Plan Review Notes
Plan Review Notes For Permit 07030932
Permit Number 07030932
Review Stop E
Sequence Number 1
Notes
Date Text
2007-04-19 16:09:15** UNSAT **
  
 ** PLEASE SEE ANY REFERENCES TO THE FBC CHAPTER 1 ARE
 THE ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY OF
 WEST PALM BEACH.
  
 ** PLEASE KNOW THAT SOME OF THE PRELIMINARY COMMENTS
 BELOW DO NOT APPLY TO KAMM CONSULTING ENGINEERS.
  
 1) NOTE: PLEASE SEE THE FOLLOWING ADOPTED CODES SHOULD
 BE STATED ON PLANS AS THE STATE ADOPTED NEW CODES AS OF
 DECEMBER 8TH, 2006.
 PLEASE SEE THE WRONG NEC WAS STATED.
 2004 FBC W/2006 REVISIONS,
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72.
 SOME OF THESE ARE STATED ON THE FRONT ARCHITECTURAL
 SHEETS AND SOME ARE NOT. PLEASE ALSO INCLUDE THE STATED
 CODE ON THE ELECTRICAL PLANS.
 ** PLEASE KNOW THAT ANY OTHER CODES WHICH MAY BE STATED
 FROM OTHER TRADES SHOULD BE NOTED BY OTHER TRADES.
  
 2) NOTE: PLEASE SEE MISSING LICENSE INFORMATION FOR THE
 YJ DESIGN, PER FLORIDA STATUTES 481.221/471.023 PLEASE
 SEE FAC WHICH REQUIRES ALL INFORMATION ON TITLE BLOCKS
 FOR SAID FIRM PER 61G1-16.004.
 *THIS IS REQUIRED FOR ALL TRADES AND FOR ALL SHEETS
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES.
  
 3) NOTE: PLEASE SEE *S* SHEETS WHICH CONTAIN A *RUBBER
 STAMP* BY THE ENGINEERWHICH IS REQUIRED TO BE AN
 RAISED IMPRESSION TYPE SEAL IN THE STATE OF FLORIDA PER
 FAC61G15-23.001.
 PLEASE ALSO SEE THE SEAL WHICH IS FROM THE STATE OF
 CALIFORNIA. THIS MUST BE LICENSED IN THE STATE OF
 FLORIDA.
 PLEASE ALSO SEE MISSING INFORMATION REQUIRED IN TITLE
 BLOCKS FOR FIRM LICENSE NUMBER ALSO KNOW AS THE
 CERTIFICATE OF AUTHORIZATION NUMBER, THE PRINTED NAME
 AND LICENSE NUMBER OF DESIGNER OF RECORD.
 ** THIS IS REQUIRED FOR ALL SHEETS AND DOCUMENTS DONE
 BY THIS ENGINEER WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES.
  
 4) NOTE: PLEASE SEE FBC 2004 W/ 2006 REVISIONS FOR
 CHAPTER 13.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.,
 13-415.1.AB.1, 13-415.2, 13-415.2.ABC.1.2
 PLEASE SEE SEVERAL AREAS WHICH ARE MISSING THE REQUIRED
 OVER RIDE DEVICES, OR OTHER TYPE DEVICES REQUIRED FOR
 CONTROL OF LIGHTING.
 PLEASE SEE SEVERAL LOCATIONS WHICH LIGHTING CONTROL IS
 REQUIRED FOR AREAS IN WHICH THE OCCUPANT CAN SEE THE
 LIGHTING WHICH IS BEING CONTROLLED.
 PLEASE SEE THE NORTH-SIDE ENTRANCE INTO THE 15TH FLOOR
 WHICH SHOWS NO CONTROL.
 PLEASE SEE THE SOUTH-SIDE ENTRANCE ON THE 16TH FLOOR
 WHICH SHOWS NO CONTROL.
 PLEASE SEE SEVERAL ROOMS WHICH CONTAIN ONLY A STANDARD
 WALL SWITCH.
 PLEASE SEE THE DETAIL FOR EACH CONTROL PANEL DOES NOT
 PROVIDE ENOUGH DETAILS FOR PROPOSED SYSTEM AND OVER
 RIDES.
 PLEASE SEE THAT NO MAXIMUM TIMES FOR OVER RIDES ARE
 STATED ON LEGEND.
 PLEASE SEE THAT NO CONTROLS ARE SHOWN FOR NUMEROUS
 LOCATIONS OF ACCENT LIGHTING.
 PLEASE SEE THAT THE CIRCUITING SHOWN ON THE LIGHTING
 CONTROL PANELS DO NOT CORRELATE WITH THE PLANS AS THERE
 ARE SEVERAL LIGHTING CIRCUITS ON PLANS NOT ON THE LCP.
 PLEASE SEE THAT THE LIGHTING WHICH IS BEING SHOWN UNDER
 A SEPARATE VOLTAGE OTHER THAN THE 277/480V WILL BE
 REQUIRED TO BE UNDER SEPARATE SYSTEM YET TO BE SHOWN.
 PLEASE SEE THAT THE LIGHTING SHOWN ON PLANS DO NOT
 CORRELATE WITH THE SUBMITTED ENERGY CALCULATIONS
 SUBMITTED FOR THE NUMBER OF FIXTURES, THE TYPE OF
 FIXTURES, THE WATTAGE ON THE FIXTURES ETC. THERE WERE
 ONLY TWO TYPES OF FIXTURES ON THE ENERGY CALCULATIONS
 SUBMITTED WHEN THERE IS AS MANY AS 20+ DIFFERENT TYPES
 OF FIXTURES?
 PLEASE INDICATE THE ZONES WHERE APPLICABLE.
 PLEASE SEE THE SQUARE FOOT LIMITS. PLEASE SEE THE
 ENERGY CALCULATIONS INDICATE A TOTAL OF 21,425 SQ. FT
 AND THE PLANS INDICATE A TOTAL OF 25,157 SQ FT PER
 FLOOR. PLEASE COORDINATE PLANS AND CALCULATIONS. PLEASE
 SEE BATHROOMS DO NOT PROVIDE DEVICES FOR SAFE COVERAGE
 FOR CONTROL OF LIGHTING.
  
 ** PLEASE KNOW THAT DUE TO NUMEROUS ITEMS FOR CHAPTER
 13 COMPLIANCE, A FULL REVIEW OF ALL SYSTEMS AND DEVICES
 CAN NOT BE DONE AT THIS TIME.
  
 5) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS
 FOR THE IT ROOM EQUIPMENT.
 PLEASE SEE MISSING DISCONNECTING MEANS FOR POWER OF ALL
 PER 645.10.
 PLEASE SUBMIT INFORMATION FOR THE TWO SYSTEMS WHICH
 APPEAR TO SHOW SOME SORT OF SHUNT TRIP BUT NOT SURE HOW
 THIS PROPOSED SYSTEM DEVICES ARE BEING INSTALLED TO
 PROVIDE THIS SHUNT OF ALL REQUIRED.
 **PLEASE SEE REVIEW COMMENTS FROM OTHER TRADES WHICH
 MAY AFFECT PLANS WITH RESPECT TO RATING OF WALLS, ROOM,
 ETC. PLEASE SEE NFPA-75
 FBC 106.1.2, NEC 90.7, 110.3
  
 6) NOTE: PLEASE PROVIDE THE PHOTO-METRICS FOR STAIR
 AREAS ( NOT EXIT STAIR TOWERS) IN THE SPACE FROM 16TH
 FLOOR TO THE 15TH FLOOR. PLEASE SEE NFPA-101 7.8.1.3,
 7.9.2.2.
  
