Plan Review Notes
Plan Review Notes For Permit 07030932
Permit Number 07030932
Review Stop E
Sequence Number 10
Notes
Date Text
2008-07-31 11:57:16** DENIED**
  
  
 REV #13
  
 1) NOTE: PLEASE SEE COMMENTS FROM PREVIOUS REVIEW WHICH
 ARE STILL IN NEED OF ADDRESSING.
  
 2) NOTE: PLEASE SUBMIT REVISED PLANS WITH REVISED PANEL
 SCHEDULES AS THE NEW CIRCUITS AND REVISED CIRCUITS ON
 PLANS DO NOT COORDINATE WITH THE RECORD SET OF PLANS ON
 FILE.
 408.4, ETC
 FBC 106.5, 106.1.1
  
 3) NOTE: PLEASE REVISE SYMBOL LEGEND ON PLANS WITH NEW
 ITEMS NOW ADDED.
 FBC 106.1.1,
  
  
 ** IF THERE ARE ANY QUESTIONS OR IF THE COMMENTS ARE
 NOT CLEAR IN ANY MANOR PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]