| 2007-04-19 16:09:15 | ** UNSAT ** |
| | |
| | ** PLEASE SEE ANY REFERENCES TO THE FBC CHAPTER 1 ARE |
| | THE ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY OF |
| | WEST PALM BEACH. |
| | |
| | ** PLEASE KNOW THAT SOME OF THE PRELIMINARY COMMENTS |
| | BELOW DO NOT APPLY TO KAMM CONSULTING ENGINEERS. |
| | |
| | 1) NOTE: PLEASE SEE THE FOLLOWING ADOPTED CODES SHOULD |
| | BE STATED ON PLANS AS THE STATE ADOPTED NEW CODES AS OF |
| | DECEMBER 8TH, 2006. |
| | PLEASE SEE THE WRONG NEC WAS STATED. |
| | 2004 FBC W/2006 REVISIONS, |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72. |
| | SOME OF THESE ARE STATED ON THE FRONT ARCHITECTURAL |
| | SHEETS AND SOME ARE NOT. PLEASE ALSO INCLUDE THE STATED |
| | CODE ON THE ELECTRICAL PLANS. |
| | ** PLEASE KNOW THAT ANY OTHER CODES WHICH MAY BE STATED |
| | FROM OTHER TRADES SHOULD BE NOTED BY OTHER TRADES. |
| | |
| | 2) NOTE: PLEASE SEE MISSING LICENSE INFORMATION FOR THE |
| | YJ DESIGN, PER FLORIDA STATUTES 481.221/471.023 PLEASE |
| | SEE FAC WHICH REQUIRES ALL INFORMATION ON TITLE BLOCKS |
| | FOR SAID FIRM PER 61G1-16.004. |
| | *THIS IS REQUIRED FOR ALL TRADES AND FOR ALL SHEETS |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES. |
| | |
| | 3) NOTE: PLEASE SEE *S* SHEETS WHICH CONTAIN A *RUBBER |
| | STAMP* BY THE ENGINEERWHICH IS REQUIRED TO BE AN |
| | RAISED IMPRESSION TYPE SEAL IN THE STATE OF FLORIDA PER |
| | FAC61G15-23.001. |
| | PLEASE ALSO SEE THE SEAL WHICH IS FROM THE STATE OF |
| | CALIFORNIA. THIS MUST BE LICENSED IN THE STATE OF |
| | FLORIDA. |
| | PLEASE ALSO SEE MISSING INFORMATION REQUIRED IN TITLE |
| | BLOCKS FOR FIRM LICENSE NUMBER ALSO KNOW AS THE |
| | CERTIFICATE OF AUTHORIZATION NUMBER, THE PRINTED NAME |
| | AND LICENSE NUMBER OF DESIGNER OF RECORD. |
| | ** THIS IS REQUIRED FOR ALL SHEETS AND DOCUMENTS DONE |
| | BY THIS ENGINEER WHETHER OR NOT COMMENT IS MADE BY |
| | OTHER TRADES. |
| | |
| | 4) NOTE: PLEASE SEE FBC 2004 W/ 2006 REVISIONS FOR |
| | CHAPTER 13. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3., |
| | 13-415.1.AB.1, 13-415.2, 13-415.2.ABC.1.2 |
| | PLEASE SEE SEVERAL AREAS WHICH ARE MISSING THE REQUIRED |
| | OVER RIDE DEVICES, OR OTHER TYPE DEVICES REQUIRED FOR |
| | CONTROL OF LIGHTING. |
| | PLEASE SEE SEVERAL LOCATIONS WHICH LIGHTING CONTROL IS |
| | REQUIRED FOR AREAS IN WHICH THE OCCUPANT CAN SEE THE |
| | LIGHTING WHICH IS BEING CONTROLLED. |
| | PLEASE SEE THE NORTH-SIDE ENTRANCE INTO THE 15TH FLOOR |
| | WHICH SHOWS NO CONTROL. |
| | PLEASE SEE THE SOUTH-SIDE ENTRANCE ON THE 16TH FLOOR |
| | WHICH SHOWS NO CONTROL. |
| | PLEASE SEE SEVERAL ROOMS WHICH CONTAIN ONLY A STANDARD |
| | WALL SWITCH. |
| | PLEASE SEE THE DETAIL FOR EACH CONTROL PANEL DOES NOT |
| | PROVIDE ENOUGH DETAILS FOR PROPOSED SYSTEM AND OVER |
| | RIDES. |
| | PLEASE SEE THAT NO MAXIMUM TIMES FOR OVER RIDES ARE |
| | STATED ON LEGEND. |
| | PLEASE SEE THAT NO CONTROLS ARE SHOWN FOR NUMEROUS |
