| 2007-06-06 16:46:06 | BUILDING PLAN REVIEW |
| | PERMIT: 07030932 |
| | ADD: 525 OKEECHOBEE BLVD PENTHOUSE A & B |
| | CONT: CENTEX |
| | TEL: (954)214-9415 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3)Y J ARCHITECTURAL DESIGN WILL REQUIRE A CERTIFICATE |
| | OF AUTHORIZATION,) 481.219 F.S.CERTIFICATE OF |
| | AUTHORIZATION.THE TITLE BLOCK FOR ANY |
| | SHEET BEARING THE NAME OF AN ARCHITECT PRACTICING UNDER |
| | A FICTITIOUS NAME, A CORPORATION, OR A PARTNERSHIP, |
| | OFFERING ARCHITECTURAL SERVICES, SHALL INCLUDE |
| | THE CERTIFICATE OF AUTHORIZATION NUMBER.ADD THE |
| | NUMBER TO EACH SHEET. |
| | |
| | 4)STRUCTURAL SHEET S-1 WILL REQUIRE A RAISED |
| | IMPRESSION TYPE SEAL NOT A STAMPED SEAL. FAC |
| | 61G15-23.001 THE SEAL IS ALSO A CALIFORNIA SEAL THE |
| | DESIGN PROFESSIONAL MUST BE A LICENSED ENGINEER IN THE |
| | STATE OF FLORIDA. 471.025 |
| | |
| | 5) THE SAME HOLDS TRUE FOR THECALCULATIONS SUBMITTED |
| | FOR THE STAIRS BETWEEN THE 15TH & 16TH FLOOR. MUST BE A |
| | LICENSED ENGINEER FOR THE STATE OF FLORIDA AND |
| | IF THE ENGINEER OF RECORD DOES NOT SEAL EACH SHEET THEN |
| | A SEALED COVER SHEET LISTING HOW MANY PAGES ARE COVERED |
| | UNDER THIS SEAL. 61G15-23.002. |
| | |
| | 6) LS-01 / LS-02 PLEASE UPDATE APPLICABLE CODE TO THE |
| | 2004FBC W 2006 AMENDMENTS, PLEASE CORRECT. |
| | |
| | 7) LS-01 BOTTOM RIGHT OF SHEET THERE IS A DISCREPANCY |
| | IN ONE AREA THE PLAN INDICATES THIS SHEET REPRESENTS |
| | THE 15TH FLOOR WHILE LESS THAN SIX INCHES AWAY THE |
| | PLAN |
| | |
| | INDICATES WORK ON THE 16TH FLOOR, PLEASE CORRECT. |
| | |
| | 8)SHEET I-G.1 PLEASE CORRECT THE REFERENCES MADE TO |
| | EITHER THE LOS ANGLES BUILDING CODE OR THE UBC AND CODE |
| | REFERENCE NUMBERS. |
| | |
| | 9) SHEET 1-16C THE 2 AREAS THAT ARE CONSIDERED AS |
| | ATRIUMS DO NOT HAVE RATED WALLS NOR DOORS, PLEASE |
| | COMPLY WITH: |
| | 404.5 ENCLOSURE OF ATRIUMS. |
| | ATRIUM SPACES SHALL BE SEPARATED FROM ADJACENT SPACES |
| | BY A 1-HOUR FIRE BARRIER WALL. |
| | EXCEPTIONS: |
| | 1.A GLASS WALL FORMING A SMOKE PARTITION WHERE |
| | AUTOMATIC SPRINKLERS ARE SPACED 6 FEET (1829 MM) OR |
| | LESS ALONG BOTH SIDES OF THE SEPARATION WALL, OR ON THE |
| | ROOM SIDE ONLY IF THERE IS NOT A WALKWAY ON THE ATRIUM |
| | SIDE, AND BETWEEN 4 INCHES AND 12 INCHES (102 MM AND |
| | 305 MM) AWAY FROM THE GLASS AND SO DESIGNED THAT THE |
| | ENTIRE SURFACE OF THE GLASS IS WET UPON ACTIVATION OF |
| | THE SPRINKLER SYSTEM. THE GLASS SHALL BE INSTALLED IN A |
| | GASKETED FRAME SO THAT THE FRAMING SYSTEM DEFLECTS |
| | WITHOUT BREAKING (LOADING) THE GLASS BEFORE THE |
| | SPRINKLER SYSTEM OPERATES. |
| | 2.A GLASS-BLOCK WALL ASSEMBLY IN ACCORDANCE WITH |
| | SECTION 2110 AND HAVING A ?-HOUR FIRE PROTECTION |
| | RATING. |
