Plan Review Notes
Plan Review Notes For Permit 07030932
Permit Number 07030932
Review Stop P
Sequence Number 1
Notes
Date Text
2007-05-14 11:38:30DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS. THE BUSINESS NUMBER FOR "YJ
 ARCHITECTURAL DESIGN" IS REQUIRED IN THE TITLE BLOCK.
 FAC 61G1-16.004(2) & FS 481.219, 481.2055.
  
 2. SHT 1-16.C PER TABLE 403.1 3 DRINKING FOUNTAINS ARE
 REQUIRED. PLEASE INDICATE THE LOCATION OF EACH DRINKING
 FOUNTAIN.
  
 3. SHT 1-16.C BATHROOM (1608) SHALL BE ACCESSIBLE OR
 ADAPTABLE PER SECTIONS 11-4.22 OR 11-4.1.3(11). PLEASE
 SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTIONS
 11-4.16, 11-4.19 & 11-4.21 WITH ALL SUBSECTIONS IF
 BATHROOM IS TO BE ACCESSIBLE. SUBMIT A DETAIL SHOWING
 ALL BACKING FOR GRAB BARS FOR THE W/C & SHOWER, SPACING
 FOR THE W/C, (MIN. 33" WITH THE W/C BEING 18" OFF THE
 WALL AND MIN. 15" OFF THE SHOWER), A TURNING AREA IN
 THE BATHROOM, THE VALVE LOCATION FOR THE SHOWER, AND A
 CURB DETAIL OF THE SHOWER, (MAX 1/2").
  
 4. SHT 1-16.C THE SINKS IN ROOMS 1613, 1628, 1633, 1643
 & 1656 SHALL BE ACCESSIBLE. PLEASE SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS.
  
 5. SHT 1-16.C MORE INFORMATION IS REQUIRED FOR THE
 PLANTERS. PLEASE INDICATE IF THE PLANTERS WILL HAVE
 WATER SUPPLY OR DRAINAGE CONNECTED TO THEM. SECTION
 106.1.2. IF SO THE DRAINAGE PIPING & SUPPLY PIPING
 SHALL BE SHOWN ON THE FLOOR PLANS AND ON THE RISER
 DIAGRAMS. SECTION 106.3.5.1.3.
  
 6. SHT1-16.C PER TABLES 1004.1.2 AND 403.1 4 WATER
 CLOSETS ARE REQUIRED FOR BOTH THE MEN'S AND WOMEN'S
 TOILET ROOMS.
  
 7. SHT 1-16.C ROOMS 1613 & 1628. PLEASE INDICATE THE
 FIXTURE TYPE, (BS), IN EACH ROOM. SECTION 106.1.2.
  
 8. SUBMIT DETAILS FOR THE MEN'S & WOMEN'S TOILET ROOMS
 SHOWING COMPLIANCE WITH SECTIONS 11-4.16, 11-4.17,
 11-4.18, 11-4.19 & 11-4.22 WITH ALL SUBSECTIONS.
  
 9. SUBMIT A DETAIL FOR THE ACCESSIBLE DRINKING
 FOUNTAINS. SHOW COMPLIANCE WITH SECTION 11-4.15 WILL
 ALL SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
  
 10. SHT 1-15.C PER TABLE 403.1 3 DRINKING FOUNTAINS ARE
 REQUIRED. PLEASE INDICATE THE LOCATION OF EACH DRINKING
 FOUNTAIN.
  
 11. SHT 1-15.C PER TABLES 1004.1.2 AND 403.1 4 WATER
 CLOSETS ARE REQUIRED FOR BOTH THE MEN'S AND WOMEN'S
 TOILET ROOMS.
  
 12. SHT 1-15.C THE SINK IN ROOM 1520SHALL BE
 ACCESSIBLE. PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE
 WITH SECTION 11-4.24 AND ALL SUBSECTIONS.
  
 13. SHT S-1 SHALL BE SEALED WITH AN EMBOSSED OR
 IMPRESSION TYPE SEAL. NAIM & ASSOCIATES SHALL INDICATE
 THEIR BUSINESS NUMBER, (CERTIFICATE OF AUTHORIZATION),
 IN THE TITLE BLOCK. A PROFESSIONAL ENGINEER SHALL SIGN
 HIS NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID DOCUMENTS
 PROVIDED TO THE OWNER OR THE OWNER'S REPRESENTATIVE, OR
 OTHER DOCUMENTS PREPARED OR ISSUED BY SAID REGISTRANT
 AND BEING FILED FOR PUBLIC RECORD. THE DATE THAT THE
 SIGNATURE AND SEAL IS AFFIXED AS PROVIDED HEREIN SHALL
 BE ENTERED ON SAID PLANS, SPECIFICATIONS, REPORTS, OR
 OTHER DOCUMENTS IMMEDIATELY UNDER THE SIGNATURE OF THE
 PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1) FS 471.025. ENGINEERS
 SHALL LEGIBLY INDICATE THEIR NAME, ADDRESS AND LICENSE
 NUMBER ON EACH SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGINEERS, ENGINEERS
 SHALL LEGIBLY INDICATE THEIR NAME AND LICENSE NUMBER,
 AS WELL AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS ON
 EACH SHEET. A TITLE BLOCK WILL SATISFY THIS
 REQUIREMENT. (THE CERTIFICATE OF AUTHORIZATION IS NOT
 INDICATED IN THE TITLE BLOCK).FAC 61G15-23.002(2) -
 FS 471.025.--PLANS APPEAR TO BE SIGNED WITH
 INITIALS. INITIALS ARE NOT APPROVED, THE LEGAL
 SIGNATURE IS REQUIRED. IF INDEED THIS IS THE LEGAL
 SIGNATURE, A SIGNED, SEALED, NOTORIZED LETTER SHALL BE
 SUBMITTED INDICATING THE LEGAL SIGNATURE FOR OUR
 FILES.
  
 14. SHT P2.1 SOME ROOM NUMBERS ON THE PLUMBING SHEETS
 DO NOT REFLECT THE ROOM NUMBERS ON THE ARCHITECTURAL
 SHEETS. (EXAMPLE - 1565(P)/1576(A), 1568(P)/1538(A),
 1538(P)/1539(A) ETC). PLEASE CORRELATE THE INFORMATION
 ON THE PLUMBING SHEETS WITH THE INFORMATION ON THE
 ARCHITECTURAL SHEETS. SECTION 106.1.1.
  
 15. SHT P2.1 PLEASE INDICATE THE USE OF THE FLOOR DRAIN
 IN ROOM 31565(P). PLEASE INDICATE WHAT WILL BE DRAINING
 INTO THE FLOOR DRAIN. SECTION 106.1.2.
  
 16. SHT P2.1 LAVS ARE REQUIRED IN THE ACCESSIBLE STALLS
 OF THE MEN'S AND WOMEN'S TOILET ROOMS. FIGURE 11-30E.
  
 17. SHT P2.1 INDICATE THE LOCATION OF THE 3 REQUIRED
 DRINKING FOUNTAINS. SECTION 106.1.2 & TABLE 403.1.
  
 18. SHT P2.2 PLAN INDICATED AT THE 18TH FLOOR. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 19. SHT P2.2 STUDOR VENTS ARE NOT APPROVED FOR THE
 PUMPS AT THE SINKS IN ROOMS 1613, 1628, 1633 & 1650,
 (SHOWN AS ROOM # 1643 ON SHT 1-16.C). SECTION 917.2.
  
 20. SHT P2.2 LAVS ARE REQUIRED IN THE ACCESSIBLE STALLS
 FOR THE MEN'S & WOMEN'S TOILET ROOMS. FIGURE 30E.
  
 21. SHT P2.2 NOTE INDICATES PLUMBING FIXTURE SCHEDULE
 PROVIDED BY THE ARCHITECT. NO FIXTURE SCHEDULE HAS BEEN
 LOCATED, AND NOTHING TO INDICATED WHAT FIXTURE "BS"
 REPRESENTS.( SEE ROOMS 1613 & 1628).PLEASE INDICATE
 WHERE THE FIXTURE SCHEDULE CAN BE FOUND. SECTION
 106.1.2.
  
 22. SHT P3.1 LAVS ARE REQUIRED IN THE ACCESSIBLE STALLS
 FOR THE MEN'S & WOMEN'S TOILET ROOMS. FIGURE 30E.
  
 23. SHT P3.1 PLEASE INDICATE WHAT THE COLD WATER LINE
 TO ROOM 1544 CONNECTS TO. PER SECTION 608, BACKFLOW
 PROTECTION MAY BE REQUIRED.
  
 24. SHT P3.2 PLAN INDICATED AT THE 18TH FLOOR. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 25. SHT P3.2 BACKFLOW PREVENTION IS REQUIRED ON THE
 COLD WATER SUPPLY TO THE WATER WALL. PLEASE INDICATE
 METHOD. SECTION 608.
  
 26. SHT P3.2 LAVS ARE REQUIRED IN THE ACCESSIBLE STALLS
 FOR THE MEN'S & WOMEN'S TOILET ROOMS. FIGURE 30E.
  
 27. SHT P51 DOMESTIC WATER ISOMETRIC RISER DIAGRAM. THE
 WATER HAMMER ARRESTORS SHALL BE LOCATED NEAR THE
 FIXTURE IN AN "EFFECTIVE RANGE" NOT IN THE CEILING AS
 SHOWN IN SOME AREAS. PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS.--A WATER HAMMER ARRESTOR IS REQUIRED
 FOR THE ICE MAKER BY THE WATER HEATER ON THE 16TH
 FLOOR. SECTION 604.9.
  
 28. SHT P51 LAVS ARE REQUIRED IN THE ACCESSIBLE STALLS
 FOR THE MEN'S & WOMEN'S TOILET ROOMS. FIGURE 30E.
 PLEASE SHOW LAVS ON THE FLOOR PLAN AND SHOW PIPING ON
 THE ISOMETRICS. SECTION 106.1.2.
  
 29. SHT P51 THERMAL EXPANSION CONTROL IS REQUIRED FOR
 THE WATER HEATERS ON THE 15TH & 16TH FLOORS. PLEASE
 INDICATE THE METHOD OF CONTROL. SECTION 607.3.2.
  
 30. SHT P51 DOMESTIC WATER ISOMETRIC RISER DIAGRAM 16TH
 FLOOR DOES NOT REFLECT THE FLOOR PLAN BY THE MOP
 SINK/WATER HEATER & TO THE REF. IN ROOM 1633. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 31. SHT P51 16TH FLOOR SANITARY ISOMETRIC RISER DIAGRAM
 SHOWS STUDOR VENTS (AAV'S) AT THE PUMPS FOR THE KITCHEN
 SINKS AND AT THE "BS" FIXTURES. THESE ARE NOT APPROVED
 PER SECTION 917.2. THESE PUMP VENTS SHALL BE CONNECTED
 TO THE VENT SYSTEMS.--TRAPS ARE REQUIRED FOR ALL
 THE KITCHEN SINKS AND "BS" FIXTURES. SECTION 1002.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  