| 2007-06-05 11:01:41 | *****DENIED***** |
| | |
| | |
| | 01.IN ADDITION TO THE 2003 EDITION OF NFPA 101, THE |
| | FLORIDA FIRE PREVENTION CODE (2004 EDITION) SHALL BE |
| | REFERENCED. |
| | |
| | 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 03.ACCUMULATIONS OF COMBUSTIBLE WASTE MATERIALS, |
| | DUST, AND DEBRIS SHALL BE REMOVED FROM THE SITE AT THE |
| | END OF EACH OF SHIFT OR MORE FREQUENTLY AS NECESSARY |
| | FOR SAFE OPERATION. |
| | |
| | 04.THE SCOPE OF WORK (ON THE 15TH AND 16TH FLOORS) |
| | SHALL NOT INTERFERE OR HINDER ACCESS TO OR EGRESS FROM |
| | OTHER FLOORS AND/OR AREAS OF THE BUILDING. |
| | |
| | 05.DOORS LEADING DIRECTLY TO THE CORRIDORS SHALL BE |
| | AN APPROVED, LISTED, AND LABELED FIRE DOOR AND ASSEMBLY |
| | IN ACCORDANCE WITH NFPA 80. |
| | |
| | 06.SPECITY THE INTERIOR FINISH CLASSIFICATION FOR THE |
| | WALLS AND CEILINGS IN THE EXITS, EXIT ACCESS CORRIDORS, |
| | AND ALL OTHER SPACES IN TERMS OF CLASS A, CLASS B, OR |
| | CLASS C. |
| | |
| | 07.ON SHEETI-G-1, GENERAL NOTE 13, PLEASE EXPLAIN |
| | THE REFERENCE TO THE CITY OF LOS ANGELES DEPARTMENT OF |
| | BUILDING AND SAFETY. |
| | |
| | 08.ON SHEETE0.1 UNDER ELECTRICAL SPECIFICATIONS, |
| | PART 1 -SECTION C,THE 2003 EDITION OF NFPA 101 SHALL |
| | BE REFERENCED. |
| | |
| | 09.ON SHEET E2.1, THE DESCRIPTION IS FOR THE 17TH |
| | FLOOR.PER YOUR APPLICATION, THE SCOPE OF WORK IS FOR |
| | THE 15TH AND 16TH FLOOR. |
| | |
| | 10.AS PER WEST PALM BEACH FIRE PREVENTION, DUCT SMOKE |
| | DETECTORS SHALL ACTIVATE A GENERAL FIRE ALARM.AMEND |
| | FIRE ALARM NOTE #17 ON SHEET FA0.1. |
| | |
| | 11.TWO (OF THE FOUR) SPECIFICATION/DETAIL SHEETS ARE |
| | NOT LEGIBLE ENOUGH FOR REVIEW. |
| | |
| | 12.ON SHEET FS2.1 (15TH FLOOR FIRE SPRINKLER PLAN) IS |
| | DESCRIBED IN THE TITLE BLOCK AS THE 17TH FLOOR. |
| | |
| | 13.ON SHEET FS2.2(16TH FLOOR FIRE SPRINKLER PLAN) |
| | IS DESCRIBED IN THE TITLE BLOCK AS THE 18TH FLOOR. |
| | |
| | 14.SHEET FS2.2 IS DESCRIBED IN THE TITLE BLOCK AS THE |
| | 18TH FLOOR. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |