINIMUM OF THREE GLASS BALUSTERS OR SHALL BE OTHERWISE |
| | SUPPORTED TO REMAIN IN PLACE SHOULD ONE BALUSTER PANEL |
| | FAIL. GLASS BALUSTERS SHALL NOT BE INSTALLED WITHOUT AN |
| | ATTACHED HANDRAIL OR GUARD. |
| | |
| | 17)COMPLIED. |
| | |
| | 18) SECOND REQUEST, THE RESPONSE SHEET INDICATES A NOTE |
| | 59 WAS ADDED TO THE GENERAL COMMENTS? THE GLASS WALL IS |
| | ALSO CONSIDERED A HAZARDOUS LOCATION 15TH AND 16TH |
| | FLOORS. SEE 2406.3(7) |
| | 7.GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE |
| | PANEL, OTHER THAN IN THOSE LOCATIONS DESCRIBED IN |
| | PRECEDING ITEMS 5 AND 6, WHICH MEETS ALL OF THE |
| | FOLLOWING CONDITIONS: |
| | 7.1.EXPOSED AREA OF AN INDIVIDUAL PANE GREATER |
| | THAN 9 SQUARE FEET (0.84 M 2 ); |
| | 7.2.EXPOSED BOTTOM EDGE LESS THAN 18 INCHES (457 |
| | MM) ABOVE THE FLOOR; |
| | 7.3.EXPOSED TOP EDGE GREATER THAN 36 INCHES (914 |
| | MM) ABOVE THE FLOOR; AND |
| | 7.4.ONE OR MORE WALKING SURFACE(S) WITHIN 36 |
| | INCHES (914 MM) HORIZONTALLY OF THE PLANE OF THE |
| | GLAZING. |
| | EXCEPTION: SAFETY GLAZING FOR ITEM 7 IS NOT REQUIRED |
| | FOR THE FOLLOWING INSTALLATIONS: |
| | 1.A PROTECTIVE BAR 1? INCHES (38 MM) OR MORE IN |
| | HEIGHT, CAPABLE OF WITHSTANDING A HORIZONTAL LOAD OF 50 |
| | POUNDS PLF (730 N/M) WITHOUT CONTACTING THE GLASS, IS |
| | INSTALLED ON THE ACCESSIBLE SIDES OF THE GLAZING 34 |
| | INCHES TO 38 INCHES (864 MM TO 965 MM) ABOVE THE |
| | FLOOR. |
| | |
| | 19-23B) COMPLIED. |
| | |
| | 24) A NEW COMMENT, E2.1 INDICATES WORK BEING COMPLETED |
| | ON THE 17TH FLOOR AND E2.2 INDICATES THE 16TH FLOOR, |
| | PLEASE CORRECT THIS DISCREPANCY. |
| | |
| | 25) A NEW COMMENT,I-15.C ROOMS 1543& 1544 BOTH ARE |
| | INDICATED AS COMPUTER EQUIPMENT ROOMS SEE ELECTRICAL |
| | COMMENTS AS TO THE 1 HR FIRE RATING REQUIREMENTS. |
| | |
| | 26) ENERGY CALCULATIONS PLEASE PROVIDE THE INFORMATION |
| | FOR THE SKYLIGHTS TO BE INSTALLED ON THE |
| | ROOF OF THE 16TH FLOOR. ADDITIONAL INFORMATION REQUIRED |
| | 106.1.2* |
| | 27) SHEET I-15.R PLEASE CORRECT THIS SHEET TITLE BLOCK |
| | IT APPEARS WHITE OUT WAS USED IN THE TITLE BLOCK AND |
| | THEN HAND DRAWN NUMERALS. |
| | |
| | 28) SHEETS S-1 AND S-2 INDICATE NEW STAIRS AND FLOOR |
| | BEAMS COMMUNICATING BETWEEN THE FLOORS, AS PART OF A |
| | THRESHOLD BUILDING THE FOLLOWING ITEMS WILL NEED TO BE |
| | ADDRESSED: |
| | |
| | 28A)105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A |
| | SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON |
| | A THRESHOLD BUILDING PURSUANT TO A "STRUCTURAL |
| | INSPECTION PLAN" |
| | PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | 28B) THE SHELL BUILDING HAS NOT ACHIEVED A CERTIFICATE |
| | OF COMPLETION, THE STRUCTURAL PLANS FOR THIS TENANT |
| | SPACE SHALL BE REVIEWED BY THE ENGINEER OF RECORD FOR |
| | THE " BASE BUILDING" |
| | AND BE STAMPED WITH THEIR SHOP DRAWING STAMP THEY ARE |
| | APPROVING THE PLANS AND WORK TO BE COMPLETED UNDER THIS |
| | PERMIT BEFORE THEIR CERTIFICATE OF COMPLETION HAS BEEN |
| | ISSUED. |
| | |
| | 28C) THE SAME HOLDS TRUE FOR THE ARCHITECTURAL SHEETS, |
| | THE DESIGNER OF RECORD FOR THE BUILDING SHALL REVIEW |
| | AND AFFIX THEIR SHOP DRAWING STAMP TO THESE PLANS WITH |
| | THEIR APPROVAL. |
| | |
| | 28D) SINCE THERE WILL NEED TO BE A THRESHOLD INSPECTOR |
| | ON SITE, A THIRD SET OF PLANS, SUBMITTALS AND OR OTHER |
| | DOCUMENTS WILL NEED TO BE SUBMITTED BEFORE ISSUANCE OF |
| | THIS PERMIT. |
| | |
| | 28E) SINCE THE STEEL BEAMS ARE NEW ELEMENTS AND NEED TO |
| | INDICATE FIRE PROOFING AS TO TABLE 601 FLOOR AND BEAM 3 |
| | HR RATING SEE FOOTNOTE "G" 1 HR REDUCTION FOR FIRE |
| | SPRINKLED BUILDINGS. |
| | PLEASE SHOW COMPLIANCE. |
| | |
| | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| | REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE |
| | APPLICABLE. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | |
| | |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |