Plan Review Notes
Plan Review Notes For Permit 07030932
Permit Number 07030932
Review Stop M
Sequence Number 1
Notes
Date Text
2007-04-25 09:26:22--------------DENIED------------------
  
 FBC 2004 CODE FAMILY W/2006 REVISIONS
 FBC CH 1 AS AMENDED BY THE CITY OF WEST PALM BEACH NFPA
 90A-02
  
 1. M2.1 NOTE #9: NOTE CALLS FOR 12X12 EXHAUST DUCT,
 PLAN SHOWS 10X10 DUCT FROM SHAFT TO LUNCH ROOM. PLEASE
 COORDINATE NOTES AND PLANS. FBC 106.1.1
  
 2. M2.1 NOTE #9: FIRE AND SMOKE DAMPERS ARE REQUIRED
 WHERE EF 9 DUCT PENETRATES RATED SHAFT ON 15TH AND 16TH
 FLOORS. FBC,M 607.5.5.1
  
 3. M2.1: WHAT IS THE PURPOSE OF THE TWO RAFD'S IN THE
 WALL BETWEEN ROOMS 1542 AND 1544? THIS WALL IS SHOWN ON
 SHEET I-15.C AS A TYPE "B" WHICH IS NON-RATED AND ONLY
 EXTENDS 6" ABOVE THE CEILING. PLEASE CLARIFY AND
 COORDINATE WITH ARCHITECTURAL PLANS.
  
 4. I-15.C: VARIOUS WALL TYPES SHOW DRYWALL STOPPING 6"
 ABOVE CEILING WITH INSULATION CONTINUING TO UNDERSIDE
 OF DECK. THIS CONDITION WOULD RESTRICT THE FREE FLOW O
 RETURN AIR BACK TO AIR HANDLING EQUIPMENT, PREVENTING
 BALANCED RETURN AS REQUIRED BY FBC,M 601.4. ALSO, TOPS
 OF OPEN WALL CAVITIES EXPOSED TO PLENUM AREA SHALL BE
 SEALED BY AN APPROVED AIR BARRIER PER FBC,M 603.8.
  
 5. M2.1: VAV 15-10 SHOWS 700 CFM ON FLOOR PLAN, BUT
 SCHEDULE ON M6.1 SHOWS 1250 CFM REQUIRED. WHICH IS
 CORRECT? PLEASE CLARIFY. FBC 106.1.1
  
 6. AHU 1,2 AND RTU 1,2: PLEASE SHOW MEANS AND LOCATION
 OF CONDENSATE DISPOSAL ALONG WITH MEANS OF AUXILIARY
 DRAIN PROTECTION. FBC,M 307.1 THROUGH 307.4.
 NOTE: A/C CONDENSATE SHALL NOT DISCHARGE INTO CITY
 WASTE WATER PIPING PER MUNICIPAL CODE SEC 90-125(B)(5)
  
 7. PLEASE PROVIDE INSTALLATION/HANGING DETAIL FOR AHU 1
 & 2.
  
 8. M2.1 KEY NOTE #5: NO DETAIL COULD BE FOUND REGARDING
 OFFSET OF RATED WALLS ABOVE CEILING FOR FIRE DAMPERS.
 THE FIRE DAMPERS IN QUESTION APPEAR TO BE QUITE DISTANT
 FROM THE LOCATION OF THE RATED WALLS.
  
 9. M2.1: FIRE DAMPER IS NOT SHOWN IN 54X12 DUCT PASSING
 THROUGH RATED WALL BETWEEN ROOM 1551 AND 1553. PLEASE
 SHOW MEANS OF COMPLIANCE WITH FBC,M 607.5.
  
 10. M2.2: FIRE DAMPERS ARE SHOWN TO BE INSTALLED IN
 NON-RATED PARTITIONS BASED ON WALL TYPES AS SHOWN ON
 SHEET I-16.C. SOME FIRE DAMPER ARE SHOWN WHERE NO
 PARTITION OF ANY KIND EXISTS ON ARCHITECTURAL PLANS,
 SUCH AS THE RAFD IN LOBBY 1601. PLEASE COORDINATE
 ARCHITECTURAL AND MECHANICAL PLANS BY DETERMINING WHERE
 FIRE-RATED PARTITIONS ARE TO BE LOCATED (WHETHER
 REQUIRED BY CODE OR DESIGN) AND SHOW FIRE DAMPERS TO BE
 AT THE APPROPRIATE LOCATIONS AS NEEDED. A COMPLETE
 REVIEW IS NOT POSSIBLE AT THIS TIME AND WILL BE
 COMPLETED ONCE THESE DISCREPANCIES ARE ADDRESSED.
  