| | 3.THE ADJACENT SPACES OF ANY THREE FLOORS OF THE |
| | ATRIUM SHALL NOT BE REQUIRED TO BE SEPARATED FROM THE |
| | ATRIUM WHERE SUCH SPACES ARE INCLUDED IN COMPUTING THE |
| | ATRIUM VOLUME FOR THE DESIGN OF THE SMOKE CONTROL |
| | SYSTEM. |
| | |
| | 10) SHEET 1-16C INDICATE TWO TYPE OF DOORS THAT WILL BE |
| | PENETRATING THE 1 HR RATED WALL DOOR TYPED-6 WHICH DOES |
| | HAVE 45 MINUTE RATING AND DOOR TYPE D-3 WHICH DOES NOT |
| | PLEASE CORRECT. TABLE 715.3. |
| | |
| | 11)PLEASE TAKE NOTE OF : 404.7 INTERIOR FINISH. THE |
| | INTERIOR FINISH OF WALLS AND CEILINGS OF THE ATRIUM |
| | SHALL NOT BE LESS THAN CLASS B WITH NO REDUCTION IN |
| | CLASS FOR SPRINKLER PROTECTION. |
| | |
| | 12)SHEET 1-15C DOES INDICATE THE 1 HR RATED |
| | PARTITIONS AT THE ATRIUM AREAS BUT THERE IS NO DOOR |
| | SHEDULE IF TAKEN FROM SHEET 1-16.C D-3 IS NOT RATED |
| | PLEASE CORRECT. |
| | |
| | 13) PLEASE REVIEW LS-02 THE NORTHEAST CORNER OF THE |
| | BUILDING INDICATES THE DISTANCE TO AN EXIT AS 204 FT. |
| | 404.8 TRAVEL DISTANCE, THE SOUTHEAST CORNER THIS |
| | DISTANCE WILL BE GREATER. IN OTHER THAN THE LOWEST |
| | LEVEL OF THE ATRIUM , WHERE THE REQUIRED MEANS OF |
| | EGRESS IS THROUGH THE ATRIUM SPACE, THE PORTION OF EXIT |
| | ACCESS TRAVEL DISTANCE WITHIN THE ATRIUM SPACE SHALL |
| | NOT EXCEED 200 FEET . |
| | |
| | 14) 7-06-07 THIS COMMENT HAS BEEN RESOLVED, NO SMOKE |
| | CONTROL WILL BE REQUIRED, SINCE NOT PAT OF AN MEANS OF |
| | EGRESS, SEE 404EXCEPTIONS, 707.2 EXCEPTION # 7. |
| | |
| | |
| | |
| | 15) THERE IS A DISCREPANCY IN THE PLANS THE |
| | ARCHITECTURAL , STRUCTURAL, ELECTRICAL AND FIRE ALARM |
| | ALL INDICATE WORK ON THE 15THAND 16TH FLOORS, WHERE |
| | AS THE |
| | FIRE SPRINKLER AND MECHANICAL PLANS INDICATE THE 17TH |
| | AND 18TH FLOORS. PLEASE CORRECT. |
| | |
| | 16)PLEASE PROVIDE ADDTIONAL INFORMATION ON THE GLASS |
| | HANDRAILS AND GUARDS SEE 2407. |
| | 2407.1.1 LOADS. |
| | THE PANELS AND THEIR SUPPORT SYSTEM SHALL BE DESIGNED |
| | TO WITHSTAND THE LOADS SPECIFIED IN SECTION 1607.7 . A |
| | SAFETY FACTOR OF FOUR SHALL BE USED. |
| | |
| | 2407.1.2 SUPPORT. |
| | EACH HANDRAIL OR GUARD SECTION SHALL BE SUPPORTED BY A |
| | MINIMUM OF THREE GLASS BALUSTERS OR SHALL BE OTHERWISE |
| | SUPPORTED TO REMAIN IN PLACE SHOULD ONE BALUSTER PANEL |
| | FAIL. GLASS BALUSTERS SHALL NOT BE INSTALLED WITHOUT AN |
| | ATTACHED HANDRAIL OR GUARD. |
| | |
| | 17)PLEASE PROVIDE AT WHAT SLOPE IN DEGREES THE GLASS |
| | WALL IS FROMVERTICAL, IF THE SLOPE IS MORE THAN 15 |
| | DEGREES SEE 2405.2 . |
| | |
| | 18) THE GLASS WALL IS ALSO CONSIDERED A HAZARDOUS |
| | LOCATION 15TH AND 16TH FLOORS. SEE 2406.3(7) |
| | 7.GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE |
| | PANEL, OTHER THAN IN THOSE LOCATIONS DESCRIBED IN |
| | PRECEDING ITEMS 5 AND 6, WHICH MEETS ALL OF THE |