 7) NOTE: PLEASE SEE SHEET E2.1 WHICH INDICATES LIGHTING
 FOR FLOOR 17? THIS SEEMS TO BE A MISPRINT WHICH SHOULD
 READ 15TH FLOOR AS SHOWN ON PLANS.
 FBC 106.1.2
  
 8) NOTE: PLEASE PROVIDE ALL ROOM ARE AREA DESIGNATIONS
 ON PLANS AND COMPLETE PANEL SCHEDULES TO COORDINATE
 WITH THE NUMERICAL OR NAME DESIGNATIONS FOR THESE ROOMS
 AND AREAS. PLEASE SEE THE FOLLOWING TEXT WHICH IS
 EXTRACTED DIRECTLY FROM THE NEC 408.4.
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO
 REQUIRE THAT THE IDENTIFICATION FOR EVERY CIRCUIT
 SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND
 CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE
 CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE
 MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE,
 SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN
 THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS.
 IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH
 CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE
 IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING
 ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP
 RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES
 CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR
 ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL
 REQUIRED BY THIS SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 9) NOTE: PLEASE PROVIDE INFORMATION ON DOOR CLOSURES
 WHICH ARE REQUIRED TO MEET NFPA-101 7.2.1.5
  
 10) NOTE: PLEASE SUBMIT AND COMPLETE THE PANEL
 SCHEDULE(S) LOAD CALCULATIONS ON PLANS. PLEASE INCLUDE
 ALL CONTINUOUS LOADS AT 125%. PLEASE KNOW THAT ANY
 ELECTRICAL WATER HEATERS UNDER THE 2005 NEC ARE NOW
 ALSO REQUIRED TO BE SHOWN AT 125%. 422.13
 220.12, 220.14, 220.42, 220.44 ETC.
 PLEASE SEE SOME OF THE ELECTRICAL PANELS ARE BLANK AT
 THIS TIME, OR ONLY SOME LOADS ARE SHOWN ON PANELS.
 PLEASE COMPLETE.
 FBC 106.3.5.1.2
  
 11) NOTE: PLEASE PROVIDE GROUNDING ATTACHMENT AND
 CONDUCTOR SIZES FOR THE NEW TRANSFORMERS.
 250.50, 250.66, 250.20,250.30
  
 12) NOTE: PLEASE SEE THE PLANS DO NOT INDICATE ANY
 SIZES FOR THESE NEW TRANSFORMER AND SEVERAL ITEMS TO
 REVIEW FOR ELECTRICAL CODE COMPLIANCE CAN NOT BE DONE
 AT THIS TIME.
 PLEASE COMPLETE.
 FBC 106.3.5.1.2
  
 13) NOTE: PLEASE SEE 422.17 FOR WATER HEATERS WHICH MAY
 NOT BE IN STORAGE ROOM LOCATIONS ALONG WITH
 COMBUSTIBLES AND EASILY IGNITABLE MATERIALS. PLEASE SEE
 THE CODE REQUIRES SEPARATION OF THESE ITEMS. PLEASE
 ADJUST PLANS ACCORDINGLY.
  
 14) NOTE: PLEASE OBTAIN THE MOST RECENT REVISED RISER
 DIAGRAM FOR THE BASE BUILDING AS IT IS CURRENTLY SHOWN
 ON PLANS, DOES NOT MATCH.
 FBC 106.1.2
  
 15) NOTE: PLEASE INDICATE HOW THE CONDUCTORS ARE RUN,
 SIZED AND CONNECTED TO THE IT EQUIPMENT.
 PER 645.5
  
 16) NOTE: PLEASE INDICATE THE AIC RATINGS FOR ALL NEW
 ELECTRICAL SERVICE EQUIPMENT.
 110.9, FBC 106.1.2
  
 17) NOTE: PLEASE CLARIFY THE KITCHEN AREA WHICH
 CONTAINS A *HOT/DISP* NOTE? WHAT IS THIS?
 FBC 106.1.2
  
 18) NOTE: PLEASE INDICATE IF THERE ARE ANY WATER
 HEATING UNITS FOR KITCHEN AREA ?
  
 19) NOTE: PLEASE CLARIFY THE PANEL L16, AND L16C AS MCB
 PANELS. THIS IS PERMITTED HOWEVER NOT CLEAR?
 ONLY NOTED AS PLANS DO NOT NEED TO BE REVISED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-04-19 10:48:46REVIEW COMMENCED ON 4/19