 11. M2.2 KEY NOTE #6: NO SECTION DETAIL COULD BE
 LOCATED RELATED TO SUPPLY PLENUMS OR DIFFUSERS IN THIS
 AREA.
  
 12. M2.1 AND 2.2 ELEVATOR LOBBIES: PLEASE INDICATE ON
 ARCHITECTURAL PLANS WHICH WALL TYPE IS TO BE USED AT
 LOBBY DOORS TO ENSURE PROPER RETURN AIR FLOW FROM LOBBY
 CEILINGS.
 NOTE: BUILDING CAVITIES USED AS RETURN AIR PLENUMS
 SHALL BE LINED WITH A CONTINUOUS AIR BARRIER MADE OF
 DURABLE NON-POROUS MATERIALS PER FBC,M 603.8. APPROVED
 AIR BARRIERS ARE TO BE AS DEFINED BY FBC,M 603.9.1.
 THIS APPLIES TO ALL CONCRETE BLOCK WALLS AND EXTERIOR
 WALLS EXCEPT THOSE BETWEEN THE MECHANICAL ROOM AND THE
 CONDITIONED SPACE.
  
 13. M2.2 VAV 16-12: 12X10 BRANCH DUCT TAP IS SHOWN IN A
 DIRECTION CONTRARY TO AIRFLOW. PLEASE CORRECT. FBC,M
 603.3
  
 14. M2.2 VAV 16-13: SCHEDULE CALLS FOR REQUIRED 1400
 CFM SUPPLY. FLOOR PLAN SHOWS 1350 CFM. WHICH IS
 CORRECT?
  
 15. M2.2 EF-10: EXHAUST DUCTS UNDER POSITIVE PRESSURE
 SHALL NOT PASS THROUGH DUCTS OR PLENUMS PER FBC,M
 601.3.
  
 16. M2.2 VAV 16-17: SCHEDULE CALLS FOR REQUIRED 1950
 CFM SUPPLY. FLOOR PLAN SHOWS 2000 CFM SUPPLY. WHICH IS
 CORRECT?
  
 17. M2.2: RETURN AIR INTAKE ON SOUTH SIDE OF MECHANICAL
 ROOM SHOWS TWO DUCT SMOKE DETECTORS. ARE BOTH TO BE
 INSTALLED? PLEASE CLARIFY. FBC 106.1.1
  
 18. M0.1 NOTE #23: NO INFORMATION REGARDING WIND LOADS
 FOR OUTDOOR EQUIPMENT COULD BE FOUND FROM ARCHITECT OR
 STRUCTURAL ENGINEER.
  
 19. 15TH AND 16TH FLOOR CEILING AREA TO BE USED AS
 RETURN AIR PLENUMS. PLEASE VERIFY THAT EXISTING ROOF IS
 INSULATED TO MIN. R-19 AND EXTERIOR WALL SECTIONS
 EXPOSED TO PLENUM ARE INSULATED PER FBC TABLE
 13-410.1.ABC.2.2 IN ACCORDANCE WITH FBC,M 603.8.
  
 20. ENERGY CALCULATIONS:
 A) CALCULATIONS APPEAR TO BE FOR ONLY THE 16TH FLOOR.
 PLEASE ADJUST TO INCLUDE CALCULATIONS FOR ENTIRE
 PROJECT.
 B) SCHEDULE ON M6.2 SHOWS 2500 CFM OUTDOOR AIR PER
 FLOOR. ENERGY CALCS FOR 16TH FL ONLY SHOWS 2040. PLEASE
 ADJUST CALCULATIONS TO SHOW ACTUAL VALUE.
 C) AIR SYSTEM SIZING: PAC-16 IS A CHILLED WATER AHU OR
 A WATER COOLED PACKAGE UNIT? PLEASE CONFIRM WITH
 EXISTING BUILDING CONDITIONS
  
 REVIEWED BY:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]