| | LOCATIONS OF ACCENT LIGHTING. |
| | PLEASE SEE THAT THE CIRCUITING SHOWN ON THE LIGHTING |
| | CONTROL PANELS DO NOT CORRELATE WITH THE PLANS AS THERE |
| | ARE SEVERAL LIGHTING CIRCUITS ON PLANS NOT ON THE LCP. |
| | PLEASE SEE THAT THE LIGHTING WHICH IS BEING SHOWN UNDER |
| | A SEPARATE VOLTAGE OTHER THAN THE 277/480V WILL BE |
| | REQUIRED TO BE UNDER SEPARATE SYSTEM YET TO BE SHOWN. |
| | PLEASE SEE THAT THE LIGHTING SHOWN ON PLANS DO NOT |
| | CORRELATE WITH THE SUBMITTED ENERGY CALCULATIONS |
| | SUBMITTED FOR THE NUMBER OF FIXTURES, THE TYPE OF |
| | FIXTURES, THE WATTAGE ON THE FIXTURES ETC. THERE WERE |
| | ONLY TWO TYPES OF FIXTURES ON THE ENERGY CALCULATIONS |
| | SUBMITTED WHEN THERE IS AS MANY AS 20+ DIFFERENT TYPES |
| | OF FIXTURES? |
| | PLEASE INDICATE THE ZONES WHERE APPLICABLE. |
| | PLEASE SEE THE SQUARE FOOT LIMITS. PLEASE SEE THE |
| | ENERGY CALCULATIONS INDICATE A TOTAL OF 21,425 SQ. FT |
| | AND THE PLANS INDICATE A TOTAL OF 25,157 SQ FT PER |
| | FLOOR. PLEASE COORDINATE PLANS AND CALCULATIONS. PLEASE |
| | SEE BATHROOMS DO NOT PROVIDE DEVICES FOR SAFE COVERAGE |
| | FOR CONTROL OF LIGHTING. |
| | |
| | ** PLEASE KNOW THAT DUE TO NUMEROUS ITEMS FOR CHAPTER |
| | 13 COMPLIANCE, A FULL REVIEW OF ALL SYSTEMS AND DEVICES |
| | CAN NOT BE DONE AT THIS TIME. |
| | |
| | 5) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS |
| | FOR THE IT ROOM EQUIPMENT. |
| | PLEASE SEE MISSING DISCONNECTING MEANS FOR POWER OF ALL |
| | PER 645.10. |
| | PLEASE SUBMIT INFORMATION FOR THE TWO SYSTEMS WHICH |
| | APPEAR TO SHOW SOME SORT OF SHUNT TRIP BUT NOT SURE HOW |
| | THIS PROPOSED SYSTEM DEVICES ARE BEING INSTALLED TO |
| | PROVIDE THIS SHUNT OF ALL REQUIRED. |
| | **PLEASE SEE REVIEW COMMENTS FROM OTHER TRADES WHICH |
| | MAY AFFECT PLANS WITH RESPECT TO RATING OF WALLS, ROOM, |
| | ETC. PLEASE SEE NFPA-75 |
| | FBC 106.1.2, NEC 90.7, 110.3 |
| | |
| | 6) NOTE: PLEASE PROVIDE THE PHOTO-METRICS FOR STAIR |
| | AREAS ( NOT EXIT STAIR TOWERS) IN THE SPACE FROM 16TH |
| | FLOOR TO THE 15TH FLOOR. PLEASE SEE NFPA-101 7.8.1.3, |
| | 7.9.2.2. |
| | |
| | 7) NOTE: PLEASE SEE SHEET E2.1 WHICH INDICATES LIGHTING |
| | FOR FLOOR 17? THIS SEEMS TO BE A MISPRINT WHICH SHOULD |
| | READ 15TH FLOOR AS SHOWN ON PLANS. |
| | FBC 106.1.2 |
| | |
| | 8) NOTE: PLEASE PROVIDE ALL ROOM ARE AREA DESIGNATIONS |
| | ON PLANS AND COMPLETE PANEL SCHEDULES TO COORDINATE |
| | WITH THE NUMERICAL OR NAME DESIGNATIONS FOR THESE ROOMS |
| | AND AREAS. PLEASE SEE THE FOLLOWING TEXT WHICH IS |
| | EXTRACTED DIRECTLY FROM THE NEC 408.4. |
| | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO |
| | REQUIRE THAT THE IDENTIFICATION FOR EVERY CIRCUIT |
| | SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND |
| | CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE |
| | CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE |
| | MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE, |
| | SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN |
| | THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS. |
| | IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH |
| | CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE |
| | IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING |
| | ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP |
| | RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES |
| | CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR |
| | ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL |
| | REQUIRED BY THIS SECTION.* |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.3.5.4 |
| | |
| | 9) NOTE: PLEASE PROVIDE INFORMATION ON DOOR CLOSURES |
| | WHICH ARE REQUIRED TO MEET NFPA-101 7.2.1.5 |
| | |
| | 10) NOTE: PLEASE SUBMIT AND COMPLETE THE PANEL |
| | SCHEDULE(S) LOAD CALCULATIONS ON PLANS. PLEASE INCLUDE |
| | ALL CONTINUOUS LOADS AT 125%. PLEASE KNOW THAT ANY |
| | ELECTRICAL WATER HEATERS UNDER THE 2005 NEC ARE NOW |
| | ALSO REQUIRED TO BE SHOWN AT 125%. 422.13 |
| | 220.12, 220.14, 220.42, 220.44 ETC. |
| | PLEASE SEE SOME OF THE ELECTRICAL PANELS ARE BLANK AT |
| | THIS TIME, OR ONLY SOME LOADS ARE SHOWN ON PANELS. |
| | PLEASE COMPLETE. |
| | FBC 106.3.5.1.2 |
| | |
| | 11) NOTE: PLEASE PROVIDE GROUNDING ATTACHMENT AND |
| | CONDUCTOR SIZES FOR THE NEW TRANSFORMERS. |
| | 250.50, 250.66, 250.20,250.30 |
| | |
| | 12) NOTE: PLEASE SEE THE PLANS DO NOT INDICATE ANY |
| | SIZES FOR THESE NEW TRANSFORMER AND SEVERAL ITEMS TO |
| | REVIEW FOR ELECTRICAL CODE COMPLIANCE CAN NOT BE DONE |
| | AT THIS TIME. |
| | PLEASE COMPLETE. |
| | FBC 106.3.5.1.2 |
| | |
| | 13) NOTE: PLEASE SEE 422.17 FOR WATER HEATERS WHICH MAY |
| | NOT BE IN STORAGE ROOM LOCATIONS ALONG WITH |
| | COMBUSTIBLES AND EASILY IGNITABLE MATERIALS. PLEASE SEE |
| | THE CODE REQUIRES SEPARATION OF THESE ITEMS. PLEASE |
| | ADJUST PLANS ACCORDINGLY. |
| | |
| | 14) NOTE: PLEASE OBTAIN THE MOST RECENT REVISED RISER |
| | DIAGRAM FOR THE BASE BUILDING AS IT IS CURRENTLY SHOWN |
| | ON PLANS, DOES NOT MATCH. |
| | FBC 106.1.2 |
| | |
| | 15) NOTE: PLEASE INDICATE HOW THE CONDUCTORS ARE RUN, |
| | SIZED AND CONNECTED TO THE IT EQUIPMENT. |
| | PER 645.5 |
| | |
| | 16) NOTE: PLEASE INDICATE THE AIC RATINGS FOR ALL NEW |
| | ELECTRICAL SERVICE EQUIPMENT. |
| | 110.9, FBC 106.1.2 |
| | |
| | 17) NOTE: PLEASE CLARIFY THE KITCHEN AREA WHICH |
| | CONTAINS A *HOT/DISP* NOTE? WHAT IS THIS? |
| | FBC 106.1.2 |
| | |
| | 18) NOTE: PLEASE INDICATE IF THERE ARE ANY WATER |
| | HEATING UNITS FOR KITCHEN AREA ? |
| | |
| | 19) NOTE: PLEASE CLARIFY THE PANEL L16, AND L16C AS MCB |
| | PANELS. THIS IS PERMITTED HOWEVER NOT CLEAR? |
| | ONLY NOTED AS PLANS DO NOT NEED TO BE REVISED. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-04-19 10:48:46 | REVIEW COMMENCED ON 4/19 |
| 2007-04-15 20:09:01 | IN ELEC FOR REVIEW, |