| | FOLLOWING CONDITIONS: |
| | 7.1.EXPOSED AREA OF AN INDIVIDUAL PANE GREATER |
| | THAN 9 SQUARE FEET (0.84 M 2 ); |
| | 7.2.EXPOSED BOTTOM EDGE LESS THAN 18 INCHES (457 |
| | MM) ABOVE THE FLOOR; |
| | 7.3.EXPOSED TOP EDGE GREATER THAN 36 INCHES (914 |
| | MM) ABOVE THE FLOOR; AND |
| | 7.4.ONE OR MORE WALKING SURFACE(S) WITHIN 36 |
| | INCHES (914 MM) HORIZONTALLY OF THE PLANE OF THE |
| | GLAZING. |
| | EXCEPTION: SAFETY GLAZING FOR ITEM 7 IS NOT REQUIRED |
| | FOR THE FOLLOWING INSTALLATIONS: |
| | 1.A PROTECTIVE BAR 1? INCHES (38 MM) OR MORE IN |
| | HEIGHT, CAPABLE OF WITHSTANDING A HORIZONTAL LOAD OF 50 |
| | POUNDS PLF (730 N/M) WITHOUT CONTACTING THE GLASS, IS |
| | INSTALLED ON THE ACCESSIBLE SIDES OF THE GLAZING 34 |
| | INCHES TO 38 INCHES (864 MM TO 965 MM) ABOVE THE |
| | FLOOR. |
| | |
| | |
| | 19) SHEET I-E.2 STAIRWELL SECTION THE HANDRAIL AT THE |
| | TOP LANDING IS MISSING : 11-4.9.4(2) IF HANDRAILS ARE |
| | NOT CONTINUOUS, THEY SHALL EXTEND AT LEAST 12 INCHES |
| | (305 MM) BEYOND THE TOP RISER AND AT LEAST 12 INCHES |
| | (305 MM) PLUS THE WIDTH OF ONE TREAD BEYOND THE BOTTOM |
| | RISER. AT THE TOP, THE EXTENSION SHALL BE PARALLEL WITH |
| | THE FLOOR OR GROUND SURFACE. AT THE BOTTOM, THE |
| | HANDRAIL SHALL CONTINUE TO SLOPE FOR A DISTANCE OF THE |
| | WIDTH OF ONE TREAD FROM THE BOTTOM RISER; THE REMAINDER |
| | OF THE EXTENSION SHALL BE HORIZONTAL [SEE FIGURE 19 (C) |
| | AND FIGURE 19 (D)]. HANDRAIL EXTENSIONS SHALL COMPLY |
| | WITH SECTION 11-4.4 . |
| | |
| | 20) SHEET I-E.2 HANDRAILS: 11-4.9.4(5) TOP OF HANDRAIL |
| | GRIPPING SURFACE SHALL BE MOUNTED BETWEEN 34 INCHES AND |
| | 38 INCHES (865 MM AND 965 MM) ABOVE STAIR NOSING. |
| | |
| | 21)PLANS DO NOT PROVIDE THE DISTANCE FROM THE |
| | VERTICAL GLASS GUARD RAILING AND THE HANDRAIL? |
| | 11-4.9.4(3) THE CLEAR SPACE BETWEEN HANDRAILS AND WALL |
| | SHALL BE 1?". |
| | |
| | 22) THE SAME STAIR ELEMENTS WILL NEED TO BE ADDRESSED |
| | ON THE NORTHWEST STAIR AND HAND RAILS AS LISTED IN |
| | ITEMS 19-21, THE CUT SECTIONS OF THIS STAIRARE NOT |
| | CLEAR AND THESE ITEMS CAN NOT BE VISSIBLY ADDRESSED. |
| | |
| | 23)ARE THE SKYLIGHTS PART OF THIS PERMIT OR ARE THEY |
| | PART OF THE SHELL BUILDING? IF PART OF THIS PERMIT THE |
| | FOLLOWING WILL BE REQUIRED: FL BLD CODE 1609.1.4: |
| | COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT |
| | INSPECTOR) OF PRODUCT TESTING REPORTS,MISSING REPORTS |
| | ARE AS |
| | FOLLOWS: A ) SKYLIGHTS |
| | |
| | 23A)PRODUCT APPROVALS SUBMITTED WITH PERMIT |
| | APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO |
| | COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE SEE THE |
| | STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 23B)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |